400 kVA Padmount Transformer-23 / 0.4 kV|Chile 2024

400 kVA Padmount Transformer-23 / 0.4 kV|Chile 2024

Kasar: Chile 2024
Yawan aiki: 400kVA
Wutar lantarki: 23/0.4kV
Feature: tare da akwatin tasha
Aika Aikace-aikacen

 

 

padmount transformer

Mai ɗorewa kuma mai sassauƙa, ɗorawa guda uku -kushin ɗorawa{1}}wayoyin wuta suna ba da ingantaccen tallafi ga duk buƙatun ku!

 

01 Gabaɗaya

1.1 Fagen Aikin

Wanda ya sayi taransfoma na wannan aikin shine Dovey{0}} kVA pad mounted transformer an isar da shi zuwa Chile a cikin 2024. Ƙimar wutar lantarki shine kVA 400 tare da sanyaya KNAN. Babban ƙarfin lantarki shine 23kV tare da kewayon tapping ± 2 * 2.5% (NLTC), ƙarfin lantarki na biyu shine 0.4kV, sun kafa ƙungiyar vector na YNyn0, kuma shine radial feed da matattarar gaba.

Abokan cinikinmu a cikin abubuwan more rayuwa na birni, wuraren shakatawa na masana'antu, da ci gaban kasuwanci akai-akai suna fuskantar ƙalubale masu mahimmanci: tabbatar da cikakkiyar amincin aiki a wuraren jama'a, sarrafa faɗuwar grid a cikin sawun jiki mai tsauri, da kuma ci gaba da ci gaba da wutar lantarki a ƙarƙashin yanayin da ake buƙata.

Don magance waɗannan maki zafi, ainihin dabarun samfurin mu yana mai da hankali kanm, cikakken rufin, da ƙira mai juriya sosai. Wannan yana kunshe a cikin 400 kVA pad -wanda aka ɗora shi, wanda aka ƙera shi don isar da aminci da aminci wanda bai dace ba.

Mabuɗin Zane-zane don Haɗu da Kalubalen Zamani:

Cikakkun Cikakkun Ciki, Amintacce{0}Ta-Tsarin Gine-gine:Babban shigar da wutar lantarki mai girma{0}yana amfani da nau'in filogi na igiyar igiya da aka haɗa da bushing, yana rufe dukkan sassan rayuwa a cikin rufin. Wannan yana haifar da mataccen ƙira ta gaba inda tasha ba ta da yuwuwar sifili,asali yana kawar da haɗarin haɗarin lantarkida kuma tabbatar da tsaron ma'aikata a ko da wuraren da aka fi cunkoso.

Sassauci na Aiki don Amsar Gaggawa:Mai haɗin gwiwar gwiwar hannu ba kawai yana sauƙaƙe haɗin kebul ba amma har ma yana ninka sau biyu azaman kaya{0}maɓallin karya a cikin gaggawa. Wannan zane yana bayarwasassauci mai mahimmanci don kulawa da keɓewar kuskure, rage raguwar lokaci da haɓaka ƙarfin grid.

Babban Ayyukan Resilient tare da Ruwan FR3:Na'urar tana cika da babban{0}}wuta{1}}maki FR3 man ester na halitta, yana ba da fa'idodin muhalli da aminci. Yana bayarwana musamman aiki: ƙaramar asara, ƙaramar amo, da ƙaramin zafin zafin aiki.Wannan tushe yana ba shi aƙarfin juriya mai ƙarfi, kyakkyawan gajeriyar juriyar kewayawa, da juriya mai ƙarfi, Tabbatar da aminci a lokacin hawan wutar lantarki da kuma cikin yanayin aiki mai tsanani.

Gina tare da fasaha na ci gaba da kayan ƙima, injin ɗin mu na 400 kVA an ƙera shi don tsawon rayuwar sabis mai dogaro. Kowane naúra yana fuskantar ƙwaƙƙwaran gwajin karɓa kafin bayarwa.

Muna tallafawa samfuran mu tare da cikakkiyar sabis ɗin fakitin ɗaya{0}, yana rufe komai tun daga tuntuɓar da magana zuwa masana'anta, shigarwa, ƙaddamarwa, horo, da tallafin tallace-tallace bayan{1}. Tare da injiniyoyinmu suna aiki cikin nasara a cikin ƙasashe sama da 50, mun himmatu wajen zama mafi amintaccen mai samar da ku da amintaccen abokin tarayya a cikin iko.

 

 

1.2 Ƙayyadaddun Fasaha

400 KVA nau'in ƙayyadaddun bayanai da takaddun bayanai

Isarwa zuwa
Chile
Shekara
2024
Nau'in
Tashin wutar lantarki
Daidaitawa
IEEE Std C57.12.34-2022
Ƙarfin Ƙarfi
400 KVA
Ciyarwa
Matattu
Gaba
Matattu
Yawanci
50HZ
Mataki
3
Nau'in Sanyi
KNAN
Liquid Insulant
FR3
Babban Voltage
23KV
Na biyu Voltage
0.4KV
Abubuwan Iska
Copper
Matsala ta kusurwa
Dyn1
Impedance
4.5%
Matsa Canji
Farashin NLTC
Taɓa Range
±2*2.5%
Babu Asara Load
0.75KW
Akan Rasa Load
5.605KW
Na'urorin haɗi
Daidaitaccen Kanfigareshan

 

1.3 Zane

400 KVA kushin da aka ɗora zane da girman hoto.

padmount transformer diagram padmount transformer nameplate

 

 

02 Masana'antu

2.1 Kori

Fuskantar ƙalubalen masana'antu na rashin isassun wutar lantarki, rashin kwanciyar hankali, da tsadar rayuwa, dabarun mu sun dogara ne akan ƙira mai mahimmanci guda uku{0}. Wannan dabarar tana magance waɗannan batutuwa kai tsaye ta hanyar ƙirƙirar gajeriyar hanya mai ma'ana ta maganadisu wacce ke rage asarar kuzari (asara baƙin ƙarfe), tana hana magnetic son rai don kwanciyar hankali aiki, da rage ɗigo. Bugu da ƙari kuma, ƙira ta zahiri tana haɓaka sanyaya yanayi kuma tana ba da ingantaccen tsarin injina, wanda ke haifar da na'ura mai canzawa tare da inganci mafi girma, ingantaccen juriya, da ƙarancin ƙimar mallaka.

laminated soft iron core

 

2.2 Guda

high-voltage wire winding

 

Dabarun jujjuyawar mu na haɗe-haɗe, haɗa ƙaramin ƙaramar iska mai ƙarfi tare da babban iska mai ƙarfi{1}, yana magance ƙalubalen ƙalubalen amincin rufi, sarrafa zafi, da gajeriyar juriyar kewayawa. Wannan ƙira yana ƙirƙirar filin lantarki iri ɗaya don hana rushewa, yana haɓaka ɓarkewar zafi don mafi girman ƙarfin lodi, kuma yana ba da ƙarfin injina don jure magudanar ruwa. Bugu da ƙari kuma, kusancin haɗin kai na iska yana haɓaka da'irar maganadisu, yana rage asarar ɗigo don samun babban inganci gabaɗaya.

 

2.3 Tanko

Don tabbatar da amincin mai canza canji da tsawon rai a ƙarƙashin manyan lodi da matsananciyar yanayi, dabarun ƙirar mu yana haɗa tanki mai ƙarfi da tsarin sanyaya ci gaba. Ana samun wannan ta hanyar tursasawa{1}}wararrun radiyo mai zagayawa don mafi girman zafi, babban tanki mai ƙarfi{2} tare da ingantaccen hatimi don hana yaɗuwa da lalata, da mahimman fa'idodin aminci kamar bawul ɗin taimako na matsa lamba, tare da ba da garantin ingantaccen aiki da tsawaita rayuwar sabis a aikace-aikace masu buƙata.

corrosion-resistant stainless steel tank

 

2.4 Taron Karshe

electrical components

Don tabbatar da ingancin masana'anta da dogaro na dogon lokaci{0}, dabarun samar da mu yana haɗe da ingantaccen sarrafa inganci a kowane muhimmin mataki. Wannan ya ƙunshi madaidaicin binciken sassa, jiyya na musamman a lokacin babban taro -, da kuma amfani da rufaffiyar, lalata{3}}waɗanda ke jurewa. An kammala tsarin tare da amintattun hanyoyin haɗin lantarki, haɗaɗɗen kariyar tsaro, da ingantattun tsarin sanyaya, sadar da na'urar canji da aka gina don ingantaccen aiki da dorewa.

 

 

03 Gwaji

A'a.

Gwajin Abun

Naúrar

Dabi'un Karɓa

Ƙimar Ma'auni

Kammalawa

1

Ma'aunin Juriya

%

Matsakaicin juriya ƙasa da ko daidai da 5%

1.18

Wuce

2

Gwajin Rabo

%

Bambancin rabon ƙarfin lantarki akan babban tapping: ƙasa da ko daidai da 0.5%

Alamar haɗi: Dyn1

-0.02% ~ -0.01%

Wuce

3

zango{0}}gwajin dangantaka

/

Dyn1

Dyn1

Wuce

4

A'a -asara da tashin hankali na halin yanzu

/

I0 :: bayar da ma'auni darajar

0.52%

Wuce

P0: bayar da ƙima (t:20 digiri)

0.625 kW

juriyar rashin hasara shine +10%

/

5

Load hasarar impedance ƙarfin lantarki da inganci

/

t:85 ku

haƙuri ga impedance shine ± 7.5%

juriyar jimlar asarar kaya shine +6%

/

Wuce

Z%: ƙimar da aka auna

4.82%

Pk: ƙimar ƙima

5.551 kW

Pt: ƙima mai ƙima

6.176 kW

Ingancin ba kasa da 99.00%

99.07%

6

Gwajin Karfin Wutar Lantarki

kV

HV: 40kV 60s

LV: 10kV 60s

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

7

Jarrabawar Juriya da Wutar Lantarki

kV

Wutar lantarki mai aiki (KV):2Ur

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

Induced ƙarfin lantarki (KV):46

Duration(s):40

Mitar (HZ): 150

8

Gwajin Leaka

kPa

Aiwatar da matsa lamba: 20kPA

Babu yabo kuma babu

Lalacewa

Wuce

Tsawon lokaci: 12h

9

Ma'aunin Resistance Insulation

GΩ

HV{0}LV zuwa Ground:

3.76

/

LV -HV zuwa Ground:

4.41

HV&LV zuwa Ground:

2.51

10

Gwajin Dielectric Oil

kV

Yafi ko daidai da 45

54.35

Wuce

 

transformer ratio test
transformer testing and commissioning

 

 

04 Shiryawa da jigilar kaya

4.1 Shiryawa

Kushin mu guda uku{0}}{1} da aka ɗora tafsirin na'ura an tattara shi cikin aminci a cikin kwalin katako na al'ada{2}} ginannen, nauyi{3}, wanda aka ƙera don tabbatar da cikakken kariya yayin wucewa da ajiya. Ana ƙarfafa firam ɗin katako mai ƙarfi tare da madauri na ƙarfe don hana motsi, yayin da taswirar da kanta ke toshewa a ciki kuma an ɗaure ta don ɗaukar duk wani girgiza ko tasiri. Wannan bayani na marufi yana ba da garantin cewa naúrar ku ta isa wurin a cikin cikakkiyar yanayi, a shirye don shigarwa.

padmount transformer packing

 

4.2 Shipping

padmount transformer shipping

Mu uku -fase pad{1} ɗora tafsirin tafofi an shirya su don aminci da ingantaccen jigilar teku. Kowace naúrar tana toshewa -ana cikin aminci mai nauyi -takardar katako, tana da cikakkiyar kariya don jure yanayin ruwan teku. Wannan ƙwaƙƙwaran marufi, haɗe tare da bayyanannun ɗagawa da alamun tarawa, yana tabbatar da kulawa mara kyau, ɗorewa, da isar da lokaci zuwa wuraren aikin duniya.

 

 

05 Yanar Gizo da Takaitawa

Don saduwa da ƙalubale masu mahimmanci na tabbatar da amincin rarraba wutar lantarki, daidaitawa, da inganci a cikin saituna daban-daban, dabarun mu na mayar da hankali ne kan cikakken keɓaɓɓen keɓaɓɓen keɓaɓɓen keɓaɓɓen, ƙarami uku{0} pad pad-madaidaicin na'urar wuta. Hannun gwiwar sa -nau'in fulogi{4}}a cikin masu haɗin kai yana haifar da mataccen ƙira na gaba don mafi girman aminci a wuraren jama'a, yayin da ƙarancinsa{6}}asashen cibiya da lalata{7}takarsa mai juriya yana tabbatar da ingancin makamashi mai tsayi da tsayin lokaci{8} tare da ƙarancin kulawa, yana ba da mafita mai ƙarfi don ayyukan masana'antu, kasuwanci, da na zama.