1000 kVA Kushin Haɓaka Lissafin Farashin farashin canji-13.8 / 0.415 kV|Jamaica 2024
Yawan aiki: 1000kVA
Wutar lantarki: 13.8/0.415kV
Feature: tare da keɓe mahaɗin

Ingantacciyar wutar lantarki, mai ƙarfi kamar dutsen-Uku{1}}kushin ɗorawa{2}masu wuta, amintaccen abokin aikin wutar lantarki!
01 Gabaɗaya
1.1 Fagen Aikin
An isar da wannan tafsiri mai nauyin kVA Pad 1000 zuwa Jamaica a cikin 2024. Ƙarfin da aka ƙididdige na na'urar shine 1000 kVA, tare da babban ƙarfin lantarki 13.8D kV zuwa ƙarfin lantarki na biyu 0.415y/0.24 kV. Ƙungiyar haɗin kai ita ce Dyn1, taswirar da aka ɗora pad shine babban tsarin sarrafa wutar lantarki, kariya, canjin wuta, da kayan aikin rarrabawa a cikin ɗayan cikakkun samfuran samfuran da aka riga aka shigar, waɗanda ake amfani da su sosai a cibiyoyin sadarwar birane da karkara. Samfurin yana sanya babban maɓalli{11}} ƙarfin ƙarfin ƙarfin lantarki da babban fis ɗin wutar lantarki a cikin mai, kuma yana da nau'i nau'i na tsari guda biyu na co{13}}akwatin ko keɓantaccen akwatin tare da jikin tasfo. Tankin mai yana da cikakken rufewa kuma an sanye shi da ma'aunin zafin mai, ma'aunin matakin mai, ma'aunin matsa lamba, bawul ɗin taimako na matsa lamba, bawul ɗin taimakon mai da sauran abubuwan da aka haɗa don lura da aikin na'urar. An raba samfurin zuwa nau'in cibiyar sadarwar zobe, nau'in tasha da yanayin samar da wutar lantarki. Ya dace da masana'antu, ma'adinai, wuraren mai, tashar jiragen ruwa, filayen jirgin sama, gine-ginen jama'a na birni, wuraren zama, manyan hanyoyi, wuraren karkashin kasa da sauran wurare.
1.2 Ƙayyadaddun Fasaha
1000 kVA nau'in ƙayyadaddun bayanai da takaddun bayanai
|
Isarwa zuwa
Jamaica
|
|
Shekara
2024
|
|
Nau'in
Tashin wutar lantarki
|
|
Daidaitawa
IEEE C57.12.00
|
|
Ƙarfin Ƙarfi
1000kVA
|
|
Yawanci
50HZ
|
|
Mataki
3
|
|
Ciyarwa
Madauki
|
|
Gaba
Matattu
|
|
Nau'in Sanyi
ONAN
|
|
Babban Voltage
13.8D kV
|
|
Na biyu Voltage
0.415y/0.24 kV
|
|
Abubuwan Iska
Copper
|
|
Matsala ta kusurwa
Dyn1
|
|
Impedance
4.75%
|
|
inganci
99.15%
|
|
Matsa Canji
Farashin NLTC
|
|
Liquid insulant
Ma'adinai mai
|
|
Taɓa Range
±2*2.5%
|
|
Babu Asara Load
Kasa da ko daidai da 1.3KW
|
|
Akan Rasa Load
Kasa da ko daidai da 13.2KW
|
|
Na'urorin haɗi
Daidaitaccen Kanfigareshan
|
1.3 Zane
1000 kVA kushin da aka ɗora zane da girman hoto.
![]() |
![]() |
02 Masana'antu
2.1 Kori
Jigon na'urar taswira ta shafi uku{0}3- tana qunshi da guda 6 a kowane Layer, kuma haɗewar naushin kowane yadudduka biyu yana amfani da tsare-tsare daban-daban don tursasa mahaɗin da'ira na kowane Layer. Ana kiran wannan hanyar haɗin gwiwa tare da haɗuwa, kuma wannan taron zai iya guje wa zagayawa na igiyoyin ruwa tsakanin takardar karfe da takardar karfe. Kuma saboda kowane nau'in nau'in nau'in nau'in nau'in nau'in nau'in nau'in nau'in nau'in nau'in nau'in nau'in nau'in nau'in nau'in nau'in nau'in nau'in nau'i nau'i nau'i nau'i nau'i nau'i nau'i nau'i nau'i nau'i nau'i nau'i nau'i nau'i nau'i nau'i nau'i nau'i nau'i nau'i nau'i nau'i nau'i nau'i nau'i nau'i nau'i nau'i nau'i nau'i nau'i)) wanda za'a iya amfani da ƙananan fasteners don sauƙaƙe tsarin lokacin danna maɓallin ƙarfe. A yayin da ake hadawa, ana fara jera faranti na naushi don su zama ginshiƙin ƙarfe gabaɗaya, sannan a datse karkiyar baƙin ƙarfe na ƙasa, a cire farantin karfen ƙarfe na sama don fallasa babban ginshiƙi, sai a sanya na'urar da aka ƙera a kan babban ginshiƙi, sannan a sanya farantin karfen ƙarfe na sama da aka ciro.

2.2 Guda

Haɗin Dyn1 hanya ce ta gama gari a cikin gidajen wuta, wanda galibi yana nufin amfani da haɗin tauraro (Y) don haɗa haɗin ƙasa mara ƙarfi ({1}} ƙarfin lantarki da haɗin triangle (Δ) don haɗa manyan iskar wutar lantarki a cikin uku- na'ura mai ba da hanya tsakanin hanyoyin sadarwa, da kuma matakin ƙananan - ƙarfin wutar lantarki yana bayan babban matakin digiri Angle by 1{5}. A cikin haɗin Dyn1, lokaci na ƙananan matsa lamba yana baya bayan babban matsin lamba ta 1 Phase Angle (digiri 120). Wannan dangantakar lokaci tana taimakawa wajen samun ingantacciyar ma'aunin nauyi a cikin nau'i uku{13}} da kuma rage matsalolin da ake haifar da asymmetry. Saboda haɗin tauraro na iya samar da wani yanki mai tsaka tsaki, haɗin Dyn1 zai iya hana wasu masu jituwa, musamman ma na uku masu jituwa, don inganta ingancin wutar lantarki. Matsakaicin tsaka tsaki na haɗin tauraron zai iya zama ƙasa, wanda zai iya inganta amincin tsarin kuma ya ba da kariya mafi kyau ga kayan aiki da ma'aikata. Bugu da ƙari, kayan aiki sun fi kariya daga lalacewa a yayin da aka yi kuskuren ƙasa. Haɗin Dyn1 ya dace da nau'ikan nau'ikan nau'ikan nau'ikan kaya, gami da na'urori masu layi da layi. Wannan yanayin haɗin kuma yana iya kula da kyakkyawan aikin aiki ƙarƙashin yanayin nauyi mara nauyi. Yana ba da damar ma'auni iri-iri na jujjuya wutar lantarki, ta yadda za a iya canza haɗin Dyn1 cikin sassauƙa a aikace-aikace daban-daban don dacewa da buƙatun ƙarfin lantarki daban-daban.
2.3 Tanko
Akwatin na iya amfani da ƙirar lalata da ƙirar fenti na musamman bisa ga buƙatun wurin aiki, tare da aikin “anti{1}}ƙasa-ƙasa” guda uku, wato anti-ƙarin gishiri, aikin ƙura, kuma yana iya biyan buƙatun ɓacin rai a cikin matsanancin zafin jiki da yanayin zafi. Tankin da aka rufe cikakke, cikakken ƙirar ƙira, aiki mai aminci da aminci.

2.4 Taron Karshe

Haɗin Wutar Lantarki: Cika haɗin haɗin cikin gida don manyan igiyoyin wutar lantarki da ƙananan{1}, tabbatar da ingantattun wayoyi tsakanin matakai.
Duban Tsarin Sanyaya: Bincika matakin mai da abubuwan da ke cikin tsarin sanyaya don tabbatar da cewa suna aiki yadda ya kamata.
Gwajin Insulation: Yi gwaje-gwajen rufewa don tabbatar da haɗin wutar lantarki sun cika ka'idodin aminci don aikin rufewa.
Rumbun Yaki: Rufe shingen gidan wuta, tabbatar da cewa duk haɗin gwiwa da hatimi ba su da kyau don hana danshi da gurɓatawa daga shiga.
03 Gwaji
|
A'a. |
Gwajin Abun |
Naúrar |
Dabi'un Karɓa |
Ƙimar Ma'auni |
Kammalawa |
|
1 |
Ma'aunin Juriya |
% |
Matsakaicin juriya ƙasa da ko daidai da 5% |
1.68 |
Wuce |
|
2 |
Gwajin Rabo |
% |
Bambancin rabon ƙarfin lantarki akan babban tapping: ƙasa da ko daidai da 0.5% Alamar haɗi: Dyn1 |
-0.08% ~- 0.06% |
Wuce |
|
3 |
zango{0}}gwajin dangantaka |
/ |
Dyn1 |
Dyn1 |
Wuce |
|
4 |
A'a -asara da tashin hankali na halin yanzu |
% kW |
I0: bayar da ma'auni darajar P0: ba da ƙima mai ƙima juriyar rashin hasara shine +0% |
0.48% 1.123 |
Wuce |
|
5 |
Load hasarar impedance ƙarfin lantarki da inganci |
% kW kW |
t:85 ku Z%: ƙimar da aka auna Pk: ƙimar ƙima Pt: ƙima mai ƙima haƙuri ga impedance shine ± 7.5% juriyar jimlar asarar kaya shine +0% Ingancin ba kasa da 99.15% |
4.89% 11.900 13.023 99.24% |
Wuce |
|
6 |
Gwajin Karfin Wutar Lantarki |
kV |
HV: 34kV 60s LV: 10kV 60s |
Babu rushewar ƙarfin gwajin da ke faruwa |
Wuce |
|
7 |
Jarrabawar Juriya da Wutar Lantarki |
kV |
Wutar lantarki mai aiki (KV): 2 Ur Duration(s):40 Mitar (HZ): 150 |
Babu rushewar ƙarfin gwajin da ke faruwa |
Wuce |
|
8 |
Gwajin Leaka |
kPa |
matsa lamba: 20kPA Tsawon lokaci: 12h |
Babu yabo kuma babu Lalacewa |
Wuce |
|
9 |
Ma'aunin Resistance Insulation |
GΩ |
HV{0}LV zuwa Kasa: LV -HV zuwa Ground: HV&LV zuwa Ground: |
20.4 35.1 18.3 |
/ |
|
10 |
Gwajin Dielectric Oil |
kV |
Yafi ko daidai da 45 |
56.83 |
Wuce |


04 Shiryawa da jigilar kaya


05 Yanar Gizo da Takaitawa
A cikin mahallin haɓaka buƙatar wutar lantarki da ci gaban fasaha cikin sauri, injin na'ura mai ɗaukar hoto na zamani guda uku yana ba ku ingantaccen ingantaccen wutar lantarki. Tare da aikin sa na musamman, ƙaramin ƙira, da ƙwaƙƙwaran daidaitawa, wannan samfurin ba wai kawai ya dace da buƙatun lantarki iri-iri ba har ma yana tabbatar da kwanciyar hankali a ƙarƙashin yanayin muhalli daban-daban. Ta zabar kushin mu mai ɗaure tiransifofi, za ku amfana daga ingantacciyar tabbacin inganci da fa'idodin tattalin arziki na dogon lokaci. Za mu ci gaba da haɓaka ƙirƙira fasaha da kyakkyawan sabis, taimaka wa tsarin wutar lantarki don haɓaka da inganci, cikin aminci, da dorewa. Na gode don amincewa da goyon bayan ku!

Hot Tags: pad mounted transformer price list, manufacturer, maroki, farashin, farashi
You Might Also Like
2500 kVA Residential Electrical Transformers-34.5/0....
75 kVA Kushin Dutsen Mai Canjawa-22.86 / 0.208 kV|Am...
750 kVA Kushin Dutsen Mai Canjawa-25 / 0.6 kV|Kanada...
300 kVA Mai Cika Mai Sauƙi-13.2 / 0.48 kV|Guyana 2024
2500 kVA Kushin Dutsen Mai Canjawa-12.47 / 0.48 kV|A...
1000 kVA Matattu Mai Canjin gaba-24 / 0.48 kV|Amurka...
Aika Aikace-aikacen