1000 KVA Mai Canza wurin zama Akwatin-22.86 / 0.208 KV|Amurka 2024

1000 KVA Mai Canza wurin zama Akwatin-22.86 / 0.208 KV|Amurka 2024

Kasar: Amurka 2024
Yawan aiki: 1000 kVA
Wutar lantarki: 22.86GrdY/13.2-0.208/0.12kV
Siffar: tare da mai kamawa
Aika Aikace-aikacen

 

image001

Zuciyar Ikon Ka. Uku -Pad Pad -Tsarin wutar lantarki, Gina don Aiwatar da Aiki.

 

 

01 Gabaɗaya

1.1 Bayanin Aikin

1000 kVA uku fanti pad mounted transformer aka kawo wa Amurka a 2024. Ƙimar ikon na'urar shine 1000 kVA tare da ONAN sanyaya. Babban ƙarfin lantarki shine 22.86GrdY / 13.2 kV tare da ± 2 * 2.5% tapping range (NLTC), ƙarancin ƙarfin lantarki shine 0.208 / 0.12 kV, sun kafa ƙungiyar vector na YNyn0.

Rukunin Rukunin Mataki na Uku na Na'ura mai mahimmanci a cikin tsarin rarraba wutar lantarki, ana amfani da shi sosai a cikin grid ɗin wutar lantarki na birane, wuraren masana'antu, cibiyoyin kasuwanci, da al'ummomin zama don samar da ingantaccen ƙarfi mai ƙarfi don kayan aikin lantarki daban-daban; ƙayyadaddun ƙayyadaddun sa sun haɗa da ƙimar ƙimar 1000 kVA, inganci na kusan 99.43% (gamuwa da ka'idojin DOE 2016 don rage asarar makamashi), babu - asarar 1095 W, asarar nauyi na kusan 7094.84 W, kayan iskar aluminium (wanda yake da tsada, ƙimar ƙarfin lantarki, ƙimar ƙarfin aiki, da ingancin awoyi don ƙimar wutar lantarki, matsakaicin matsakaicin matsakaicin nauyi, matsakaicin matsakaicin matsakaicin nauyi, matsakaicin matsakaicin matsakaicin nauyi, matsakaicin matsakaicin matsakaicin nauyi). 85 digiri (zazzabi na magana) da digiri 55 (zazzabi da aka canza, mai mahimmanci don amincin aiki da tsawon rayuwa). Har ila yau yana da fa'idodi masu mahimmanci kamar ƙaramin ƙira (ƙaramin sawun ƙafa tare da tsarin haɗin kai wanda ke haɗa taransfoma da HV/LV switchgear, dacewa da sararin samaniya{10}}ƙaƙƙarfan yankunan birane), ƙaƙƙarfan kariya (ƙaƙƙarfan ƙarafa mai inganci tare da kyakkyawan juriyar lalata, ƙura, hana ruwa, da rodents (ƙirar ƙira da ingantaccen aiki) aiki a cikin matsananciyar yanayi), da sauƙin kulawa (tsarin madaidaicin sassa na ba da damar dubawa da gyare-gyare cikin sauri), yin rawar da ba za a iya maye gurbinsa ba a cikin tsarin wutar lantarki na zamani don tabbatar da aminci, kwanciyar hankali, da ingantaccen samar da wutar lantarki.

 

 

 

1.2 Ƙayyadaddun Fasaha

1000 kVA kushin da aka ɗora nau'in ƙayyadaddun bayanai da takaddun bayanai

Isarwa zuwa
Amurka
Shekara
2024
Nau'in
Tashin wutar lantarki
Daidaitawa
IEEE Std C57.12.34-2022
Ƙarfin Ƙarfi
1000 kVA
Yawanci
60HZ
Mataki
3
Ciyarwa
Madauki
Gaba
Matattu
Nau'in Sanyi
ONAN
Babban Voltage
22.86GrdY/13.2 kV
Na biyu Voltage
0.208 / 0.12 kV
Abubuwan Iska
Aluminum
Ƙungiyar Vector
YNyn0
Impedance
5.75%
inganci
99.43%
Matsa Canji
Farashin NLTC
Taɓa Range
±2*2.5%
Babu Asara Load
1.095 kW
Akan Rasa Load
7.855 kW

 

1.3 Zane

1000 kVA kushin da aka ɗora zane da girman hoto.

image003 image005

 

 

02 Masana'antu

2.1 Kori

image007

An yi ainihin abin da ba za a iya jurewa ba, sanyi{0} silikon karfe laminations. Tsarinsa nau'in ƙafafu ne guda uku -, tare da iska guda uku -waɗanda suka yi rauni a kusa da ainihin ƙafafu uku na tsaye bi da bi. Wannan ƙirar tana ba da ƙaramin -hanyar ƙin yarda don jujjuyawar maganadisu, tana ba da damar gudanar da ingantaccen filin maganadisu guda uku-. An tsara tsarin lamination da ingantattun kayan masarufi masu inganci don rage yawan asara na halin yanzu da rashin jin daɗi, ta haka inganta ƙarfin wutan lantarki da aikin aiki.

 

2.2 Guda

Gilashin wannan taswirar na amfani da aluminium don duka ƙananan foil ɗin ƙaramar wutar lantarki da babbar waya mai ƙarfin lantarki. The LV winding yana amfani da faffadan foil na aluminium, yana ba da gajeriyar ƙarfin kewayawa da ingantaccen sanyaya. Iskar HV tana amfani da keɓaɓɓen waya ta aluminum, rauni don cimma madaidaicin ƙimar ƙarfin lantarki. Wannan duk ƙirar aluminium - tana ba da farashi{7}} bayani mai inganci kuma abin dogaro.

image009

 

2.3 Tanko

image011

Tankin wani katafaren karfe ne da aka rufe, wanda ke dauke da cibiya da iska yayin da yake dauke da mai. Ganuwar bangon sa yana ba da babban yanki don ingantacciyar yanayin zafi zuwa iskar yanayi, yana tabbatar da aiki mai ƙarfi. An tsara shi don dorewa da ƙarancin kulawa, yana ba da cikakkiyar kariya ga abubuwan ciki.

 

2.4 Taron Karshe

Taro na ƙarshe yana haɗa babban taron coil{0}, zuwa cikin tankin ƙarfe da aka rufe kuma an cika shi da mai. Maɓallai masu mahimmanci kamar bushings HV/LV, na'urar taimakon matsa lamba, mai kamawa da sauran na'urorin haɗi ana hawa a waje. Wannan yana haifar da cikakken kai{3}}mai ƙunshe, mai ƙarfi, da kulawa{4}}ungiyar abokantaka, shirye don shigar da kumfa da haɗin grid.

image013

 

 

03 Gwaji

An gwada na'urar taswira (samfurin: 1000KVA 22.86Grdy/13.2{14}}0.208/0.12kV) a ranar 19 ga Oktoba, 2024 (zazzabi na yanayi 34 digiri, dangi zafi 73%) daidai da ma'auni kamar IEEE C57.12.00{16}}2021 da IEEE C57.12.34-2022. Gwaje-gwajen sun haɗa da ma'aunin juriya na iska (mafi girman rashin daidaituwa 5.51%), gwajin rabo (babban famfo sabawa -0.03 ~ 0.00%), gwajin dangantaka-lokaci (sakamakon YNyn0), asarar nauyi da gwajin na yanzu (1016W a digiri 20, 0.15% halin yanzu), asarar nauyi, ƙarancin ƙarfin gwaji da ƙimar inganci (781W) 6.09% impedance, 99.45% yadda ya dace), amfani da gwajin ƙarfin lantarki (10kV don LV zuwa ƙasa, 60s ba rushewa ba), gwajin juriya na ƙarfin lantarki (45.72kV wanda aka jawo a HV, 150Hz don 48s ba rushewa), gwajin gwajin jini (20kPa don ma'aunin juriya na 12h / damaΩ) HV&LV zuwa ƙasa), da gwajin dielectric mai (ƙarfin dielectric 56.3kV, danshi 9.5mg/kg), duk waɗanda suka wuce.

A'a.

Gwajin Abun

Naúrar

Karba

Darajoji

Ƙimar Ma'auni

Kammalawa

1

Ma'aunin Juriya

%

/

5.51

Wuce

2

Gwajin Rabo

%

Bambancin rabon ƙarfin lantarki akan babban tapping: ƙasa da ko daidai da 0.5%

-0.03~0.00

Wuce

3

zango{0}}gwajin dangantaka

/

YNyn0

YNyn0

Wuce

4

A'a -asara da tashin hankali na halin yanzu

/

I0 :: bayar da ma'auni darajar

0.15%

Wuce

P0: bayar da ƙima (t:20 digiri)

1.016 kW

juriyar rashin hasara shine +10%

/

5

Load asarar impedance ƙarfin lantarki da inganci

/

t:85 ku

haƙuri ga impedance shine ± 7.5%

juriyar jimlar asarar kaya shine +6%

/

Wuce

Z%: ƙimar da aka auna

6.09%

Pk: ƙimar ƙima

7.811 kW

Pt: ƙima mai ƙima

8.827 kW

Ingancin ba kasa da 99.43%

99.45%

6

Gwajin Karfin Wutar Lantarki

kV

LV zuwa Ƙasa: 10kV 60s

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

7

Jarrabawar Juriya da Wutar Lantarki

kV

Wutar lantarki mai aiki (KV):

2 Ur

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

Duration(s):48

Mitar (HZ): 150

8

Gwajin Leaka

kPa

matsa lamba: 20kPA

Tsawon lokaci: 12h

Babu yabo kuma babu

Lalacewa

Wuce

9

Ma'aunin Resistance Insulation

GΩ

HV&LV zuwa Ground

16.5

/

10

Gwajin Mai

/

Ƙarfin Dielectric;

56,3 kv

Wuce

Abubuwan Danshi

9.5 mg/kg

Factor Dissipation

0.00276%

Furan Analysis

0.03 mg/kg

Gas Chromatography Analysis

/

 

image015
image017

 

 

04 Shiryawa da jigilar kaya

4.1 Shiryawa

image019

Ana haɗe tafsirin kushin guda uku {{0}waɗanda aka ɗauko tafsirin da farko ta ɗora ɗigon jakar gwangwani a kan tirensa, a rufe taranfomar da jakar, a sanya abin bushewa a ciki, sannan a rufe jakar (ana barin buɗawa don fitar da iskar gas da injin tsabtace ruwa da farko, sannan a rufe buɗaɗɗen da mashin); na gaba, masu kariya na kusurwa (wanda aka yi da kumfa, filastik ko kwali) ana ƙara su a kusa da taswirar kuma an nannade shi da fim mai kariya; a ƙarshe, an cika shi a cikin akwati na katako a waje, wanda aka fesa tare da alamar cokali mai yatsa da tsakiyar alamar nauyi.

 

4.2 Shipping

Ana jigilar na'urorin taranfoma ne ta hanyar jigilar kayayyaki daga kasar Sin zuwa Amurka. Ana ajiye su cikin aminci a cikin daidaitattun kwantena na jigilar kaya, waɗanda ke ba da kariya daga matsanancin yanayin ruwa. A yayin tafiyar, ana tattara kwantena a hankali kuma a adana su a kan manyan jiragen ruwa. Wannan hanya ita ce mafi tsada -mafi inganci kuma abin dogaro don jigilar irin waɗannan kayan aiki masu nauyi da ƙanƙanta a cikin Tekun Pasifik, tabbatar da cewa na'urorin taswira sun isa tashar jiragen ruwa na Amurka a shirye don isar da su gaba.

image021

 

 

05 Yanar Gizo da Takaitawa

A matsayin amintaccen ginshiƙin hanyoyin rarraba wutar lantarki na zamani, kushin ɗinmu na zamani guda uku{0}saka{1}tasfoma yana haɗa ingantaccen ƙira, ingantaccen gini, da sauƙaƙewa. Ba wai kawai yana tabbatar da amintaccen jujjuyawar wutar lantarki ba amma kuma yana aiki azaman ingantaccen bayani don sarrafa rarrabawar ku mai hankali. Mun himmatu wajen isar da ƙimar samfur wanda ya zarce tsammanin, yin aiki tare don gina ingantacciyar wutar lantarki mai inganci a nan gaba.

image023

 