2500 kVA Mai Canjawa-0.6 / 13.8 kV|Amurka 2025

2500 kVA Mai Canjawa-0.6 / 13.8 kV|Amurka 2025

Kasar: Amurka 2025
Yawan aiki: 2500 kVA
Wutar lantarki: 13.8GrdY/7.97-0.6Y/0.346kV
Siffar: tare da keɓewar allo grounding hannun riga
Aika Aikace-aikacen

 

 

image001

Ƙarfin da Ba a Gani, Tsaron da Ba a Daidaita ba: Kushin Mu{0}}Maganin Canja-canje.

 

 

01 Gabaɗaya

1.1 Bayanin Aikin

2500 kVA three phase pad mounted transformer an isar da ita zuwa Kanada a shekarar 2025. Ƙarfin wutar lantarkin shine 2500 kVA tare da sanyaya KNAN. Babban ƙarfin lantarki shine 13.8GRDY / 7.97 kV tare da ± 2 * 2.5% tapping range (NLTC), ƙananan ƙarfin lantarki shine 0.6Y / 0.346 kV, sun kafa ƙungiyar vector na YNyn0.

Muna alfahari da gabatar da wannan kundi mai nauyin 2500kVA{1}mai na'ura mai ɗaukar wuta, wanda ya haɗu da inganci, aminci, da dorewar muhalli, wanda ya sa ya dace da rarraba wutar lantarki na birni, kasuwanci, da aikace-aikacen masana'antu. Samfurin ya bi ka'idodin ingancin makamashi na DOE 2016, yana samun ingantaccen inganci har zuwa 99.53%. Yana amfani da yanayin muhalli FR3® na halitta ester insulating mai, yana ba da babban kariya ta wuta (class K4) da biodegradability. Kyawawan aikin zafi da sarrafa hawan zafin jiki yana tabbatar da kwanciyar hankali na tsawon lokaci.

A babban - ƙarfin lantarki, yana fasalta 600A hadedde plug{2} a cikin daji, sanye take da bushing pocelain tsaka tsaki da haɗa nau'in sandunan tagulla guda biyu{3}}rami{4}, yana samar da amintattun haɗin gwiwa. Ƙarƙashin gefen wutar lantarki yana da sanye take da guduro{7}} simintin simintin gyare-gyare da manyan sandunan tagulla guda goma{9}, yana tabbatar da ingantaccen gini da shigarwa cikin sauƙi. Ƙirƙirar ƙirar gefe{11}}yana adana sarari kuma ya zo cikakke tare da cikakkun sandunan haɗin gwiwa da murfin kariya, yana tabbatar da amincin aiki. Bugu da ƙari, an haɗa bushings na ƙasa guda biyu don allon ƙasa tsakanin babban ƙarfin lantarki da ƙarancin ƙarfin lantarki da kuma ƙasa mai tsaka tsaki, suna ba da cikakkiyar ƙira don biyan buƙatun ƙasa daban-daban.

Rukunin ya haɗa na'urori guda biyu{0}matsayi masu ɗaukar nauyi, masu kama uku, tsarin garkuwar ƙasa, da tsarin shinge na nitrogen, yana ba da cikakkiyar kariya da sassauƙan aiki. Wannan naúrar kyakkyawan zaɓi ne don ginin grid na wutar lantarki na zamani, yana ba da ingantaccen inganci, aminci, da aminci.

 

 

 

1.2 Ƙayyadaddun Fasaha

2500 kVA kushin da aka ɗora nau'in ƙayyadaddun bayanai da takaddun bayanai

Isarwa zuwa
Amurka
Shekara
2025
Nau'in
Tashin wutar lantarki
Daidaitawa
IEEE C57.12.34
Ƙarfin Ƙarfi
2500 kVA
Yawanci
60HZ
Mataki
3
Ciyarwa
Madauki
Gaba
Matattu
Nau'in Sanyi
KNAN
Babban Voltage
13.8GRDY/7.97kV
Na biyu Voltage
0.6Y/0.346 kV
Abubuwan Iska
Aluminum
Matsala ta kusurwa
YNyn0
Impedance
5.75%
Matsa Canji
Farashin NLTC
Taɓa Range
±2*2.5%
Babu Asara Load
2.4 kW
Akan Rasa Load
15.79 kW

 

1.3 Zane

2500 kVA kushin da aka ɗora zane da girman hoto.

image003 image005

 

 

02 Masana'antu

2.1 Kori

Wannan 2500kVA pad -wanda aka ɗora tafsiri yana da fasalin silikon ƙarfe na ƙarfe mai inganci-mai inganci{1} Zane-zanen kafa guda biyar- yana rage ƙin yarda sosai kuma babu -asara, tare da rage yawan zubar ruwan maganadisu da abun ciki mai jituwa a cikin ainihin. Ƙarin gaɓoɓin gaɓoɓin gefen biyu suna aiki azaman ƙaramar hanyar rashin ƙarfi don na uku{12}} jigila masu jituwa, ta haka ne ke danne murguɗin igiyar wutar lantarki da kuma tabbatar da ingantaccen fitarwa mai inganci. Mahimmancin yana nuna kyakkyawan yanayin maganadisu da kwanciyar hankali na inji, mai iya jurewa gajeriyar tasirin kewayawa da rage hayaniyar aiki. Wannan ƙaƙƙarfan ƙira yana ba da ƙwaƙƙwaran tushe don aikin transfoma yana da inganci, santsi, da ƙarancin aiki-asara.

image007

 

2.2 Guda

image009

Ƙarƙashin wutar lantarki - yana ɗaukar tsarin jujjuyawar foil, kuma foil ɗin yana da kyawawan halayen wutar lantarki, wanda zai iya haɓaka ingancin watsawa na yanzu; babban ƙarfin wutar lantarki - yana da tsarin rauni na waya -, wanda zai iya biyan buƙatun watsa wutar lantarki mai girma -. Babban da ƙananan sassa na iska an gyara su kuma an matsa su ta faranti na karfe. Tare da tsayin daka na faranti na karfe, ana tabbatar da iska don kula da tsayayyen tsari da tsari yayin aiki da amfani na gaba. Bayan kafa, ana iya cire faranti na karfe, ta yadda iska ta dace da buƙatun taro na gaba ɗaya kuma yana tabbatar da aikin lantarki da kwanciyar hankali na injin.

 

2.3 Tanko

An gina tankin ne daga lalata{0}}ƙarfe mai juriya kuma yana da cikakkiyar ƙira, ƙarancin ƙira. An gama shi a cikin Green Equipment (Munsell 9 GY 1.5/2.6), yana ba da dorewa da kariya ta lalata. Cike da ruwan ester na halitta na FR3® don ingantaccen sanyaya da amincin gobara, tankin yana fuskantar ɗigo mai tsauri{8}}gwajin hujja don tabbatar da dorewar dogon lokaci- cikin mahalli masu buƙata.

image011

 

2.4 Taron Karshe

image013

Haɗin ƙarshe na wannan kushin{0} da aka ɗora tafsiri yana farawa tare da haɗa ɓangaren da ke aiki: iskar tana hawa daidai ginshiƙan ginshiƙan, sannan a saka manyan laminations na karkiya don kammala da'irar maganadisu. Dukkan abubuwan taimako, gami da bushings, masu canza famfo, da na'urorin kariya, ana shigar dasu kuma a haɗa su cikin aminci. A ƙarshe, an cika tankin a hankali tare da FR3® na ester insulating ruwa a ƙarƙashin yanayin injin da aka sarrafa don tabbatar da cikawa da kawar da iska, yana ba da garantin ingantacciyar wutar lantarki da aikin zafi a duk rayuwar sabis ɗin sa.

 

 

03 Gwaji

A'a.

Gwajin Abun

Naúrar

Dabi'un Karɓa

Ƙimar Ma'auni

Kammalawa

1

Ma'aunin Juriya

%

Matsakaicin juriya rashin daidaituwa

4.05

Wuce

2

Gwajin Rabo

%

Bambancin rabon ƙarfin lantarki akan babban tapping: ƙasa da ko daidai da 0.5%

Alamar haɗi: YNyn0

-0.03% ~- 0.02%

Wuce

3

zango{0}}gwajin dangantaka

/

YNyn0

YNyn0

Wuce

4

A'a -asara da tashin hankali na halin yanzu

/

I0 :: bayar da ma'auni darajar

0.22%

Wuce

P0: bayar da ƙima (t:20 digiri)

2.192 kW

juriyar rashin hasara shine +10%

/

5

Load asarar impedance ƙarfin lantarki da inganci

/

t:85 ku

haƙuri ga impedance shine ± 7.5%

juriyar jimlar asarar kaya shine +6%

/

Wuce

合格

Z%: ƙimar da aka auna

5.70%

Pk: ƙimar ƙima

15.158 kW

Pt: ƙima mai ƙima

17.350 kW

Ingancin ba kasa da 99.53%

99.55%

6

Gwajin Karfin Wutar Lantarki

kV

LV/低压: 10kV 60s

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

7

Jarrabawar Juriya da Wutar Lantarki

kV

Wutar lantarki mai aiki (KV):2Ur

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

Duration(s):48

Mitar (HZ): 150

8

Gwajin Leaka

kPa

Aiwatar da matsa lamba: 50kPA

Babu yabo kuma babu

Lalacewa

Wuce

Tsawon lokaci:24h

9

Ma'aunin Resistance Insulation

HV{0}LV zuwa Ground:

1.22

/

LV -HV zuwa Ground:

1.45

HV&LV zuwa Ground

0.758

10

Gwajin bugun walƙiya

kV

cikakken igiyar ruwa

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

 

image015

20251029153638493177

 

 

04 Shiryawa da jigilar kaya

4.1 Shiryawa

Wannan 2500kVA pad -wanda aka ɗora tafsiri yana cikin tsaro cikin tsari na al'ada{2}}gina na katako, yana tabbatar da cikakken kariya yayin sufuri da ajiya. Gaba dayan taron an lullube shi a cikin shingen katako mai ƙarfi wanda aka yi masa jeri tare da shingaye masu juriya da kayan kwantar da hankali don hana fallasa ga zafi da tasirin jiki. Abubuwan da ke da mahimmanci kamar bushings da gauges an rufe su da keɓaɓɓun garkuwar kariya. Ana amfani da takalmin gyaran kafa na ciki da tsarin ɗaure don hana motsi. Fakitin ya dace da ƙa'idodin jigilar kaya na ƙasashen duniya da fasalulluka bayyanannun alamun waje da umarnin kulawa don isar da lafiya da sauƙi akan- ganowa da shigarwa.

 

4.2 Shipping

Za a kai taransfoma a ƙarƙashin sharuɗɗan DDU (Ba a biya ba) zuwa wurin da aka nufa. Mai sayarwa yana kula da duk shirye-shiryen sufuri da farashi zuwa ƙayyadadden adireshin, gami da hanyoyin fitarwa da jigilar kayayyaki na ruwa/kasa, yayin da mai siye ke da alhakin ƙaddamar da shigo da kaya, haraji, haraji, da saukewa na ƙarshe a wurin da aka nufa. A duk lokacin wucewa, za a kula da jigilar kayayyaki don tabbatar da kariyar injiniya da muhalli, kuma da isowa, mai karɓa zai tabbatar da amincin marufi da kayan aiki.

 

05 Yanar Gizo da Takaitawa

Wannan na'urar taswira tana haɗa ingantaccen ingantaccen makamashi, dorewar muhalli, da ingantaccen abin dogaro don biyan buƙatun buƙatun hanyoyin rarraba wutar lantarki na zamani. Tare da na musamman aikin aminci na wuta da kuma tsawaita rayuwar sabis, yana tabbatar da ci gaba da ingantaccen samar da wutar lantarki yayin rage farashin aiki da kulawa. Tsarin tsari na ɗan adam da cikakken tsarin kariya yana haɓaka sauƙin shigarwa da rage tasirin muhalli. Mun himmatu wajen isar da amintattun mafita don yanayin rarrabawa da yawa ta hanyar fasahar ci gaba da masana'anta masu tsauri, suna ba da gudummawa ga mafi wayo da haɓaka kayan aikin lantarki.