2500 kVA Masu Canzawa Pad-12.47 / 0.48 kV|Amurka 2025

2500 kVA Masu Canzawa Pad-12.47 / 0.48 kV|Amurka 2025

Ƙasar Bayarwa: Amurka 2025
Yawan aiki: 2500 kVA
Wutar lantarki: 12.47/0.48 kV
Feature: tare da IFD
Aika Aikace-aikacen

 

 

2500 kVA three phase pad mounted transformer

Amintacce kuma abin dogaro, wadatar wutar lantarki mai hankali, taswirar lokaci uku{0} yana kare bukatun ku!

 

 

01 Gabaɗaya

1.1 Bayanin - Ƙarfin Koren, Rarraba Waya

An gina 2500 kVA uku -fase pad{2}} na'ura mai ɗaukar wuta da aka kawo wa kasuwannin Amurka tare da ƙa'idodin ingancin DOE a hankali kuma an tsara su a kusa da dorewar muhalli na tsawon lokaci, ta amfani da tankin ƙarfe na bakin karfe, tsarin kariya na hankali, da ƙaramin tsari{6} asara wanda a zahiri yana rage sharar makamashi. Ta hanyar rage asara, shimfiɗa rayuwar sabis, da kiyaye kiyayewa yana buƙatar ƙayyadaddun ƙayyadaddun abubuwa, injin taswira yana ba da ƙarfi da ƙarfi mai ƙarfi, a nutse yana rage sawun sa yayin da yake tallafawa hanyar sadarwa mai dorewa.

 

 

1.2 Ƙayyadaddun Fasaha

2500 kVA kushin da aka ɗora nau'in ƙayyadaddun bayanai da takaddun bayanai

Isarwa zuwa
Amurka
Shekara
2025
Nau'in
Tashin wutar lantarki
Daidaitawa
Amurka
Ƙarfin Ƙarfi
2500 kVA
Yawanci
60HZ
Mataki
3
Ciyarwa
Madauki
Gaba
Matattu
Nau'in Sanyi
ONAN
Babban Voltage
12.47GrdY/7.2kV
Na biyu Voltage
0.48Y/0.277 kV
Abubuwan Iska
Aluminum
Tank Material
Bakin Karfe
Kayan daki
Bakin Karfe
Matsala ta kusurwa
YNyn0
Impedance
5.75%
Matsa Canji
Farashin NLTC
Taɓa Range
±2*2.5%
Babu Asara Load
2.4 kW
Akan Rasa Load
15.79 kW
Na'urorin haɗi
Daidaitaccen Kanfigareshan

 

 

1.3 Zane

2500 kVA kushin da aka ɗora zane da girman hoto.

2500 kVA three phase pad mounted transformer diagram 2500 kVA three phase pad mounted transformer nameplate

 

1.4 Amfanin Amfanin Makamashi

 

FIVE-COLUMN CORE

 

DOE-Ƙarancin Ƙarfafawa-Ƙarancin Ƙira

 

Na'urar taswira ta cika buƙatun dacewa na DOE, wanda ke nufin babu{0}}asashensa na 2.4 kW da asarar nauyi na 15.79 kW yana tsayawa akai-akai. Ko da yake waɗannan lambobin suna kama da ƙanana a keɓance, suna tarawa cikin dogon lokaci{4} tanadin makamashi wanda ke rage farashin aiki da kuma nauyin muhalli tsawon shekaru na ci gaba da aiki.

 

Ingantaccen Da'irar Magnetic - Biyar{1}}Column Core

 

Ƙaƙwalwar ginshiƙi guda biyar - yana ƙirƙirar hanyar maganadisu mai santsi, yana rage ɗimbin yawa, yana murkushe masu jituwa, da rage ɗumbin ɗumbin ɗumbin ɗumbin yawa waɗanda gidajen wuta ke samarwa galibi. Har ila yau, a zahiri yana yanke asara mai aiki, yana barin tsarin gabaɗayan ya yi aiki da kyau kuma tare da kwanciyar hankali mai natsuwa wanda ke jin niyya maimakon na bazata.

 

ONAN Natural Cooling

 

Tsarinsa na sanyaya ONAN ya dogara gabaɗaya akan motsin iska na halitta{0}}babu magoya baya, babu injina, babu wani ƙarin ƙarfin zane{1} don haka injin ɗin yana sanyaya kansa da kusan sauƙi mai sauƙi, yana amfani da kwararar iska don daidaita yanayin zafi yayin da yake guje wa amfani da kuzari, rage hayaniya, da rage dogon{2}} buƙatar kiyaye lokaci.

 

02 Masana'antu

2.1 Kori

Yin amfani da ginshiƙi -sashi na biyar{1}} yana tabbatar da rarrabawar maganadisu iri ɗaya ga kowane lokaci, yana samun kyakkyawar haɗakar maganadisu. Wannan ƙirar ba wai kawai tana rage ɓoyayyen juzu'in maganadisu ba ne amma kuma yana haɓaka ƙarfin jujjuyawar na'ura mai canzawa, don haka yana haɓaka aikin gabaɗaya. Tsarin ginshiƙi guda biyar- yana danne daidaitattun jituwa, yana rage hayaniya, kuma yana rage asarar zafi, yana tabbatar da aminci da aminci a ƙarƙashin yanayi daban-daban.

Bugu da ƙari, haɗin Y{0}Y tare da ginshiƙi guda uku-sashi na biyar{2}} yana goyan bayan ƙaddamar da tsaka-tsaki, wanda ke inganta sarrafa kaya marasa daidaituwa da gajeriyar kuskuren kewayawa.

2500 kVA three phase pad mounted transformer iron core
 

 

2.2 Taron Karshe

1. Sanya Sashe Mai Aiki cikin Tankin Mai:Tasa sashin mai aiki na taswirar (cibiya da iska) kuma sanya shi cikin tankin mai.

2. Haɗin Wutar Lantarki:Haɗa iskoki zuwa gandun daji, tabbatar da amintattun hanyoyin haɗin kai-.

3. Shigar da Na'urorin haɗi:Shigar da na'urorin haɗi, gami da ma'auni uku da bawul ɗaya, tare da sauran abubuwan da ke da alaƙa.

4. Rufe Tankin Mai:Rufe tankin mai kuma a cika shi da mai na transfoma don yin rufi da sanyaya.

2500 kVA three phase pad mounted transformer final assembly

03 Halayen Muhalli

2500 kVA pad mounted transformer stainless steel tank
01

Tankin Karfe - Tsawon Rayuwa, Karancin Shara

Tankin bakin karfe yana tsayayya da lalata, yana jure matsanancin yanayi na waje, yana tsawaita rayuwar sabis fiye da daidaitaccen karfe, yana rage maye gurbin da sharar gida, kuma ya kasance mai sake yin fa'ida sosai.

02

Gano Laifin Ciki (IFD) 

IFD tana sa ido kan canje-canjen cikin gida da faɗakarwa da wuri, hana yaɗuwa, lalata kayan aiki, da haɗarin muhalli kafin su haɓaka.

Internal Fault Detector (IFD) 
Aluminum Windings
03

Aluminum Windings - Ƙafafun Carbon Sauƙaƙe

Iskar Aluminum tana amfani da ƙarancin ƙarfi don samarwa fiye da jan ƙarfe, watsar da zafi yadda ya kamata, rage sawun carbon, da goyan bayan ingantaccen injin na'ura mai tsawo-.

 

04 Gwaji

A'a.

Gwajin Abun

Naúrar

Dabi'un Karɓa

Ƙimar Ma'auni

Kammalawa

1

Ma'aunin Juriya

%

Matsakaicin juriya rashin daidaituwa

2.43

Wuce

2

Gwajin Rabo

%

Bambancin rabon ƙarfin lantarki akan babban tapping: ƙasa da ko daidai da 0.5%

0.03-0.05

Wuce

3

zango{0}}gwajin dangantaka

/

YNyn0

YNyn0

Wuce

4

A'a -asara da tashin hankali na halin yanzu

/

I0:: bayar da ma'auni darajar

0.26%

Wuce

P0: bayar da ma'auni (digiri 20)

2.302 kW

Hakuri don babu asarar kaya shine +10%

/

5

Load hasarar impedance ƙarfin lantarki da inganci

/

t:85 ku

Haƙuri don impedance shine ± 7.5%

Haƙuri don jimlar asarar kaya shine +6%

/

Wuce

Z%: ƙimar da aka auna

5.79%

Pk: ƙimar ƙima

16.196 kW

Pt: ƙima mai ƙima

18.498 kW

Ingancin ba kasa da 99.53%

99.53%

6

Gwajin Karfin Wutar Lantarki

kV

LV: 10kV 60s

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

7

Jarrabawar Juriya da Wutar Lantarki

kV

Wutar lantarki mai aiki (KV):

2 Ur

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

Duration(s):60

Mitar (HZ): 120

8

Gwajin Leaka

kPa

Aiwatar da matsa lamba: 20kPA

Tsawon lokaci: 12h

Babu yabo kuma babu

Lalacewa

Wuce

9

Ma'aunin Resistance Insulation

GΩ

HV{0}LV zuwa Ground

21.6

/

LV -HV zuwa Ground

19.4

HV&LV zuwa Ground

20.9

10

Gwajin Mai

/

Ƙarfin Dielectric;

58,1 kv

Wuce

Abubuwan Danshi

9.4 mg/kg

Factor Dissipation

0.00211%

Furan Analysis

Kasa da ko daidai da 0.03

Gas Chromatography Analysis

/

 

2500 kVA three phase pad mounted transformer test
2500 kVA three phase pad mounted transformer fat

 

 

05 Kiɗa da jigilar kaya

2500 kVA three phase pad mounted transformer packaging
2500 kVA three phase pad mounted transformer shipping

 

 

06 Aikace-aikace & Koren Amfani

6.1 Dogon -Fa'idodin Muhalli

Tsawon rayuwar sabis yana nufin ƙarancin maye gurbin da ƙananan amfani da kayan aiki, yana tallafawa dorewa.

Ƙananan ƙira{0}ƙasa yana adana kuzari gabaɗaya, rage farashi da tasirin muhalli tsawon shekaru da yawa.

Tankuna masu ɗorewa suna rage sauye-sauye da ɓata mai, suna kiyaye ayyuka mafi tsabta da kore.

IFD tana gano kurakurai da wuri, hana yadudduka ko lalacewa da rage haɗarin muhalli.

 

6.2 Abubuwan da suka dace

3 phase pad mounted transformer applicable scenarios 1
Wuraren Kasuwanci/Masana'antu
3 phase pad mounted transformer applicable scenarios 4
Rukunin Gine-ginen Birane
3 phase pad mounted transformer applicable scenarios 2
Tsarin Rarraba Wutar Jama'a

 

 

 