5 MVA Pad Dutsen Masu Canzawa-33 / 0.48 kV|Amurka 2025
Yawan aiki: 5000kVA
Wutar lantarki: 33/0.48kV
Feature: tare da saman ma'aunin zafi da sanyio

Maɓalli na grid mai wayo, na'ura mai ɗaukar hoto na zamani guda uku- yana ƙarfafa gaba!
01 Gabaɗaya
1.1 Fagen Aikin
5000 kVAuku fase kushin saka transformerAn isar da shi zuwa Amurka a cikin 2025. Ƙarfin ƙarfin wutar lantarki shine 5000 kVA tare da sanyaya ONAN. Babban ƙarfin lantarki shine 33GrdY/19.053kV tare da kewayon tapping ± 2*2.5% (NLTC), ƙarfin lantarki na biyu shine 0.48Y/0.277kV, sun kafa ƙungiyar vector na YNyn0.
Na'urar canza wutar lantarki da ake amfani da ita sosai a tsarin rarraba birane da karkara. Babban aikinsa shi ne musanya babban{3}}lantarki mai ƙarfi zuwa ƙaramar wutar lantarki, ba da damar samar da lafiya ga masu amfani da kasuwanci, masana'antu, da mazauna. The pad Dutsen transformers kunshi rufaffiyar tanki bakin karfe tsara don jure yanayi daban-daban. Akwatin ya ƙunshi na'ura mai canzawa, na'urori masu sauyawa, kayan kariya, da sauran abubuwan da ake buƙata na lantarki. Ƙirƙirar kushin lokaci guda uku- - da aka ɗora tasfoma ya ƙunshi matakan tsaro da yawa, gami da kariyar wuce gona da iri, gajeriyar kariyar kewayawa, da tsarin ƙasa don tabbatar da amintaccen aiki da kulawa. Wannan 5000 kVA uku -saitin kushin{14}} da aka ɗora tasfoma, sanye take da maɓalli huɗu{15}, yana haɗa babban ƙarfin wuta tare da sassauƙar sarrafa kaya, samar da masu amfani da amintaccen, tsayayye, da ingantaccen wutar lantarki.
Saboda girman iyawar na'urar na'ura, daidaitattun fis ɗin bayoneti da ake samu a kasuwa ba su dace da kariyar sa ba. Ana magance wannan ƙalubalen gabaɗaya ta hanyar ƙirarmu ta ci-gaba: iskar da aka ƙarfafa tare da matakan ƙarfafawa da ingantaccen tsarin sanyaya yana haɓaka iyawar da yake da ita na jure magudanar ruwa da magudanar ruwa; haɗe tare da ƙira mai girma - da kuma haɗaɗɗen tsarin sa ido mai wayo, ana murkushe abubuwan da ba su dace ba na ciki yadda ya kamata kuma an riga an yi gargaɗin-. Sakamakon haka, injin na'urar na'ura tana samun tsayin daka da tsayin lokaci{4}} aiki abin dogaro ba tare da dogaro da kariyar fis na waje ba.
1.2 Ƙayyadaddun Fasaha
5000kVAuku fase kushin saka transformerbayani dalla-dalla da takardar bayanan
|
Isarwa zuwa
Amurka
|
|
Shekara
2025
|
|
Nau'in
Face kushin hawa uku na wuta
|
|
Daidaitawa
IEEE Std C57.12.34-2022
|
|
Ƙarfin Ƙarfi
5000kVA
|
|
Yawanci
60HZ
|
|
Ciyarwa
Madauki
|
|
Gaba
Matattu
|
|
Mataki
Uku
|
|
Nau'in Sanyi
ONAN
|
|
Babban Voltage
33GrdY/19.053kV
|
|
Na biyu Voltage
0.48Y/0.277kV
|
|
Abubuwan Iska
Aluminum
|
|
Impedance
6.5%
|
|
Matsa Canji
Farashin NLTC
|
|
Taɓa Range
±2*2.5%
|
|
Babu Asara Load
4.23 kW
|
|
Akan Rasa Load
51.5 kW
|
|
Na'urorin haɗi
Daidaitaccen Kanfigareshan
|
|
Jawabi
N/A
|
1.3 Zane
5000kVA kushin Dutsen masu canzawa girma da cikakkun bayanai masu nauyi
![]() |
![]() |
02 Masana'antu
2.1 Transformer bushing
Kebul na lantarki suna aiki azaman hanyar haɗin gwiwa tsakanin ƙananan kushin wutar lantarki masu ɗaukar wutar lantarki bushes bushings da nau'ikan wutar lantarki daban-daban: don sauƙaƙan yanayin ɗaukar nauyi, kebul guda ɗaya da aka haɗa da kowane daji galibi yana isa don biyan buƙatun samar da wutar lantarki. Koyaya, yayin da ake mu'amala da kayan aiki mafi girma ko na'urori masu ɗaukar nauyi, ana buƙatar haɗa igiyoyi da yawa a layi daya zuwa daji iri ɗaya.
Waɗannan ƙananan ƙananan bushings{0}voltage suna zuwa{1} an shirya su da ramukan waya da yawa, waɗanda aka tsara musamman don tallafawa haɗin haɗin kebul da yawa. Musamman ma, ainihin adadin ramukan da aka tanadar don kowane ƙananan ƙananan ƙarfin lantarki ana ƙaddara gabaɗaya ta girman girman da ƙayyadaddun na'urorin lantarki masu dacewa.

2.2 matakin mai

Ma'aunin matakin mai shine gilashin gani mai mahimmanci, yawanci ana ɗora shi a gefen tanki, yana ba da alamar gani na ƙarar ruwa mai rufewa. Samar da ma'aunin zafin jiki{1} da aka biya, yana ba da damar ingantaccen sa ido don tabbatar da cewa matakin mai ya kasance a cikin amintaccen kewayon aiki, wanda ke da mahimmanci ga ingantaccen rufin, sanyaya, da tsawon lokaci - amintaccen na'urar taswira.
2.3 Tanko
An yi tankin man ne da karfe kuma ana kula da shi da mayuka masu lalacewa don haɓaka juriya ga oxidation da lalata, yana tsawaita rayuwar sabis. Tsarin tankin mai yana hana danshi da ƙura daga shiga, yana kare ingancin mai da hana lalacewa. Man da ke cikin tanki yana da kyawawan kaddarorin kariya na lantarki, yadda ya kamata ya hana gajerun da'irori na wutar lantarki da al'amurran da suka shafi ɗigogi, don haka yana kare ainihin abubuwan na'urar.

2.4 mai canza matsi

Babu -mai canza tap tap (NLTC) na kushin da aka ɗora tasfoma shine maɓalli na ƙayyadaddun wutar lantarki akan babban gefen wutar lantarki. Ana aiki da shi kawai lokacin da wutar lantarki ta ƙare -, yana canzawa tsakanin famfo daban-daban don rama juzu'i na grid da buƙatun lodi, yana tabbatar da tsayayyen ƙarfin fitarwa. Karamin tsari, ya dace sosai da yanayin aiki na waje wanda aka ɗora pad ɗin.
03 Gwaji
Gwajin Juriya na Matsi (Gwajin Ƙarfin Ƙarfi):- Aiwatar da babban ƙarfin lantarki zuwa sassa daban-daban na taswirar (kamar windings da casing, tsakanin windings daban-daban, da sauransu) don gudanar da gwajin juriya. Manufar ita ce tabbatar da ko taswirar zata iya kula da aikinta na rufi a ƙarƙashin yanayin lodin lantarki.
- Akwai manyan nau'ikan gwaje-gwajen juriya guda biyu: gwajin juriya na DC da gwajin ƙarfin ƙarfin AC. Gwajin jurewar wutar lantarki na DC galibi ana amfani da shi don gano polarity da ƙarfin rufin, yayin da gwajin jurewar wutar lantarki na AC galibi ana amfani da shi don daidaita ƙarfin wutar lantarki na taswira a ainihin aiki.


04 Shiryawa da jigilar kaya


05 Yanar Gizo da Takaitawa
Da farko, an riga an yi simintin siminti don daidaita ma'auni na naúrar da ɗaukar nauyi, tare da keɓaɓɓen tashoshi don bi da igiyoyi. Bayan haka, ana ɗaga injin ɗin zuwa matsayi ta amfani da kayan ɗagawa masu dacewa (tare da kulawa da hankali don daidaitawa yayin ɗagawa), sannan a daure da ƙarfi zuwa ƙafar ƙafa tare da ƙugiya.
Bayan haka, manyan igiyoyin wutan lantarki masu girma{0}} da ƙananan - ana haɗa su zuwa tashoshin da aka keɓe su{2}}kowace hanyar haɗin gwiwa tana daɗaɗawa yadda ya kamata, kuma ana tabbatar da kariyar rufi don saduwa da ƙa'idodin aminci. Bayan wayoyi, ana gudanar da bincike na ciki: tabbatar da canjin lodin yana cikin madaidaicin matsayi (aminci), duba madaidaicin tashoshi, da kuma tabbatar da gina - a cikin mitoci/bangarori.
A ƙarshe, ana yin bitar tsaro kafin - don kawar da haɗari masu yuwuwa, sannan na'urar wutar lantarki ta shirya don fara gyara aikin.

Hot Tags: pad Dutsen transformers, manufacturer, maroki, farashin, farashi
You Might Also Like
2500 kVA Residential Electrical Transformers-34.5/0....
150 kVA Mai Canjin Wuta na Wuta-24.94 / 0.208 kV|Amu...
300 kVA Pad -wanda aka ɗora Transformer-34.5/0.208 k...
750 kVA Kushin Haɗa Mai Canjawa-13.2 / 0.48 kV|Amurk...
750 kVA Kushin Haɓaka Kudin Canji-13.8 / 0.22 kV|Guy...
2500 kVA Kushin Haɓaka Masu Canjin Rarraba-25/0.6 kV...
Aika Aikace-aikacen