1000 KVA Mai Cika Mai Sauƙi-21 / 0.48 KV|Amurka 2025

1000 KVA Mai Cika Mai Sauƙi-21 / 0.48 KV|Amurka 2025

Kasar: Amurka 2025
Yawan aiki: 1000 kVA
Ƙarfin wutar lantarki: 21D-0.48Y/0.277 kV
Feature: tare da mai kama
Aika Aikace-aikacen

 

image001

Kushin Zamani{0}Mounted Transformer: Amintaccen, Ingantacce, Ya ƙunshi.

 

 

01 Gabaɗaya

1.1 Bayanin Aikin

1000 kVA three phase pad mounted transformer an isar da ita zuwa Jamaica a shekarar 2025. Ƙarfin wutar lantarkin shine 1000 kVA tare da sanyaya ONAN. Babban ƙarfin lantarki is21D kV tare da ± 2 * 2.5% tapping range (NLTC), ƙananan ƙarfin lantarki shine 0.48Y / 0.277 kV, sun kafa ƙungiyar vector na Dyn1.

Wannan 1000kVA guda uku -mai mai -mai nutsewa - wanda aka ɗora tasfoma, yana tsaye a tsakiyar cibiyar rarraba wutar lantarki a cibiyoyin bayanai na zamani ko wuraren shakatawa na masana'antu, yana aiki a matsayin babban mai kula da samar da wutar lantarki. An ƙera shi musamman don ingantaccen aiki da dogaro mai ƙarfi mai shigowa 21kV mai shigowa babban ƙarfin lantarki zuwa 0.48kV ƙananan ƙarfin lantarki, yana kafa ginshiƙi don tabbatar da aiki mara yankewa na wurare masu mahimmanci. Don magance ƙalubale da yawa kamar ƙarfin walƙiya, haɗarin wuta, da lalata muhalli, wannan na'ura mai ɗaukar hoto tana haɗa jerin saitunan da suka wuce na al'ada: cikinsa yana cike da babban -aiki na FR3® na ester insulating fluid, wanda ba wai kawai yana ba da kyawawan kaddarorin wuta ba (K-}asashen wuta (K-}asashen waje) amma kuma yana ba da damshi sosai a wurin. tsawon rayuwar kayan aiki - mai yiwuwa ma ya ninka shi; ƙaƙƙarfan ƙaƙƙarfan ƙaƙƙarfan ƙaƙƙarfan ƙaƙƙarfan ƙaƙƙarfan ƙaƙƙarfan ƙaƙƙarfan foda (RAL 9003), yana haɗa mafi girman juriyar lalata tare da kayan ado na masana'antu na zamani yayin nuna zafi don taimakawa sanyaya; mafi mahimmanci, ya zo daidai da ƙima tare da manyan masu kama aiki, gina ingantaccen layin tsaro don ingantacciyar iska da rage haɗarin faɗuwar lokacin da ba zato ba tsammani sakamakon wutar lantarki da 30-40%. Daga qarshe, waɗannan fasalolin yankan{19}} suna fassara su zuwa ƙididdige ƙima a sarari-ta hanyar haɓaka lokaci, rage buƙatun kulawa, da haɓaka jimillar kuɗin mallaka, wannan tafsirin ya zarce ainihin aikinsa ya zama kadara mai dabara wacce ke haɓaka ƙarfin ƙarfin samar da wutar lantarki, yana kiyaye saka hannun jari, da sadaukar da kai ga ci gaba mai dorewa.

 

 

 

1.2 Ƙayyadaddun Fasaha

1000 kVA kushin da aka ɗora nau'in ƙayyadaddun bayanai da takaddun bayanai

Isarwa zuwa
Amurka
Shekara
2025
Nau'in
Tashin wutar lantarki
Daidaitawa
Saukewa: IEC60076
Ƙarfin Ƙarfi
1000 kVA
Yawanci
60HZ
Mataki
3
Ciyarwa
Madauki
Gaba
Matattu
Nau'in Sanyi
KNAN
Babban Voltage
21d kV
Na biyu Voltage
0.48Y/0.277 kV
Abubuwan Iska
Aluminum
Ƙungiyar Vector
Dyn1
Impedance
5.75%
inganci
99.43%
Matsa Canji
Farashin NLTC
Taɓa Range
±2*2.5%
Babu Asara Load
1.3 kW
Akan Rasa Load
6.94 kW

 

1.3 Zane

1000 kVA kushin da aka ɗora zane da girman hoto.

image003 image005

 

 

02 Masana'antu

2.1 Kori

image007

Zuciyar naúrar mu madaidaici ne{0}} ginanniyar ginshiƙi mai ƙarancin ƙarfe{1} hasarar siliki, yana tabbatar da nagartaccen kwanciyar hankali a ƙarƙashin kaya masu nauyi. Wannan yana haifar da aiki mai sanyaya har zuwa 25% don tsawon rayuwa da kariya mai ƙarfi don kayan aikin ku masu mahimmanci, yana ba da ingantaccen amincin da kuke buƙata don rage lokacin raguwa da haɓaka kwanciyar hankali.

 

2.2 Guda

An ƙirƙira don mahalli masu buƙata kamar tsire-tsire na masana'antu, iskar tafsirin mu na yin amfani da ci gaba da jujjuyawar madubin jan ƙarfe (CTCC) tare da ƙarancin zafin jiki na Nomex. Wannan ƙaƙƙarfan ƙira yana tunkarar ƙalubalen lalacewar zafi a ƙarƙashin ɗorawa na cyclic, maƙasudin gazawar gama gari a daidaitattun raka'a. Sakamako a gare ku shine haɓaka 15% a cikin ɗan gajeren lokaci - kewayawa juriya mai ƙarfi da tabbataccen tsawon shekaru 25 ko da a ƙarƙashin manyan kaya, yana rage haɗarin ƙarancin lokaci mai tsada da sadar da kwanciyar hankali mara misaltuwa.

image009

 

2.3 Tanko

image011

An gina tankin injin ɗin mu daga babban{0}}ƙarfi, ƙarancin ƙarfe-karfe kuma yana fasalta ƙaƙƙarfan ƙira, yana kawar da buƙatar radiators na waje a mafi yawan yanayi. Wannan aikin da ba shi da matsala, guda ɗaya{3} yana magance damuwarku game da ɗibar mai da dogon lokaci{4}} a cikin buƙatun muhallin waje. A gare ku, wannan yana haifar da tanki mai ingantacciyar rayuwar sabis fiye da shekaru 40, rashin kulawa akan walda ko radiyo, da ɗigo{7} kyauta wanda ke kiyaye rukunin yanar gizonku kuma yana kawar da haɗarin gyara muhalli mai tsada.

 

2.4 Taron Karshe

A cikin rukunin kasuwanci inda farashin makamashi ke bayyana riba, taron ƙarshe na transformer yana inganta kowane haɗin gwiwa da haɗin gwiwa don ƙarancin asara. Hanyoyin mallakarmu suna tabbatar da daidaitaccen jeri na asali da coils, yana rage asarar nauyi da kashi 15% sabanin ma'aunin masana'antu. A gare ku, wannan yana nufin ingantaccen 2% mafi girma- inganci, rage dubunnan farashin aiki na shekara-shekara da kuma isar da ROI mai sauri, yayin da ƙarin garantin mu da ke da goyan bayan gwajin masana'anta yana ba da kariya ga saka hannun jari mara misaltuwa.

image013

 

 

03 Gwaji

Gwajin daidaitaccen gwajin mu ya wuce ƙa'idodi na asali don haɗawa da cikakken asarar nauyi da ma'aunin amo, tabbatar da cewa kowace naúrar tana yin daidai daidai da ƙayyadaddun farantin sunanta. Wannan madaidaicin tsari yana ba da garantin cewa inganci da aiki na shiru da aka yi alkawari a cikin ƙasidarmu shine ainihin abin da kuke karɓa. Kuna samun bayanan aikin da aka tabbatar da kansa wanda ke nuna ingancin 99.43% a cikakken nauyi da matakan amo da ke ƙasa da 55 dB, yana ba da tanadin makamashi da ta'aziyyar muhalli da kayan aikin ku ke buƙata.

image015
image017

 

 

04 Shiryawa da jigilar kaya

4.1 Shiryawa

image019

A cikin masana'anta -zuwa{1}} na duniya - yanayin isarwa, na'urar tawul ɗin mu guda uku da aka ɗora tana kunshe a cikin IPPC{3}}akwatunan plywood masu dacewa tare da masana'antu{4}samar ƙarfafa ƙarfe, tela{5}wanda aka yi don samfura kamar 1000kVA. Ba kamar masu fafatawa ba, muna fuskantar ƙalubalen girgizar hanya, zafi, da kuma mugun aiki, cimma 0% na lalacewar sufuri da yanke jinkirin shigar abokin ciniki da kashi 25%. Wannan yana nuna bajintar aikin injiniyan fakitin kariya, yana tabbatar wa abokan ciniki cewa an kare jarin su a kowane mataki{11}}yana nuna himmarmu don dogaro da kuma barin su su mai da hankali kan mahimman ayyuka tare da kwanciyar hankali.

 

4.2 Shipping

Maganin jigilar kaya na DDP ɗin mu na mai taswira 1000kVA yana ƙarfafa duk kayan aiki - daga tashi daga tashar jiragen ruwa na China zuwa izinin kwastan Amurka da isar da rukunin ƙarshe - cikin fakitin farashi ɗaya ƙayyadaddun-. Muna magance rikitattun ƙalubalen rabe-raben kuɗin fito da buƙatun haɗin kai ta hanyar haɗin gwiwar Amurka da aka kafa, muna ceton ku 15{8}}20% a cikin jimlar farashin kayan aiki tare da sarrafa dillalai da yawa. Kuna karɓar cikakken tsinkayar farashi ba tare da kuɗaɗen mamaki ba, 30% saurin izinin kwastam, da sadaukarwar tallafin harsuna biyu - yana tabbatar da isar da saƙon zuwa wurin ku na Amurka.

image021

 

 

05 Yanar Gizo da Takaitawa

Kuna zabar fiye da na'ura mai canzawa - kuna zabar amintaccen abokin tarayya. Wannan 1000kVA pad{2} da aka ɗora tafsiri yana ba da ƙima fiye da kayan aikin kansa ta hanyar ingantaccen ƙarfinsa na musamman, ƙirar muhalli, da ingantaccen gini. Yana wakiltar ƙananan farashin aiki, mafi girman alhakin muhalli, da dogon{4}} dawo da kadari.

Bayanin abokin ciniki ya bayyana cewa "Bayan watanni shida na kimantawa mai tsauri, daga ƙarshe mun zaɓi wannan na'ura mai canzawa don aikin sabunta biranenmu. DOE{1} ƙwararrun ƙarfin kuzarin sa yana rage farashin aikinmu kai tsaye, yayin da fa'idodin muhalli na FR3 na ester ruwa ya ba mu gagarumin fa'ida a cikin tsarin amincewar muhalli. Mafi mahimmanci, gazawar sifili a cikin watanni takwas na aikin da ya dace. Bari mu taimake ka gina mafi wayo, kore, kuma mafi tattalin arziki tsarin rarraba wutar lantarki. Tuntuɓi ƙungiyar injiniyoyinmu a yau don ingantaccen bayani da cikakken bincike na ƙima.

image023

 

Hot Tags: 1000 kva mai cike da wutar lantarki, masana'anta, mai kaya, farashi, farashi

Aika Aikace-aikacen