500 kVA Matattu Gaban Kushin Haɓaka Mai Canjawa-24.94 / 0.48 kV|Kanada 2024
Yawan aiki: 500kVA
Wutar lantarki: 24.94/0.48kV
Siffar: tare da mai sauya famfo

Kyawawan inganci, rarrabuwar hankali - Uku -Pad Pad{1}Mounted Transformer, sabon ma'auni don sarrafa makamashi!
01 Gabaɗaya
1.1 Fagen Aikin
500 kVA pad mounted transformer an isar da ita zuwa Kanada a cikin 2022. Ƙarfin wutar lantarkin shine 500 kVA tare da sanyaya ONAN. Babban ƙarfin wutar lantarki na na'urar shine 24.94GrdY/14.4kV, yayin da ƙarfin lantarki na biyu shine 0.48y/0.277kV tare da ƙarfin lantarki guda biyu a gefen LV, wanda shine ainihin fifikon wannan taswirar. sun kafa ƙungiyar vector ta YNyn0.
Pad mounted transformer, wanda kuma aka sani da haɗin haɗin gwiwa, cikakkiyar saiti ne na na'ura mai rarrabawa da na'urar rarrabawa wanda ke haɗawa da na'ura mai haɗawa, babban{0} ƙarfin lantarki da na'urar fius mai kariya, ƙaramin-ɓangaren rarraba wutar lantarki, da sauransu. Ana amfani da shi wajen samar da wutar lantarki ta hanyar sadarwa ta zobe, samar da wutar lantarki biyu ko tsarin samar da wutar lantarki. Ya dace da masana'antu, ma'adinai, wuraren mai, tashar jiragen ruwa, filayen jirgin sama, gine-ginen jama'a na birni, wuraren zama, manyan hanyoyi, wuraren karkashin kasa da sauran wurare. Yana da abũbuwan amfãni na sauƙin sauyawa na yanayin samar da wutar lantarki, aiki mai aminci da abin dogara, ƙananan girman, shigarwa mai sauri, amfani mai aminci, aiki mai sauƙi, kyakkyawan bayyanar da kulawa mai sauƙi. Ta fuskar tattalin arziki, yana da fa'idodin ƙananan sawun ƙafa, ɗan gajeren lokacin gini da ƙarancin sharar gida.
1.2 Ƙayyadaddun Fasaha
500 kVA kushin da aka ɗora ƙayyadaddun taswira da takaddar bayanai
|
Isarwa zuwa
Kanada
|
|
Shekara
2024
|
|
Samfura
500kVA-24.94GrdY/14.4-0.480y(0.277)kV
|
|
Nau'in
Tashin wutar lantarki
|
|
Daidaitawa
IEEE C57.12.34
|
|
Ƙarfin Ƙarfi
500kVA
|
|
Yawanci
60HZ
|
|
Mataki
3
|
|
Nau'in Sanyi
ONAN
|
|
Babban Voltage
24.94GrdY/14.4kV
|
|
Na biyu Voltage
0.480y/0.277 kV
|
|
Abubuwan Iska
Aluminum
|
|
Matsala ta kusurwa
YNyn0
|
|
Impedance
5.75%
|
|
Matsa Canji
Farashin NLTC
|
|
Taɓa Range
(+0,-4)*2.5%
|
|
Babu Asara Load
0.765KW
|
|
Akan Rasa Load
3.870KW
|
|
Na'urorin haɗi
Daidaitaccen Kanfigareshan
|
1.3 Zane
150 kVA kushin da aka ɗora zane da girman hoto.
![]() |
![]() |
02 Masana'antu
2.1 Kori
Iron core shine babban bangaren wutar lantarki, tsarinsa yana da nau'ikan asali guda biyu na cibiya da harsashi, muna samar da irin wannan nau'in na'ura mai ɗaukar hoto don ɗaukar ainihin tsarin a cikin nau'in simintin ƙarfe. Laminated baƙin ƙarfe core an yi shi da laminated lantarki silicon karfe takardar daya bayan daya, kuma ainihin kayan ne sanyi - birgima hatsi -daidaitacce silicon karfe takardar. An sanya ainihin abin a tsaye, kuma ya ƙunshi babban lamination, manne, ƙafa, bel ɗin ja, farantin ja da goyan baya. Bangaren da ke da iska a wajen tsakiyar ƙarfe ana kiransa core column, ɓangaren da ba tare da juyi ba ana kiransa karkiya baƙin ƙarfe, karkiya ta ƙarfe an kasu kashi biyu na ƙarfe na sama da karkiya na ƙasa, don nau'in nau'in shafi na uku na kashi biyar a bangarorin biyu, iskan da ba a rufe ba ana kiransa karkiya ta gefe.

2.2 Guda

Wayar da aka yi ta daskare ba a yi ta da waya mai zagaye da tagulla ba, sai dai an yi ta ne da foil ɗin tagulla ko foil na aluminium, kowane Layer yana da rauni har juzu'i ɗaya, kuma kowane nau'in foil ɗin tagulla yana rabu da abin rufe fuska. Wannan abin rufe fuska an yi shi da takarda mai rufe fuska ta Nomax wanda Kamfanin DuPont ya samar a Amurka. Wannan takarda mai rufewa tana da juriya ga yanayin zafi mai zafi, mai daɗaɗɗen harshen wuta da kuma rufi mai kyau. An haɗe foil ɗin tagulla da takarda mai rufewa tare da rauni, faɗin takarda mai rufewa ya fi faɗin foil ɗin tagulla, kuma faɗin ɓangaren bangarorin biyu an rufe shi da ɗigon rufi na kauri ɗaya da foil ɗin tagulla kuma ana haɗa su a lokaci guda don samar da rufin ƙarewa, kuma ana sanya sassan tallafi tsakanin kowane yadudduka biyu ko uku don samun iska da zubar da zafi. Bayan an raunata foil ɗin tagulla da takardar insulating bisa ga adadin da aka tsara, takarda mai sanyaya ta yi rauni da yawa sannan kuma a raunata tef ɗin da ba{4}} alkali ba a kan takardar. Bayan da aka jiƙa da iska kuma an bushe, ana iya saita shi. Tsarin iska ya dace gabaɗaya don ƙarancin iskar wutar lantarki na taransfoma-.
2.3 Tanko
1. Za a iya zubar da saman akwatin ta dabi'a, kuma kusurwar kusurwar murfin saman ba ta kasa da digiri 3 ba.
2. Kyakkyawar aikin rigakafin rana, ba mai sauƙin zafi ba, don guje wa matsanancin zafin jiki wanda ya haifar da matsanancin zafin jiki na waje, rufin rufi.
3. Kyakkyawar danshi{1}}aiki mai tabbatarwa, ba mai sauƙin samar da ruwa ba
4. Anti -lalacewa, hana wuta, daskare{2}
5. Kyakkyawan kayan aikin injiniya, juriya na matsa lamba, juriya mai tasiri
6. Haɗin kai tare da muhalli

2.4 Taron Karshe

Bayan an yi ainihin abubuwan da aka haɗa da iska, ya kamata a haɗa su. Bayan an yi ainihin abubuwan da aka haɗa da iska, ya kamata a haɗa su. Da farko, cire matsi na sama, cire karkiya na ƙarfe na sama, sanya murfin ƙasa na ƙasa, sanya kwali mai insulating na core saita iska mai ƙarancin wuta da babban ƙarfin wutar lantarki, sanya rufin ƙarshen sama, toshe karkiya na ƙarfe, shigar da matsi, ƙara ƙarfi, shigar da gubar, shigar da mai canza famfo. Matsa -mai canzawa shine canza juzu'in juzu'i na taransfoma ta hanyar canza wurin famfo don tabbatar da ingantaccen ƙarfin lantarki.
Bayan an tattara jikin, shigar da dakin bushewa don bushewa, ana iya shigar da tanki bayan jikin ya bushe, tankin na'urar shine don kare harsashi na jikin injin da kwandon mai, kuma shine kwarangwal na taron na kayan aikin waje na injin, kuma yana iya taka rawar convection da radiation tsakanin mai canza wuta da makamashi, da kuma yanayin zafi.
03 Gwaji
Gwajin insulation: gami da gwajin ƙarfin dielectric da gwajin juriya don tabbatar da cewa ingancin iska da kayan kwalliya sun cika buƙatun.
Asara mai nauyi kuma babu gwajin asarar kaya: Ana amfani da shi don auna asarar wuta a ƙimar da aka ƙididdigewa da ƙimar ƙarfin lantarki don tabbatar da aikin sa.
Short{0}}Gwajin ƙwanƙwasa kewayawa: Ana auna gajeriyar rashin ƙarfi na na'ura mai ba da hanya tsakanin hanyoyin sadarwa don tantance martanin taransfoma zuwa gajeriyar zazzagewar wutar lantarki.
Gwajin wutar lantarki mai ƙwanƙwasa: Ana amfani da shi don gwada ƙarfin tsarin insulating don jure wuce gona da iri.
Gwajin juzu'i na sifili: Bincika iskar wutar lantarki don gajarta.
Matsa{0}}gwajin canji: Ana amfani da shi don gwada aikin, kwanciyar hankali da aikin mai canza tambarin{1}.
Gwajin hawan zafin jiki: Ƙayyade tashin zafin na'urar taswira a ƙarƙashin ƙimar ƙima kuma tabbatar da cewa bai wuce iyakar da aka yarda ba.
Duban bayyanar: Bincika ko bayyanar, sigina da shigarwa na taswirar sun cika buƙatu.


04 Shiryawa da jigilar kaya


05 Yanar Gizo da Takaitawa
Na gode don sha'awar ku ga kushin mu guda uku - wanda aka ɗora{1} A matsayin babban abin da ke cikin watsa wutar lantarki da rarrabawa, samfurinmu ya yi fice tare da ingancin sa, kwanciyar hankali, da aminci, yana biyan buƙatun aikace-aikace iri-iri. Ko don wuraren shakatawa na masana'antu ko wuraren kasuwanci, yana ba da ingantaccen hanyoyin samar da wutar lantarki da za ku iya dogaro da su. Fahimtar ƙaƙƙarfan buƙatun inganci da sabis a cikin tsarin wutar lantarki, mun himmatu wajen ba da sabbin fasahohi da tallafi mai kulawa. Muna sa ran samar da ƙwararrun hanyoyin samar da wutar lantarki don ayyukanku da yin aiki tare zuwa ga ingantaccen kuma mai dorewa nan gaba! Da fatan za a ji daɗin tuntuɓar mu tare da kowace tambaya.

Hot Tags: matattu gaban kushin da aka saka taranfoma, masana'anta, mai kaya, farashi, farashi
You Might Also Like
500 kVA Kushin Haɓaka Farashin-22.86 / 0.208 kV|Amur...
750 kVA Kushin Waje Mai Sauƙi Mai Sauƙi-34.5 / 0.48 ...
750 kVA Kushin Haɗa Mai Canjawa-13.2 / 0.48 kV|Amurk...
1500 kVA Kushin Haɗa Mai Canjawa-34.5 / 0.48 kV|Amur...
750 kVA Kushin Haɓaka Mai Canja wurin Mai amfani-34....
1000 kVA Mai Cika Man Fetur Mai Sauƙi Mai Sauƙi-13.8...
Aika Aikace-aikacen