2500 kVA Uku Pad Pad Haɗa Masu Canza-25 / 0.6 kV|Kanada 2025
Yawan aiki: 2500kVA
Ƙarfin wutar lantarki: 25kV-600Y/347V
01 Gabaɗaya
1.1 Hasken Aikin

Hasken Haske Lokacin da abokin cinikinmu na Kanada ya kusanci mu, suna buƙatar masu canji waɗanda zasu iya ɗaukar matsanancin yanayi, nauyi mai nauyi, da ci gaba da aiki. Wannan shi ne ainihin abin da muka isar: biyu2500 kVA pad -masu tafsirian tsara shi don samar da abin dogaro, daidaiton ƙarfi don cibiyoyin sadarwa na masana'antu da kasuwanci. Waɗannan raka'o'in ba inji ba ne kawai{1}alƙawari ne. Alkawarin cewa makamashi zai ci gaba da gudana, cikin aminci da inganci, kowace rana.
1.2 An Keɓance Don Yanayin Kanada
Mun ƙirƙira waɗannan taswira musamman don ƙalubalen yanayin waje na Kanada. Tare da iskar aluminium da sanyaya mai na ONAN, suna dawwama ko da lokacin da grid ya canza ko yanayin zafi ya yi saurin canzawa. Madauki -Mataccen ciyarwa-ƙirar gaba tana kiyaye mutane lafiya, yayin da ƙungiyar Dyn1 vector ta sa haɗawa cikin hanyoyin sadarwa masu tsaka tsaki mai sauƙi. Ainihin, mun tabbatar da cewa za su yi abin dogaro ko da menene yanayi ya jefa su{6} kuma su sa masu aiki da kwarin gwiwa yayin da suke kan sa.
1.3 Ƙimar Fasaha
2500 kVA uku lokaci kushin saka tasfo bayani dalla-dalla da bayanai takardar
|
Isarwa zuwa
Kanada
|
|
Shekara
2025
|
|
Nau'in
Uku fanni kushin Dutsen transformer
|
|
Daidaitawa
CSA C227.4:21
|
|
Ƙarfin Ƙarfi
2500 kVA
|
|
Yawanci
60HZ
|
|
Ciyarwa
Madauki
|
|
Gaba
Matattu
|
|
Mataki
Uku
|
|
Nau'in Sanyi
ONAN
|
|
Liquid insulant
Ma'adinan Mai
|
|
Babban Voltage
25 kv
|
|
Na biyu Voltage
0.6 kV
|
|
Ƙungiyar Vector
Dyn1
|
|
Abubuwan Iska
Aluminum
|
|
Impedance
5.75%
|
|
Matsa Canji
Farashin NLTC
|
|
Taɓa Range
±2*2.5%
|
|
Babu Asara Load
2500 W
|
|
Akan Rasa Load
24000 W
|
|
Na'urorin haɗi
Daidaitaccen Kanfigareshan
|
1.4 Zane
2500 kVA uku kushin kushin da aka ɗora tasfotoci zane da farantin suna
![]() |
![]() |
02 Keɓance don Yanayin Kanada
Mun tsara waɗannan2500 kVA uku lokaci kushin saka tasfotocimusamman don ƙalubalen yanayin waje na Kanada. Tare da iskar aluminium da sanyaya mai na ONAN, suna dawwama ko da lokacin da grid ya canza ko yanayin zafi ya yi saurin canzawa. Madauki -Mataccen ciyarwa-ƙirar gaba tana kiyaye mutane lafiya, yayin da ƙungiyar Dyn1 vector ta sa haɗawa cikin hanyoyin sadarwa masu tsaka tsaki mai sauƙi. Ainihin, mun tabbatar da cewa za su yi abin dogaro ko da menene yanayi ya jefa su{6} kuma su sa masu aiki da kwarin gwiwa yayin da suke kan sa.
2.1 Core da Magnetic Innovation
![]() |
A zuciyar kowane tafsirin wutan lantarki yana da ƙanƙantaccen ƙaƙƙarfan ƙafar ƙafa guda uku{0} waɗanda ke tafiyar da motsin maganadisu cikin sauƙi da inganci. Mun yi amfani da ƙananan zanen ƙarfe na silica -arancin tare da lalata{3}}magani don rage asarar kuzari da hayaniya. Yana da sauƙi mai sauƙi, i, amma wanda muka tsara a hankali don ɗorewa da aiki cikin nutsuwa, kiyaye tsarin ku a ƙarƙashin kowane nau'in lodi. |
2.2 Ƙarfin iska da Haɗin kai
![]() |
A gefen ƙananan wutar lantarki -, muna amfani da iska mai ƙarfi tare da ƙwanƙwaran mashin bas ɗin jan ƙarfe. Wannan yana nufin gajerun kewayawa ba za su ɓata musu rai ba, kuma zafi yana ɓarna da kyau. Babban - gefen wutar lantarki yana amfani da takarda{4}}wayar aluminium mai rufi{5}}karami, farashi{6}mai inganci, kuma abin dogaro. Tare, waɗannan zaɓuɓɓukan iska suna ba ku ma'auni da muke fata koyaushe: mai ɗorewa, inganci, kuma a shirye don dogon aiki na waje-. |
2.3 Halayen Kariya & Kariyar Hankali
![]() |
Tsaro bai kasance abin tunani ba. Mun ƙara Bay{1}O-Fus ɗin net da na yanzu{3}}iyakance fis ɗin madadin don kariya mai ɗorewa, yayin da babu{4}}mai sauya matsa lamba yana ba da damar daidaita wutar lantarki ±2 × 2.5%. Wannan yana nufin lokacin da yanayin grid ya canza, masu taswirar za su iya daidaitawa ba tare da yin tsalle ba. Muna so mu yi la'akari da su a matsayin masu kaifin basira, abokan tsaro don hanyar sadarwar rarraba ku. |
2.4 Tsarin Tanki da Juriya na Yanayi
![]() |
2500 kVA uku pad pad wanda aka ɗora tankin na'ura da kanta an yi shi ne daga ƙarfe mai laushi da aka rufe, an kulle shi don ƙarin ƙarfi. Kowane saman yashi ne, an haɗa sasanninta, sannan an lulluɓe shi da yanayi{2}} da UV{3}} resistant epoxy primers da topcoats. Yana da wuya a iya sarrafa rana ta Kanada, dusar ƙanƙara, da ruwan sama yayin da ake kiyaye abubuwan cikin gida lafiya da kuma kiyaye ingantaccen zafi. Ba dole ba ne ka damu da abubuwan da aka rufe su{6}. |
2.5 Tattaunawa da Tabbataccen Inganci
![]() |
Muna tattara mahimmanci da iska a hankali, haɗa jagororin, shigar da tanki da kayan haɗi, cika shi da man ma'adinai, kuma rufe shi. Sa'an nan kuma mu gudanar da shi ta cikin cikakken rukunin gwaje-gwaje na CSA{1}: juriya, rabo, lokaci - dangantaka, asara, amfani da jurewar wutar lantarki, juriyar insulation, ƙarfin wuta, da gwajin ɗigo. Gaskiya, muna duba komai sau biyu. Idan ya wuce, za ku iya amincewa da shi don yin abin dogaro daga ranar farko. |
03 Gwaji


Gwajin Na yau da kullun da Matsayin Gwaji
CSA C227.4 -21 Uku-tsari, pad{3}} masu rarraba tasfoma tare da keɓaɓɓen haɗe-haɗe masu ƙarfin wuta
CSA{0}}C802.1{3}}13 (R2022) Mafi ƙarancin Ƙimar Ƙirar Rarraba Mai Ruwa
1. Ma'aunin Juriya
2. Gwajin Rabo
3. Mataki -Gwajin dangantaka
4. Babu Asara Load Kuma Babu Load A Yanzu
5. Load asarar, Impedance Voltage da inganci
6. Gwajin Karfin Wutar Lantarki
7. Gwajin Juriya da Ƙarfin Wutar Lantarki
8. Gwajin Leak tare da Matsi don Masu Canjin Ruwa na Ruwa: Za a gudanar da gwajin zubar da ruwa a 50KPa don 12h ba tare da yaduwa ba. Babu nakasar dindindin.
9. Ma'aunin Juriya na Insulation
10. Gwajin Dielectric Oil
Sakamakon Gwaji
|
A'a. |
Gwajin Abun |
Naúrar |
Dabi'un Karɓa |
Ƙimar Ma'auni |
Kammalawa |
|
1 |
Ma'aunin Juriya |
% |
Matsakaicin juriya rashin daidaituwa |
0.82 |
Wuce |
|
2 |
Gwajin Rabo |
% |
Bambancin rabon ƙarfin lantarki akan babban tapping: ƙasa da ko daidai da 0.5% |
-0.06~-0.05 |
Wuce |
|
3 |
zango{0}}gwajin dangantaka |
/ |
Dyn1 |
Dyn1 |
Wuce |
|
4 |
A'a -asara da tashin hankali na halin yanzu |
/ |
I0:: bayar da ma'auni darajar |
0.35% |
Wuce |
|
P0: ba da ƙima mai ƙima |
2.214 kW |
||||
|
Hakuri don babu asarar kaya shine +10% |
/ |
||||
|
5 |
Load hasarar impedance ƙarfin lantarki da inganci |
/ |
t:85 ku Haƙuri don impedance shine ± 7.5% Haƙuri don jimlar asarar kaya shine +6% |
/ |
Wuce |
|
Z%: ƙimar da aka auna |
5.69% |
||||
|
Pk: ƙimar ƙima |
22.183 kW |
||||
|
Pt: ƙima mai ƙima |
24.397 kW |
||||
|
Ingancin ba kasa da 99.37% |
99.43% |
||||
|
6 |
Gwajin Karfin Wutar Lantarki |
kV |
HV: 50kV 60s LV: 10kV 60s |
Babu rushewar ƙarfin gwajin da ke faruwa |
Wuce |
|
7 |
Jarrabawar Juriya da Wutar Lantarki |
kV |
Wutar lantarki mai aiki (KV): 2 Ur |
Babu rushewar ƙarfin gwajin da ke faruwa |
Wuce |
|
Duration(s):48 |
|||||
|
Mitar (HZ): 150 |
|||||
|
8 |
Gwajin Leaka |
kPa |
matsa lamba: 50kPA Tsawon lokaci: 12h |
Babu yabo kuma babu Lalacewa |
Wuce |
|
9 |
Ma'aunin Resistance Insulation |
GΩ |
HV{0}LV zuwa Ground |
2.32 |
/ |
|
LV -HV zuwa Ground |
2.83 |
||||
|
HV&LV zuwa Ground |
2.10 |
||||
|
10 |
Gwajin Mai |
/ |
Ƙarfin Dielectric; |
56.1 kV |
Wuce |
|
Abubuwan Danshi |
9.7 mg/kg |
||||
|
Factor Dissipation |
0.00204% |
||||
|
Furan Analysis |
0.03 |
||||
|
Gas Chromatography Analysis |
/ |
04 Shiryawa da jigilar kaya


05 Kwarewar SCOTECH
A SCOTECH, muna isar da miliyoyin kVA na tasfoma kowace shekara, a duk duniya. Daga CSA zuwa ma'auni na IEEE, ƙananan raka'a 100 kVA zuwa manyan tsarin 5000 kVA, kowane mai canzawa yana ɗaukar sadaukarwar mu don ƙira, gwaji, da aminci. Wadannan guda biyu 2500 kVA? Waɗannan su ne cikakken misali na wannan ƙwarewar{5}} da aka ƙirƙira don aiwatarwa, gina su don ɗorewa, kuma a shirye suke don ci gaba da sarrafa grid na Kanada ba tare da tsangwama ba.

Hot Tags: three phase pad mounted transformers,manufacturer,sapplier,price,cost
You Might Also Like
300 kVA Pad -wanda aka ɗora Transformer-34.5/0.208 k...
500kVA Kushin Dutsen Mai Canjawa-14.4 / 0.208 kV|Amu...
500 kVA Matattu Gaban Kushin Haɓaka Mai Canjawa-24.9...
5 MVA Pad Dutsen Masu Canzawa-33 / 0.48 kV|Amurka 2025
3000 kVA Kushin Haɓaka Mai Canjawa-25 / 0.6 kV|Kanad...
1000 kVA Kushin Dutsen Mai Canjawa-13.8 / 0.46 kV|Gu...
Aika Aikace-aikacen