1250 kVA Kushin Haɗa Mai Canjawa-12.47 / 0.6 kV|Amurka 2025

1250 kVA Kushin Haɗa Mai Canjawa-12.47 / 0.6 kV|Amurka 2025

Kasar: Amurka 2025
Yawan aiki: 1000 kVA
Wutar lantarki: 12.47GrdY/7.2-0.6Y/0.347kV
Siffar: tare da mai FR3 da masu kama walƙiya
Aika Aikace-aikacen

 

 

1250 kva pad mounted transformer

Ƙirƙirar Ƙwararrun Ƙwararrun Ƙwararrun Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙwara

 

 

01 Gabaɗaya

1.1 Bayanin Aikin

1250 kVA uku fage pad mounted transformer an isar da ita zuwa Amurka a cikin 2025. Ƙarfin wutar lantarkin shine 1250 kVA tare da sanyaya kNAN. Babban ƙarfin lantarki shine 12.47GrdY/7.2 kV tare da kewayon tapping ± 2 * 2.5% (NLTC), ƙarfin lantarki na biyu shine 0.6Y/0.347 kV, sun kafa ƙungiyar vector na YNyn0.

Wannan Pad{0}Mounted Transformer babban kayan aikin rarraba wutar lantarki ne wanda aka ƙera musamman don grids na zamani, haɗe eco{2} kariya ta walƙiya, da ƙaramin hankali cikin tsari ɗaya. Ya dace da mahimman aikace-aikacen wutar lantarki da suka haɗa da grid na birni, wuraren shakatawa na masana'antu, cibiyoyin kasuwanci, da tashoshin wutar lantarki masu sabuntawa.

A matsayin babban ɓangaren tsarin rarraba wutar lantarki, wannan samfurin yana amfani da babban{0}}aiki na FR3 na ester insulating mai, yana cin galaba akan iyakokin man ma'adinai na gargajiya tare da ultra{2}madaidaicin filasha, ingantaccen yanayin muhalli, da tsawaita rayuwar sabis. An sanye shi da ginannun masu kama walƙiya, yana dannewa walƙiya da jujjuya ƙarfin wuta, yana ba da kariya ta 24/7 ga grid. Cikakken tsarin ƙirar tanki yana da fashe -hujja, danshi-mai jurewa, da kaddarorin lalata, masu iya daidaita aiki a cikin matsananciyar muhalli kama daga digiri -40 zuwa digiri, har ma da yanayi mai tsauri kamar guguwa, ruwan sama mai ƙarfi, da guguwa.

Bugu da ƙari, wannan samfurin yana goyan bayan haɓakawa mai wayo tare da tsarin sa ido na kan layi na zaɓi waɗanda ke tattara bayanan lokaci na gaske akan zafin mai, yanayin kaya, fitar da wani bangare, da sauran mahimman sigogi. Ta hanyar fasahar IoT, tana ba da damar sa ido na nesa da tsinkayar kuskure, yana ba da gudummawa ga haɓaka ingantaccen, ƙarancin carbon ({2}}), da ingantattun hanyoyin sadarwar rarraba wayo.

 

1.2 Ƙayyadaddun Fasaha

1250 kVA kushin da aka ɗora nau'in ƙayyadaddun bayanai da takaddun bayanai

Isarwa zuwa
Amurka
Shekara
2025
Nau'in
Tashin wutar lantarki
Daidaitawa
IEEE StdC57.12.34-2022
Ƙarfin Ƙarfi
1250 kVA
Yawanci
60HZ
Mataki
3
Ciyarwa
Madauki
Gaba
Matattu
Nau'in Sanyi
KNAN
Babban Voltage
12.47GrdY/7.2kV
Na biyu Voltage
0.6Y/0.347 kV
Abubuwan Iska
Aluminum
Matsala ta kusurwa
YNyn0
Impedance
5.75%
Matsa Canji
Farashin NLTC
Taɓa Range
±2*2.5%
Babu Asara Load
1.41 kW
Akan Rasa Load
9.05 kW
Na'urorin haɗi
Daidaitaccen Kanfigareshan

 

 

1.3 Zane

1250 kVA kushin da aka ɗora zane da girman hoto.

transformer easy drawing 1250 kva pad mounted transformer nameplate

 

 

02 Masana'antu

2.1 Kori

Wannan kushin{0} da aka ɗora tasfoma yana da ƙaƙƙarfan tsari guda uku{1}}tsari na biyar{2}}, wanda ya ƙunshi manyan gaɓoɓi guda uku (don iska mai ƙarfi) da ƙarin karkiya biyu na dawowa. Wannan zane yana ba da fa'idodi masu zuwa:

• Ingantattun Ma'aunin Magnetic:Tsarin kafa guda biyar - yana samar da ƙananan hanyoyi masu zaman kansu-waɗanda ba a so don sauyin lokaci guda uku{2}, rage sifili{3}} asarar juyi.

• Ingantattun Ƙarfin Kiɗa:Karkiya masu taimako suna taimakawa rarraba kaya marasa daidaituwa kwatsam.

• Amo & Jijjiga Sarrafa:Rarraba juzu'i na daidaitawa yana tabbatar da hayaniya mai aiki Kasa da ko daidai da 55 dB (mai dacewa da IEEE C57.12.90).

stepped core transformer

 

2.2 Guda

 aluminum-wound high-voltage windings

Wannan 1250kVA 12.47/0.6kV pad -wanda aka ɗora tasfoma yana da tsarin iska mai laƙabi tare da aluminium{4}}rauni{5}}ƙara (HV) windings da foil aluminum{6}}rauni {{7}voltage (LV) windings. Bangaren HV yana amfani da iskar aluminium mai shimfiɗaɗɗen iska tare da keɓaɓɓun madugu, yana tabbatar da ƙarfin lantarki da aikin zafi. Bangaren LV yana amfani da ci gaba da raunin aluminum foil don ƙaramin gini, gajeriyar juriyar kewayawa, da ingantaccen zubar da zafi axial. Ƙirar tana daidaita ma'auni abin dogaro, ƙarfin injina, da rage nauyi/farashi, saduwa da ƙaƙƙarfan buƙatun fakitin waje{12}}masu tafsiri.

 

2.3 Tanko

An kafa tankin ta hanyar walda babban ƙarfe{0}ƙarar ƙarfi. Jikin tanki yana fashewa da yashi don cire tsatsa sannan kuma an lulluɓe shi da fenti na lalata don tabbatar da tsayin daka{3}} juriya a waje. An tsara ƙaƙƙarfan haƙarƙarin ƙarfafawa akan bangon tanki don haɓaka ƙarfin injin, kuma an inganta wurin zubar da zafi. Babban kabu na amfani da walda mai sarrafa ruwa mai sarrafa kansa ko garkuwar gas na CO₂ don tabbatar da zubewar haɗin gwiwa-hujja.

 high-strength mild steel

 

2.4 Taron Karshe

Stack silicon steel laminations

1. Hawan iska:Saka iska ukun akan babban ginshiƙi

2. Babban Taro:Tari silicon karfe laminations Layer da Layer

3. Shigar da manne:Amintaccen matsi na sama/ƙasa tare da manyan kusoshi masu ƙarfi{{0}

4. Haɗin kai:Jagororin da aka haɗa zuwa matsi mai daidaita sauyawa da jagororin manyan bushings masu ƙarfi da ƙarancin wuta

 

 

03 Gwaji

A'a.

Gwajin Abun

Naúrar

Dabi'un Karɓa

Ƙimar Ma'auni

Kammalawa

1

Ma'aunin Juriya

%

Matsakaicin juriya rashin daidaituwa

2.13

Wuce

2

Gwajin Rabo

%

Bambancin rabon ƙarfin lantarki akan babban tapping: ƙasa da ko daidai da 0.5%

Alamar haɗi: YNyn0

-0.12% ~ 0.09%

Wuce

3

Mataki{0}}gwajin dangantaka

/

YNyn0

YNyn0

Wuce

4

A'a -asara da tashin hankali na halin yanzu

/

I0 :: bayar da ma'auni darajar

0.32%

Wuce

P0: bayar da ƙima (t:20 digiri)

1.272 kW

juriyar rashin hasara shine +10%

/

5

Load asarar impedance ƙarfin lantarki da inganci

/

t:85 ku

haƙuri ga impedance shine ± 7.5%

juriyar jimlar asarar kaya shine +6%

/

Wuce

Z%: ƙimar da aka auna

5.87%

Pk: ƙimar ƙima

8.883 kW

Pt: ƙima mai ƙima

10.155 kW

Ingancin ba kasa da 99.45%

99.48%

6

Gwajin Karfin Wutar Lantarki

kV

HV: 34kV 60s

LV: 10kV 60s

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

7

Jarrabawar Juriya da Wutar Lantarki

kV

Wutar lantarki mai aiki (KV):2Ur

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

Duration(s):48

Mitar (HZ): 150

8

Gwajin Leaka

kPa

matsa lamba: 20kPA

Babu yabo kuma babu

Lalacewa

Wuce

Tsawon lokaci: 12h

9

Ma'aunin Resistance Insulation

GΩ

HV{0}LV zuwa Ground:

2.39

/

LV -HV zuwa Ground:

2.53

HV&LV zuwa Ground

1.40

 

oc and sc test of transformer
polarisation index test of transformer

 

 

04 Shiryawa da jigilar kaya

1250 kva pad mounted transformer packing
customs clearance procedures

 

05 Yanar Gizo da Takaitawa

Kushin mu{0}masu na'urorin wuta suna isar da ingantacciyar rarraba wutar lantarki tare da ƙaƙƙarfan ƙira, inganci mai ƙarfi, da ƙarfi mai ƙarfi, manufa don gonakin hasken rana, grid na birni, da aikace-aikacen masana'antu.

• Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙaƙwalwar Muhalli

• Kulawa mai wayo: Na'urori masu auna firikwensin IoT na zaɓi na ainihin{0}}Load/bibin yanayin zafi

• Tallafin Duniya: Daidaitaccen samarwa tare da gyare-gyare mai sauƙi

Ƙaddamar da amintattun hanyoyin samar da makamashi mai dorewa - tuntuɓe mu don ƙayyadaddun fasaha ko tallafin aikin!

 