750 kVA Kushin Dutsen Mai Canjawa-25 / 0.6 kV|Kanada 2025
Yawan aiki: 750 kVA
Ƙarfin wutar lantarki: 25D-0.6Y/0.347 kV
Feature: tare da load break switch

Dogaran Ƙarfi, Ƙirƙirar Ƙira - Masu Canjin Pad don Grid mai Wayo!
01 Gabaɗaya
1.1 Bayanin Aikin
750 kVA uku pad pad mounted transformer an isar da shi zuwa Kanada a cikin 2025. Ƙarfin wutar lantarki na 750 kVA tare da sanyaya ONAN. Babban ƙarfin lantarki shine 25D kV tare da ± 2 * 2.5% tapping range (NLTC), ƙarfin lantarki na biyu shine 0.6y / 0.347 kV, sun kafa ƙungiyar vector na Dyn1.
CSA{0}}ƙwararriyar kushin{{1}masu na'urorin wuta da aka ɗora sun cika ƙaƙƙarfan ƙa'idodin da Ƙungiyar Ƙididdiga ta Kanada (CSA) ta gindaya don aikin lantarki, dorewa, da juriyar muhalli. Pad{3}}wayoyin da aka ɗora tafsiri masu ƙarfi, ƙaƙƙarfa, da ingantacciyar na'urori masu rarraba wutar lantarki waɗanda aka tsara don shigarwa a waje a matakin ƙasa. An lullube shi cikin matsuguni masu ɗorewa, masu jurewa{5}, waɗannan tafofi suna ba da amintaccen juzu'in wutar lantarki don aikace-aikacen birane, birni, da masana'antu. Wurin ajiyar su{7} ƙira yana rage girman sawun sawu yayin da yake tabbatar da samun sauƙin kulawa.
Tare da ci-gaba da rufi, juriya na lalata, da gini mai hana yanayi, pad -masu tafsiri suna isar da daidaitattun ayyuka a wurare daban-daban{1}daga grid masu wayo da tsarin sabunta makamashi zuwa rukunin kasuwanci da cibiyoyin sadarwa. Injiniya don aminci, inganci, da tsawon rai, su ne amintaccen zaɓi don rarraba wutar lantarki na zamani.
1.2 Ƙayyadaddun Fasaha
1500 kVA kushin da aka ɗora nau'in ƙayyadaddun bayanai da takaddun bayanai
|
Isarwa zuwa
Jamaica
|
|
Shekara
2025
|
|
Nau'in
Tashin wutar lantarki
|
|
Daidaitawa
CSA 2.1-06
|
|
Ƙarfin Ƙarfi
750 kVA
|
|
Yawanci
60HZ
|
|
Mataki
3
|
|
Ciyarwa
Madauki
|
|
Gaba
Matattu
|
|
Nau'in Sanyi
ONAN
|
|
Babban Voltage
25d kV
|
|
Na biyu Voltage
0.6Y/0.347 kV
|
|
Abubuwan Iska
Aluminum
|
|
Matsala ta kusurwa
Dyn1
|
|
Impedance
4.75%
|
|
Matsa Canji
Farashin NLTC
|
|
Taɓa Range
±2*2.5%
|
|
Babu Asara Load
1.4 kW
|
|
Akan Rasa Load
8.03 kW
|
|
Na'urorin haɗi
Daidaitaccen Kanfigareshan
|
1.3 Zane
750 kVA kushin da aka ɗora zane da girman hoto.
![]() |
![]() |
02 Masana'antu
2.1 Kori
Wannan 750kVA pad - da aka ɗora tafsiri yana amfani da babban{2}} CRGO core laminations a cikin daidaitaccen tsari guda uku-, guda uku- daidaitawar gaɓa. Matakin -Labin ɗin da aka tattara akan cinya yana da nau'ikan haɗin haɗin gwiwa na digiri 45 da haɗin gwiwar epoxy don rage asara da tabbatar da daidaiton tsari. Wannan ingantaccen ƙirar lamination yana ba da ingantacciyar inganci, gamuwa da ƙa'idodin CSA, tare da zaɓin madaidaicin ƙarfe don aikace-aikace masu inganci{{9}. Ƙarfin ginin yana ba da garantin ingantaccen aiki a cikin buƙatun mahalli masu amfani.

2.2 Guda

Wannan na'ura mai jujjuyawar iska guda 3 tana da daidaitattun iskar HV/LV da aka kirkira ta amfani da madugu na aluminium tare da abin rufe fuska. The HV winding yana amfani da ƙirar Layer{3}}rauni, yayin da LV ke amfani da ginin foil/helical don babban ƙarfin halin yanzu. Tsarin iska guda 3 yana ba da damar canjin ƙarfin lantarki mai sassauƙa. Axial/radial bracing yana jure gajerun rundunonin kewayawa{{7}.
2.3 Tanko
Wannan eco -aramin tanki na abokantaka yana da lahani{1}}mai jurewa, foda{2}}karfe mai rufi tare da gubar{3}}fenti kyauta, yana ba da kariya ta UV da amincin muhalli. Ƙirar 100% -ƙirar tankin tanki mai hujja yana hana gurɓatar ƙasa yayin da yake tallafawa ruwa mai FR3 mai iya lalata. Injiniya don dorewa da aiki, yana ba da aiki mai natsuwa (<65dB) and includes reinforced lifting points with optional seismic bracing.

2.4 Taron Karshe

1. Ƙwallon Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙaƙwalwa
Zamar da iskar HV/LV a kan ainihin ƙafafu, yana tabbatar da wurin da ya dace.
Saka yoke laminations kuma matsa ainihin don samar da cikakkiyar da'irar maganadisu.
2. Haɗin Wutar Lantarki
Haɗa jagora ta hanyar walda ko bolting, masu canza fam ɗin waya, bushings, da sauran tashoshi; tabbatar da yarda.
3. Bushewar Sashe Mai Aiki
Canja wurin sashin aiki (core + windings) cikin tanda don bushewar iska{1}}zafi{2}}har sai abun cikin damshi ya cika ma'auni.
4. Shigar Tanki
Sanya busasshiyar sashin aiki a cikin tanki, daidaitawa, kuma amintacce tare da manne; rufe murfin tanki.
5. Na'urorin haɗi
Shigar da na'urorin haɗi kamar bushings, na'urorin taimako na matsa lamba, ma'aunin mai, fius ɗin bayoneti, da sarrafa wayoyi.
6. Ciko Mai & Rufewa
Cike{0}}cika da mai mai hana ruwa zuwa ƙayyadadden matakin. Bayan daidaitawa, gwada ƙarfin dielectric mai da abun ciki na danshi; yi gwajin yabo na ƙarshe.
03 Gwaji
|
A'a. |
Gwajin Abun |
Naúrar |
Dabi'un Karɓa |
Ƙimar Ma'auni |
Kammalawa |
|
1 |
Ma'aunin Juriya |
% |
Matsakaicin juriya rashin daidaituwa |
0.81 |
Wuce |
|
2 |
Gwajin Rabo |
% |
Bambancin rabon ƙarfin lantarki akan babban tapping: ƙasa da ko daidai da 0.5% |
0.00 |
Wuce |
|
3 |
zango{0}}gwajin dangantaka |
/ |
Dyn1 |
Dyn1 |
Wuce |
|
4 |
A'a -asara da tashin hankali na halin yanzu |
/ |
I0 :: bayar da ma'auni darajar |
0.53% |
Wuce |
|
P0: ba da ƙima mai ƙima |
1.197 kW |
||||
|
juriyar rashin hasara shine +10% |
/ |
||||
|
5 |
Load asarar impedance ƙarfin lantarki da inganci |
/ |
t:85 ku haƙuri ga impedance shine ± 7.5% juriyar jimlar asarar kaya shine +6% |
/ |
Wuce |
|
Z%: ƙimar da aka auna |
4.55% |
||||
|
Pk: ƙimar ƙima |
7.325 kW |
||||
|
Pt: ƙima mai ƙima |
8.522 kW |
||||
|
Ingancin ba kasa da 99.15% |
99.25% |
||||
|
6 |
Gwajin Karfin Wutar Lantarki |
kV |
HV: 50kV 60s LV: 10kV 60s |
Babu rushewar ƙarfin gwajin da ke faruwa |
Wuce |
|
7 |
Jarrabawar Juriya da Wutar Lantarki |
kV |
Wutar lantarki mai aiki (KV): 2 Ur |
Babu rushewar ƙarfin gwajin da ke faruwa |
Wuce |
|
Duration(s):48 |
|||||
|
Mitar (HZ): 150 |
|||||
|
8 |
Gwajin Leaka |
kPa |
matsa lamba: 20kPA Tsawon lokaci: 12h |
Babu yabo kuma babu Lalacewa |
Wuce |
|
9 |
Ma'aunin Resistance Insulation |
GΩ |
HV{0}LV zuwa Ground |
10.6 |
/ |
|
LV -HV zuwa Ground |
10.4 |
||||
|
HV&LV zuwa Ground |
9.12 |
||||
|
10 |
Gwajin Mai |
/ |
Ƙarfin Dielectric; |
57.3 kV |
Wuce |
|
Abubuwan Danshi |
9.9 mg/kg |
||||
|
Factor Dissipation |
0.00247% |
||||
|
Furan Analysis |
0.03 |
||||
|
Gas Chromatography Analysis |
/ |


04 Shiryawa da jigilar kaya
4.1 Shiryawa
Kunshin da aka ɗora -kunshin wutar lantarki yana amfani da katako mai ƙarfi wanda aka ƙarfafa shi da madauri na ƙarfe, yana nuna ramukan cokali mai yatsu ko ɗagawa don sarrafawa. Naúrar tana aminta da sket na katako a cikin ramin, kuma an ɗaure shi da kumfa ko roba don ɗaukar girgiza. An tattara na'urorin haɗi daban a cikin ɗakunan da aka rufe. Ana lulluɓe na waje da takardar filastik mai hana ruwa kuma ya haɗa da jakunkuna masu bushewa, yayin da alamun suna nuna tsakiyar nauyi, kariyar danshi, "Kada ku karkata," da ƙayyadaddun fasaha. Wannan tsari na fakitin na'ura mai canzawa yana tabbatar da juriya, damshi-mai jurewa, da dogon lokaci{6}kariyar waje, ana isar da shi cikin cikakken yanayin rufewa don sauƙin dubawa da shigarwa.

4.2 Shipping

Za a aika da Pad{0}Mounted Transformer a ƙarƙashin sharuɗɗan CIF zuwa tashar jiragen ruwa na Vancouver, Kanada. Mai siyar yana tsara sufuri da inshora na asali, yana ba da ISPM 15{3}}akulan katako masu ƙorafe-ƙorafe (ƙarfe{4}}mai ɗaure da gigice{8}}sharar fakiti) da sarrafa takaddun izinin fitarwa (daftar kasuwanci, lissafin tattara kaya, takardar shaidar asali, da sauransu). Jigilar kaya tana amfani da kwantena sama-sama na 40ft ko lebur, tare da welded na injin taswira kuma an lakace don tsaro, da lura da zafin jiki a duk lokacin wucewa. Inshorar rufewa. Tashar tashar jiragen ruwa ta Vancouver tana buƙatar sanarwar gaba na nau'in mai taswira (cika da ka'idojin EPA na Kanada), takaddun shaida na CSA (idan an zartar), da jadawalin taga tide don saukewa. Dole ne takaddun sun haɗa da Bill of Lading (tare da CCN na Kanada) da kuma rufe rahoton MSDS mai.
05 Yanar Gizo da Takaitawa
A matsayin ginshiƙin tsarin rarraba wutar lantarki, wannan Pad{0}Mounted Transformer yana isar da ingantaccen, inganci, da yanayin muhalli{1}}wajen juyar da makamashi don masana'antu, kasuwanci, da ababen more rayuwa na jama'a. Ƙirƙira tare da ƙaƙƙarfan sanyi - ƙarfe na siliki na birgima da cikakken gini, yana tabbatar da ƙarancin{4}}asara, aiki shiru yayin saduwa da kariya ta IP67 da ƙaƙƙarfan ƙa'idodin duniya. Ƙirar tanki mai ƙaƙƙarfan ƙira yana haɓaka sarari, kuma haɗaɗɗen hanyoyin sa ido mai kaifin basira yana ba da damar gudanarwa mai nisa. CSA/UL ta ƙware don bin ƙa'idodin Arewacin Amurka, yana ba da garantin aiki mai ɗorewa a cikin matsananciyar yanayi da manyan yanayin yanayi mai girma{9}} yana mai da shi mafi kyawun zaɓi don kayan aikin grid na zamani.

Hot Tags: 750 kva kushin Dutsen Transformer, Manufacturer, maroki, farashin, farashi
You Might Also Like
75 kVA 3 Mai Rarraba Rarraba Mataki-13.8 / 0.208 kV|...
150 kVA Kushin Haɗa Mai Canjawa-34.5 / 0.208 kV|Amur...
300 kVA Kushin Dutsen Mai Canjawa-12.47 / 0.48 kV|Am...
500 kVA Kushin Haɓaka Mai Canjin wurin zama-34.5 / 0...
2500 kVA Kushin Dutsen Mai Canjawa-12.47 / 0.48 kV|A...
1500 kVA Kushin Dutsen Mai Canjawa-13.8 / 0.46 kV|Gu...
Aika Aikace-aikacen