75 kVA Kushin Dutsen Mai Canjawa-22.86 / 0.208 kV|Amurka 2024

75 kVA Kushin Dutsen Mai Canjawa-22.86 / 0.208 kV|Amurka 2024

Kasar: Amurka 2024
Yawan aiki: 75kVA
Wutar lantarki: 22.86/0.208kV
Feature: tare da IFD
Aika Aikace-aikacen

 

 

75 kva pad mount transformer with ifd

Ƙarfin ƙarfi mai ƙarfi, zaɓi mai wayo - Uku{0}Pad Pad{1}}Maɗaukakiyar Transformer yana tabbatar da ingancin kuzari da aminci!

 

01 Gabaɗaya

1.1 Fagen Aikin

An isar da tafsiri mai nauyin kVA 75 zuwa Amurka a cikin 2024. Ƙarfin wutar lantarkin shine 75 kVA tare da sanyaya ONAN. Babban ƙarfin lantarki shine 22.86GRDY / 13.2kV ​​tare da ± 2 * 2.5% tapping range (NLTC), ƙarfin lantarki na biyu shine 0.48y / 0.208kV, sun kafa ƙungiyar vector na YNyn0, kuma shine madaidaicin ciyarwa da matattarar gaba. Akwatin jikin na'ura mai ɗorewa na kushin lokaci guda uku wanda SCOTECH ke samarwa ya ƙunshi tushe, bangarorin gefe, ɓangarori, kofofi da manyan murfi. Akwatin ya kasu kashi zuwa babban dakin matsa lamba, gidan wutan lantarki da ƙananan matsi. Babban ɗakin wutar lantarki yana ɗaukar cikakkiyar ƙirar ƙira mai inganci, tare da cikakken aikin sarkar rashin aiki, babban abin dogaro, sauƙi mai sauƙi, babban ƙarfin wutan lantarki ana iya amfani da maɓallan ɗaukar nauyi mai ƙarfi, maɓallin hanyar sadarwa na zobe da sauransu. Za a iya shigar da dakin taranfofi da injin mai ({16}}) da aka nutsar da taranfoma ko busassun tafofi, kuma an sanye shi da keɓewar net ɗin kariya, ɗakin tafsirin na iya ɗaukar iskar iska ta yanayi ko tilastawa, gwargwadon buƙatar shigar da na'urar sarrafa zafin jiki ta atomatik, kula da yanayin zafin ɗaki da na'urar iska ta atomatik. Ƙarƙashin ɗakin wutar lantarki - an sanye shi da rarrabawa, ƙididdigewa, ramuwar wutar lantarki da sauran madaidaitan tsare-tsare, kuma yana iya ƙirƙira madaidaicin madaidaicin iko na biyu da adadin wayoyi bisa ga buƙatu.

 

 

1.2 Ƙayyadaddun Fasaha

Nau'in ƙayyadaddun ƙayyadaddun wutar lantarki 75 kVA da takaddar bayanai

Isarwa zuwa
Amurka
Shekara
2024
Nau'in
Tashin wutar lantarki
Ciyarwa
Madauki
Gaba
Matattu
Daidaitawa
IEEE C57.12.34
Ƙarfin Ƙarfi
75kv ku
Yawanci
60HZ
Mataki
3
Nau'in Sanyi
ONAN
Babban Voltage
22.86GRDY/13.2 kV
Na biyu Voltage
0.48y/0.208 kV
Abubuwan Iska
Aluminum
Matsala ta kusurwa
YNyn0
Impedance
Yafi ko daidai 2.7%
Matsa Canji
Farashin NLTC
Taɓa Range
±2*2.5%
Babu Asara Load
0.28KW
Akan Rasa Load
1.07KW
Na'urorin haɗi
Daidaitaccen Kanfigareshan

 

1.3 Zane

75 kVA kushin da aka ɗora zane da girman hoto.

75 kva pad mount transformer image005

 

 

02 Masana'antu

2.1 Kori

Rukuni guda uku{0}sashi na biyar{{1} ginshiƙi ya ƙunshi ginshiƙai guda biyar, yawanci ginshiƙai uku ana amfani da su don ɗaukar iska guda uku{2} (phase A, B, C), yayin da sauran ginshiƙai biyu suna aiki azaman haɗin gwiwa da tsarin tallafi. An ƙera ƙirar da'irar maganadisu na kowane ginshiƙi don haɓaka haɗin gwiwa da aiki na lokaci guda uku -. Wannan ƙira na iya rarrabawa da sarrafa daidaitaccen lokaci guda uku - kuma yana rage tsangwama tsakanin matakai. Shirye-shiryen ginshiƙai guda biyar yana sa yiwuwar zubar da ruwa na magnetic jujjuyawar sarrafawa yadda ya kamata, kuma a lokaci guda yana inganta haɓakawa da haɓakar mahimmanci. Ana ƙirƙira maƙallan ƙarfe sau da yawa tare da ƙima don cimma daidaitaccen rarraba filayen maganadisu. Ƙimar ƙirar ƙarfe na ƙarfe na ƙarfe zai iya rage yawan asarar da ke haifar da rashin daidaituwar filin maganadisu da inganta aikin kwanciyar hankali da aikin lantarki na kayan aiki. Ana iya rarraba iska guda uku - daidai gwargwado a kan ginshiƙan uku don samar da filayen maganadisu guda uku masu dogaro da juna. Wannan shimfidar wuri yana tabbatar da haɗin kai mai kyau kuma yana haɓaka canjin makamashi.

three-phase five-column core

 

2.2 Guda

aluminum winding

Yin amfani da babban aikin aluminium{0} na iya rage juriya na iska, ta haka rage asarar layin da haɓaka ingantaccen aiki na taransfoma gabaɗaya. Yin amfani da kayan rufe fuska na iya hana gajeriyar kewayawa da ɗigowa tsakanin iska da haɓaka aikin injin na'urar. Fasahar iska na iya tabbatar da cewa adadin jujjuyawar iskar ta kasance daidai da rarrabawa, wanda zai iya haɓaka rarraba filin maganadisu da haɓaka haɓakar haɗaɗɗen na'urar. Ta hanyar ƙira mai ma'ana na tsarin iska, ana iya rarraba halin yanzu daidai gwargwado a cikin iska, rage wuraren zafi na gida da rage dumama. Ta hanyar canza adadin jujjuyawar iskar, za a iya daidaita ma'aunin wutar lantarki na na'urar, ta yadda za a iya amfani da shi cikin sassauƙa a ƙarƙashin yanayin aiki daban-daban. Tsarin masana'anta na fasahar rauni na waya yana da ɗan girma, wanda zai iya rage haɓakar samarwa da haɓaka masana'anta, don haka ƙara rage farashin.

 

2.3 Tanko

An zaɓi babban ƙarfe mai inganci{0}a matsayin kayan tankin mai don tabbatar da juriya da juriyar lalata tankin mai. An yanke farantin karfe daidai daidai da zane-zane na zane, yawanci ta yin amfani da na'urori, yankan Laser ko hanyoyin yankan plasma. An goge farantin karfen da aka yanke, gurɓataccen abu da tsatsa{3}} hujja don inganta ingancin walda da mannewar rufin da ke gaba. Farantin karfen da aka yanke yana naɗewa kuma an kafa shi bisa ga buƙatun ƙira don walƙiya ta farko, galibi ana amfani da walda ta argon, walda ta CO₂ mai kariya ko waldawar baka da sauran hanyoyin walda. Bayan kammala walda, ana duba walda, gami da duban gani da duban ultrasonic, don tabbatar da ingancin walda. Yi amfani da kayan rufewa masu inganci masu inganci (kamar gaskets na roba da masu ɗaukar nauyi) a mahaɗin mahaɗar tankin mai don tabbatar da aikin rufe tankin mai. Maganin maganin tsatsa a saman tanki, yawanci ana amfani da murfin ƙasa, sannan a fesa babban fenti wanda ya dace da buƙatun kare muhalli don samar da kyakkyawan aikin lalata.

75 kva pad mount transformer stainless steel oil tank

 

2.4 Taron Karshe

75 kva pad mount transformer final assembly
75 kva 3 phase pad mount transformer

 

 

03 Gwaji

A'a.

Gwajin Abun

Naúrar

Karba

Darajoji

Ƙimar Ma'auni

Kammalawa

1

Ma'aunin Juriya

%

Matsakaicin rashin daidaiton juriya Kasa da ko daidai da 5%

1.16

Wuce

2

Gwajin Rabo

%

Bambancin rabon ƙarfin lantarki akan babban tapping: ƙasa da ko daidai da 0.5%

-0.04~-0.02

Wuce

3

zango{0}}gwajin dangantaka

/

YNyn0

YNyn0

Wuce

4

A'a -asara da tashin hankali na halin yanzu

/

I0 : bayar da ma'auni darajar

0.33%

Wuce

P0: ba da ƙima mai ƙima

0.062 kW

juriyar rashin hasara shine +10%

/

5

Load hasarar impedance ƙarfin lantarki da inganci

/

t:85 ku

haƙuri ga impedance shine ± 7.5%

juriyar jimlar asarar kaya shine +6%

/

Wuce

Z%: ƙimar da aka auna

3.65%

Pk: ƙimar ƙima

1.168 kW

Pt: ƙima mai ƙima

1.230 kW

Ingancin ba kasa da 99.03%

99.14%

6

Gwajin Karfin Wutar Lantarki

kV

LV: 10kV 60s

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

7

Jarrabawar Juriya da Wutar Lantarki

kV

Wutar lantarki mai aiki (kV): 40

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

Duration(s): 48

Mitar (HZ): 150

8

Gwajin Leaka

kPa

matsa lamba: 20kPA

Tsawon lokaci: 12h

Babu yabo kuma babu

Lalacewa

Wuce

9

Ma'aunin Resistance Insulation

GΩ

LV -HV zuwa Ground

85.2

/

10

Gwajin Mai

/

Ƙarfin Dielectric;

56,1 kv

Wuce

Abubuwan Danshi

9.7 mg/kg

Factor Dissipation

0.00327%

Furan Analysis

0.03 mg/kg

Gas Chromatography Analysis

/

 

75 kva pad mount transformer testing
75 kva pad mount transformer test

 

 

04 Shiryawa da jigilar kaya

75 kva pad mount transformer tin foil bag
75 kva pad mount transformer shipping
 
 

 

05 Yanar Gizo da Takaitawa

Sashe na uku na 75 kVA pad Mount transformer, tare da kyakkyawan aikin sa, ingantaccen inganci, da aikace-aikace iri-iri, shine mafi kyawun zaɓi don tsarin rarraba wutar lantarki na zamani. Ko a cikin cibiyoyin kasuwanci, wuraren shakatawa na masana'antu, ko abubuwan more rayuwa na jama'a, wannan samfurin ya dace da dacewa da buƙatun wutar lantarki daban-daban, yana tabbatar da daidaiton tsarin da haɓaka amfani da makamashi. Zaɓi Canjin Canjin Mataki na Uku na Pad don sanya tsarin wutar lantarki ya fi dacewa kuma abin dogaro, yana ba da tallafi mai ƙarfi don ci gaba mai dorewa a nan gaba.

three phase 75 kva pad mount transformer

 

Hot Tags: 75 kva kushin Dutsen Transformer, Manufacturer, maroki, farashin, farashi