1000 kVA Mai Cika Man Fetur Mai Sauƙi Mai Sauƙi-13.8 / 0.48 kV|Amurka 2024

1000 kVA Mai Cika Man Fetur Mai Sauƙi Mai Sauƙi-13.8 / 0.48 kV|Amurka 2024

Kasar: Amurka 2024
Yawan aiki: 1000kVA
Wutar lantarki: 13.8/0.48kV
Feature: tare da bayoneti fuse
Aika Aikace-aikacen

 

 

oil filled pad mounted transformer

Ingantacciyar jujjuyawar makamashi{0}}Uku-kushin lokaci{2}masu tafsirai suna sa amfanin wutar ku ya damu{3}} kyauta!

 

01 Gabaɗaya

1.1 Fagen Aikin

A cikin 2024, an isar da kushin kVA 1,000{3}} wanda aka ɗora zuwa Amurka don Sashen Haske na Municipal Belmont. An ƙera wannan na'ura mai rarraba lokaci uku- don yin aiki akan tsarin wye (GrdY)/7.97 kV mai nauyin kilo 13.8 kuma yana fasalta ±2 × 2.5% babu{10}}mai sauya matsa lamba (NLTC) don daidaita wutar lantarki. Ƙarfin wutar lantarki na biyu shine 0.208/0.12 kV, yana samar da ƙungiyar vector YNyn0, kuma an saita shi azaman madauki{15}}arfin wutar lantarki don ingantaccen aikin cibiyar sadarwa.

Wannan taswirar ba ta amfani da PCB kuma tana cike da FR3, man da ke da alaƙa da muhalli. Yana da mataccen{2}} gaba, madauki{3}} ƙirar ciyarwa, wanda ke sanya shi aminci da aminci a cikin ayyukan yau da kullun. Da yake an ɗaure shi, ana iya shigar da shi a waje akan siminti, don haka yana aiki da kyau a birane, unguwannin zama, wuraren shakatawa, wuraren masana'antu, filayen jirgin sama{6}} kuna suna.

Muhimmin fasalin wannan taranfomar ita ce tsarin akwatinta na daban: transformer da kanta da manyan{0}}karfin wutan lantarki{1}}kamar na'urorin kashe wuta, toshe{2}}a cikin fuses, da backup na yanzu{3}}iyakance fiusi{4} duk suna cikin nasu tankunan da aka hatimi, an raba su ta bangare. Bangaren har ma yana da keɓaɓɓen hannun rigar bango, wanda ke sa haɗa taransfoma zuwa kayan da ke canzawa da sauƙi. Hakanan yana nufin zaku iya kulawa ko maye gurbin sassa ba tare da yin rikici tare da sauran abubuwan haɗin ba, wanda ya dace da gaske. Wannan zane yana sa kulawa da maye gurbin sassa ya fi sauƙi, ba tare da rinjayar aikin al'ada na sauran sassa ba.

Gabaɗaya, wannan na'ura mai ɗaukar hoto karami ce, mai sauƙin shigarwa da kiyayewa, ƙaramar surutai, ƙarancin hasara, mai hana sata, kuma tana iya ɗaukar nauyi mai ƙarfi. Yana ba da cikakkiyar kariya kuma ya dace da wutar lantarki na madauki, wutar lantarki biyu, ko tsarin samar da wutar lantarki, yin aiki a matsayin na'ura don canza wutar lantarki, ma'auni, ramuwa, sarrafawa, da kariya.

 

1.2 Mahimman bayanai & Coil Highlights

 

 Kafa biyar{0}, babban ingancin silikon karfe core; ƙananan -asara, ɗorewa mai ƙarfi, hana tsufa.

 Copper windings don babban inganci da karko.

 Tsayawa mai ƙarfi yana rage jijjiga, hayaniya, da karkatar da sufuri.

 Cike da ƙarancin FR3 -mai ƙonewa, eco{2}} ruwa na abokantaka, yana tabbatar da aminci da inganci na dogon lokaci{3}}aiki a waje.

 

1.3 Ƙimar Fasaha

1000 kVA nau'in ƙayyadaddun bayanai da takaddun bayanai

Isarwa zuwa
Kudancin Amurka
Shekara
2024
Nau'in
Tashin wutar lantarki
Daidaitawa
IEEE C57.12.34-2022
Ƙarfin Ƙarfi
1000kVA
Yawanci
60HZ
Mataki
3
Ciyarwa
Madauki
Gaba
Matattu
Nau'in Sanyi
KNAN
Babban Voltage
13.8GrdY/7.97kV
Na biyu Voltage
0.48Y/0.277 kV
Abubuwan Iska
Copper
Liquid Insulant
Farashin FR3
Matsala ta kusurwa
YNyn0
Impedance
5.75%
Matsa Canji
Farashin NLTC
Taɓa Range
±2*2.5%
Babu Asara Load
1.15KW
Akan Rasa Load
7.56KW
Na'urorin haɗi
Daidaitaccen Kanfigareshan

 

1.4 Zane

1000 kVA kushin da aka ɗora zane da girman hoto.

transformers symbol drawing all transformers drawing

 

 

02 Masana'antu

2.1 Kori

Ƙaƙwalwar za ta zama ƙafa biyar - kuma an gina ta da ingantacciyar inganci, maras{1}}tsufa, sanyi{2}} birgima, mai daidaita hatsi, damuwa{3}}free, siraren siliki na karfe. Mabuɗin zai sami babban haɓakawa da ƙarancin asarar hysteresis. Dole ne a goge laminations ɗin ƙarfe da kyau kuma za su kasance da filaye masu santsi a gefuna. Kowace takardar za ta kasance tana da rufin da aka keɓe, wanda ba shi da kariya ga mai mai zafi.

Za a matse ainihin ainihin kuma a toshe shi don hana tabarbarewar girgizar ƙasa, tsangwama tare da zagayawa mai, yanayin amo mara kyau, da gajeriyar kewayawa da karkatattun jigilar kaya. Cibiya za a amintacce ƙasa zuwa tanki.

core type transformer and shell type transformer

 

2.2 Guda

multi coil transformer

An yi iskar wutar lantarki da tagulla. Ƙirar-rauni -ƙirar wutar lantarki yana ƙara sararin samaniya don mafi kyawun ɓarkewar zafi, yana tallafawa ci gaba da aiki mai girma{3}. Yana tabbatar da ƙarin daidaiton rarraba na yanzu, haɓaka kwanciyar hankali gabaɗaya, yana tsayayya da ƙarfin lantarki daga gajerun da'irori, yana rage hasarar ɗigogi, kuma yana rage yawan zafin jiki a cikin iska. Wannan haɗin yana inganta inganci kuma yana tsawaita rayuwar sabis na transfoma.

 

2.3 Tanko

Tankin na'ura mai jujjuyawar yanayi, ƙarfe mai walda, ruwa{0}tsattsauran tsari ne wanda aka ɗora akan ginshiƙi na ƙeƙasasshen ƙarfe don birgima ko tsalle-tsalle, tare da ƙugiya masu ɗagawa da kayan jacking. Ya haɗa da tagulla guda biyu{2}}asashen fuska, matattu- ɓangarorin tasha na gaba tare da ƙofofi, shingen ƙarfe, da kayan aikin tagulla. Tubular radiators ana waldasu na dindindin a baya. Ana iya buɗe kofofin a buɗe digiri 150 don kiyayewa lafiya. Filayen da aka yi da yashi, an yi musu magani, kuma an lulluɓe na waje tare da filaye da yadudduka gamawa biyu (min{8}} mils) a cikin Munsell Green 7GY 3.29/1.5, tare da ƙarin kariya a ƙasa da sill.

weatherproof and welded steel tank

 

2.4 Taron Karshe

transformer electrical components

Binciken Bangaren: Tabbatar da amincin abin da ke cikin gidan wuta, shinge, da kayan lantarki.

Majalisar Transformer: Haɗa ginshiƙi tare da windings kuma yi maganin rufewa.

Shigar da ƙulli: Haɗa mahalli na bakin karfe kuma tabbatar da cewa an rufe shi don hana lalata.

Haɗin Wutar Lantarki: Haɗa tashoshi masu ƙarfi da ƙananan ƙarfin lantarki da kuma tsarin ƙasa.

Na'urorin Tsaro: Shigar da na'urorin kariya don hana wuce gona da iri da gajerun kewayawa.

Tsarin Sanyaya: Shigar da tsarin sanyaya don tabbatar da tasirin zafi mai tasiri.

 

 

03 Gwaji

A'a.

Gwajin Abun

Naúrar

Karba

Darajoji

Ƙimar Ma'auni

Kammalawa

1

Ma'aunin Juriya

%

Matsakaicin juriya rashin daidaituwa

0.29

Wuce

2

Gwajin Rabo

%

Bambancin rabon ƙarfin lantarki akan babban tapping: ƙasa da ko daidai da 0.5%

0.11-0.12

Wuce

3

Mataki{0}}gwajin dangantaka

/

YNyn0

YNyn0

Wuce

4

A'a -asara da tashin hankali na halin yanzu

%

I0 :: bayar da ma'auni darajar

0.30

Wuce

kW

P0: ba da ƙima mai ƙima

1.115

/

Haƙuri don asarar nauyi shine ± 10%

/

5

Load asarar , impedance ƙarfin lantarki, jimlar asara da kuma yadda ya dace

/

t:85 ku

haƙuri ga impedance shine ± 7.5%

Haƙuri don asarar nauyi shine ± 6%

/

Wuce

%

Z%: ƙimar da aka auna

5.88

kW

Pk: ƙimar ƙima

7.264

kW

Pt: ƙima mai ƙima

8.379

%

Ingancin ba kasa da 99.43%

99.45

6

Gwajin Karfin Wutar Lantarki

/

LV: 10kV 60s

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

7

Jarrabawar Juriya da Wutar Lantarki

/

Wutar lantarki mai aiki (KV): 0.96

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

Duration(s):30

Mitar (HZ): 240

8

Ma'aunin Resistance Insulation

GΩ

HV{0}LV zuwa Kasa:

2.54

/

LV -HV zuwa Ground:

2.76

HV&LV zuwa Ground:

2.89

9

Gwajin Leaka

/

Aiwatar da matsa lamba: 50kPA

Babu yabo kuma babu

Lalacewa

Wuce

Tsawon lokaci: 12h

10

Gwajin Mai

kV

Ƙarfin Dielectric

51.7

Wuce

mg/kg

Abubuwan Danshi

106.4

%

Factor Dissipation

0.02106

mg/kg

Furan Analysis

/

/

Gas Chromatography Analysis

/

 

 

04 Shiryawa da jigilar kaya

transformer 1000kva packing transformer 1000kva shipping

 

05 Amfanin Muhalli & Aiki

Mai FR3:Mai lalacewa, mai ƙarancin wuta fiye da man ma'adinai, eco{0}} abota.

Ƙarfafan Shigarwa a Waje:Mai hana yanayi, lalata{0}}, amintaccen cibiya da gyaran iska.

Ingantaccen Makamashi:Ƙananan asarar baƙin ƙarfe, ingantacciyar iskar jan ƙarfe, rashin ƙarfi mai sarrafawa.

Daidaita dogaro, aminci, da alhakin muhalli.