Karfin: 650kva
Voltage: 11000 / 340V
Fasalin: tare da shinge IP20
Aika Aikace-aikacen

Jiantagshan Scotech Wutar lantarki Co., Ltd yana daya daga cikin manyan masana'antun masana'antu da masu siyarwa na 650 KVA Cast COILSSMERMERS Saudi Arabia Emirates 2025 a China. Da fatan za a sami kyauta don siyan samfuran farashi mai inganci daga masana'antarmu. Don zane, tuntuɓi Amurka yanzu.

 

image001

Energyarfin ƙarfi ga kowane aikace-aikacen - ► Zaɓi Scotech Cast Coil Transformers

 

 

Janar 01

1.1 Bayanin aikin

Kaka 650 KVA bata resin bushe {{1} Canza Nazarin Nazari (CRT) yana ba da madaidaiciyar ƙarfi don matsakaici Bi ka'idojin IC. Featuring wani abin da aka shigar na wutar lantarki na 11kv da fitowar wutar lantarki 0.34 kV, tare da ƙimar wutar lantarki na 650 KVA. Featuring a hatsi- up da aka daidaita silibon na siliki da jan ƙarfe, mai canzawa yana aiki cikin aminci yayin da tabbatar da rayuwar dogon lokaci. Kungiyar vector Vector na YD11 na ba da tsaka tsaki da tsaka tsaki da daidaito uku {10} uture, tallafawa wadataccen lokaci.

Mai canzawa yana amfani da A / anima da f {{0} lafazin aji, yana ba da damar yin aiki a ƙarƙashin launuka daban-daban. Babu- asarar saukarwa shine 1.25 kW da hasara na kaya shine 7.3 KW, wanda ke taimakawa rage yawan kuzari. NLTC (A'a - ► Zaɓi Matsa) tare da ± 2 × 2.5% Gyarawa yana kiyaye fitarwa na ƙwayoyin cuta.

 

 

 

Bayanan Fasaha

650kva resin simintin busassun zane mai canzawa da kuma takardar bayanai

Isar da shi
Saudi Arab Emirates
Shekara
2025
Iri
Resin simintin simintin simintin
Core kayan
Hatsi da aka haɗa silicon karfe
Na misali
Kai
Iko da aka kimanta
650kva
Firta
50Hz
Zamani
Uku
Kungiyar vector
Yd11
Nau'in sanyaya sanyaya
A / AF
Na farko
11K
Sakandare
0.34 KV
Winding abu
Jan ƙarfe
Wanda ba a sani ba
6%
Matsa Canja
Nlc
Faɗakarwa
±2-A2.5.5BJIRAY VLATAGE
Babu asarar kaya
1.25 kw
A kan asarar kaya
7.3 KW
Matakin rufi
F
Kaya
Mai sarrafa zafi, magoya baya mai sanyaya, wurin shinge

 

 

1.3 zane-zane

650kva resin simintin canza canjin canjin canjin canzawa da cikakkun bayanai

image003 image005

 

 

Kafa 02

2.1 Core

Core na bushe -} Mai watsa sauti na nau'in an yi shi da hatsi {{1} +} +} orfuded silicon karfe zanen gado. Yana amfani da mataki {3} ir} ir}} ign haɗin gwiwa tare da digiri 45, rami-} la laminations. Wannan ƙirar ƙasa babu- asarar nauyin kaya kuma yana rage amo. Mai canjin yana gudana cikin barga da hanya mai shiru.

 

2.2 Murya mai iska

image007

Kewaye na 650 KVA COIL COIL COIL Transformers Coil an yi shi ne da babba {{1} Aiki da tagulla, samar da ƙarfi na injiniya da gajere {2} juriya na da'ira. Takeings amfani da aji f (155 digiri) rufin kuma suna epoxy {6} ya zama mai aminci da kuma m aikin da aiki.

 

2.3 IPO2

Mu na cikin gida mai bushe -} Transfors na nau'in rufin: hana {asariyar kariya tare da abubuwa na ƙasƙanci, da kuma faɗakar da rayuwar waje, da kuma haɓaka rayuwar kuɗaɗe, da kuma haɓaka rayuwar ta waje, da kuma haɓaka rayuwar ta waje, da kuma haɓaka rayuwar ta waje, da kuma haɓaka rayuwar ta waje, da kuma haɓaka rayuwar kuɗaɗe, da kuma faɗakar da rayuwar kuɗaɗe, da kuma haɓaka rayuwar ta waje. Sauraren rufewa kuma yana rage hayaniya da haɓaka aikin ta'aziyya na cikin gida. Tsarinsa na farfadowa da ingantaccen tsarin suna ba abokan ciniki da amintaccen, abin dogaro, da sauƙi- {kula da rarraba wutar lantarki.

image009

 

2.4 Babban taro

image011

A yayin taro, kowane mai bushe- Mai watsa sauti na nau'in zazzabi da kuma lokutan zazzabi na PT100. Waɗannan lura da yanayin zafi na iska a cikin ainihin lokaci kuma nuna su akan allon dijital. Araba shida- entoly fans fans ficing da lalacewa zafi da tabbatar da tsawo {{6} {Action aiki. Kowane samfur ya yi fama da ayyukan gaske da yawa da gwaje-gwaje yayin tsarin masana'antu kuma an sake dubawa sosai kafin jigilar kaya. Mun dage kan samar da abokan ciniki tare da amintattu, lafiya, da girma- asar aiki- bushe kwarewar aiki.

 

 

03 Gwaji

Gwajin daidaitaccen gwaji da gwajin yau da kullun

IEC 60076-1-2011 Transforers Power - Part 1: Janar
IEEC 60076-013 Transforers Power - Part 3: matakan rufi, gwaje-gwaje na siye da ruwa na waje a cikin iska
IEEC 60076-11-018 RLV Power Transformers - Part 11: Canjin Tan Canjin

1. Aunawa na juriya

2

3

4

5. Gwajin kayan karewa

6. Ingantaccen wutar lantarki da tsayayya da gwaji

7. Gwajin fitarwa

 

image013
image015

 

Sakamakon gwajin

A'a

Abu na gwaji

Guda ɗaya

Yarjejeniyar Yarjejeniya

Auna darajar

Ƙarshe

1

Aunawa na juriya na iska

/

Matsakaicin juriya da rashin daidaituwa

Layin juriya: kasa da ko daidai da 2%

HV (layi)

LV (Layi)

Wuce

0.19%

0.84%

2

Aunawa na tsaran wutar lantarki kuma duba gudun hijira na farko

/

Amincewa da ƙarfin lantarki a kan babban taping: ± 1/10

Alamar haɗin haɗin: YD11

0.02% ~ 0.17%

Yd11

Wuce

3

Aunawa gajere {{0} {ECRPECEWIX da rashi kaya

/

Kwat

Kwat

T: 120 digiri

Z%: darajar da aka auna

Pk: An auna darajar

PT: An auna darajar

6.09%

5.857

7.338

Wuce

4

Aunawa babu- asarar saukarwa da na yanzu a 90% da 110% na wutar lantarki

/

Kwat

I0 :: samar da darajar daraja

P0: samar da darajar daraja

90% ur

0.44

1.000

Wuce

100% ur

0.49

1.112

110% ur

0.53

1.223

5

Amfani da kayan lantarki

/

HV: 35kV 60s

LV: 3kv 60s

Ba a rushe wutar lantarki ba

Wuce

6

Jawo wutar lantarki da tsayayya da gwaji

/

Amfani da wutar lantarki (KV):

2 Ur

Jawo wutar lantarki (KV): 0.68

Tsari (s): 40

Mita (HZ): 150

Ba a rushe wutar lantarki ba

Wuce

7

Gwaji na gwaji

pC

Matsakaicin matakin 'yantar sakin gari zai zama 8 PC

<10

Wuce

 

 

04 tattara da jigilar kaya

4.1 tattarawa

1. Matakan kariya: mai canzawa yana a hankali tare da kayan kariya kamar kumfa don hana lalacewa yayin sufuri.

2. Katako na katako na katako: Ana sanya mai canzawa a cikin ƙarfi, katako mai ƙarfi na katako, tare da tube katako ƙarfafa daji don rage rawar jiki yayin sufuri.

3. An kulle crate na katako a kan katako na katako ko karfe.

4. Ya kamata a yiwa alama ta katako tare da alamomin gargajiya da kuma cibiyar nuna alama da kuma cibiyar da ke nuna nauyi.

5. Rufe saman crate na katako tare da danshi {{1} Jawp.

image017

 

4.2 Siyarwa

image019

1. Takardar da ta kawo ta kwashe jigilar kayayyakin sufuri, jigilar kaya, abin hawa don takaice nesa da iska, kuma don Allah kiyaye kayan aikin sufuri mai tsabta da bushe.

2. Ya kamata a yi amfani da iyakokin sufuri na sufuri kuma a sanya samfuran a tsaye, girgiza da rawar jiki da motsi za a hana.

3. Kayan haɗi da sassa da fito da fitowar - Takardun aikin za a kawo tare da mai canzawa.

4. Canji ba tare da kunshin ba a cikin kayan aikin sufuri ta trailer da clams da kuma murƙushe coil, insulator, farantin, farantin jiki a matsayin cutar da samfuran.

5. Karkashin mai canzawa bai wuce 300 lokacin sufuri ba.

6. Idan ana buƙatar sauya wuri ko a tashar jiragen ruwa, kar a tari karar, kuma a cikin ya kamata tsutsotsin da ke ƙasa da mai canzawa, tsayi ba ya wuce 100mm.

 

 

05 Site da taƙaitawa

Scotech 650 KVOST CIGABA GASKIYA {{1} ire} ire na keɓancewa da ikon aiki lafiya da aikace-aikacen masana'antu da kasuwanci. Tana da silicon na silibon da jan karfe gabaɗaya an rufe ta a cikin epoxy resin, ba da daɗewa ba {{3} Aiki ba tare da mai ba.

Canjin yana da ƙungiyar vector da kuma babu {{1} ► Zaɓi hoto Matsa (NlC) don kiyaye ƙarfin lantarki a ƙarƙashin canjin kaya. Inshoran A / A / agaji da kuma rufaffiyar fsasalin ba su ba da damar yin aiki lafiya a yanayin zafi. Low no - ►ari da kuma asarar kaya suna taimakawa rage amfani da makamashi.

IP2-2 shinge ya yi aminci da hana ƙura da abubuwa daga shiga. An gina -}} a na'urori masu sanyin jiki da magoya masu sanyaya suna taimaka wa transformer gudu.