2250 kVA Kushin Haɗa Mai Canjawa-12.47 / 0.6 kV|Amurka 2025

2250 kVA Kushin Haɗa Mai Canjawa-12.47 / 0.6 kV|Amurka 2025

Kasar: Amurka 2025
Yawan aiki: 2250kVA
Wutar lantarki: 12.47GrdY/7.2-0.6Y/0.347kV
Feature: Tare da mai FR3
Aika Aikace-aikacen

 

 

2250 kva pad mounted transformer-front-door-open

2250 kVA pad mounted transformer{1}} wanda aka kera don gonakin hasken rana, an gina shi don aminci, inganci, da kyakkyawar makoma mai haske.

 

01 Gabaɗaya

1.1 Fagen Aikin

Don tallafawa faɗaɗa tura tsarin makamashin hasken rana a kasuwannin Amurka, mun isar da 2250 kVA uku -kushin lokaci{4}}wanda aka ɗora shi musamman don aikace-aikacen aikace-aikacen photovoltaic (PV). An ƙera shi da ƙaƙƙarfan tsari guda biyar - da matattu{8}}gaba, madauki{9}} daidaitawar ciyarwa, wannan rukunin yana tabbatar da aminci, aminci, da sassaucin tsarin a cikin mahallin makamashi mai sabuntawa.

Wannan2250 kva kushin da aka saka tafsiriyana aiki tare da ƙarfin lantarki na farko na 12.47 GrdY / 7.2 kV da ƙarfin lantarki na biyu na 0.6Y/0.347 kV, yana mai da shi manufa don haɗawa da inverters na hasken rana da cibiyoyin rarraba ƙasa. Ƙungiyar vector YNyn0 tana ba da damar haɓaka ƙasa mai inganci kuma tana sauƙaƙe haɗin haɗin ƙananan ƙarfin lantarki guda uku{7} a cikin gonakin hasken rana. Tare da iska na aluminum, naúrar tana ba da ma'auni tsakanin aiki da ƙimar farashi.

Built with FR3 natural ester fluid, the transformer achieves a high level of environmental sustainability and fire safety, thanks to its high flash point (>300 digiri) da kuma biodegradability. KNAN (iskar da aka sanyaya - sanyaya) tana rage wahalar aiki da buƙatun kulawa yayin da ke tabbatar da kyakkyawan aikin zafi.

Ana isar da shi akan jadawali, wannan tafsiri yana ba da gudummawa kai tsaye ga abokin ciniki na faɗaɗa ababen more rayuwa na hasken rana, yana goyan bayan faffadan manufofin ƙasa na lalata da kuma sabunta grid. Yana nuna iyawarmu don yin ƙira mai girma{1}}arewa, kayan aiki{2}kayan aiki don haɓaka buƙatun ɓangaren makamashi mai sabuntawa.

 

 

1.2 Ƙayyadaddun Fasaha

2250 kVA kushin da aka ɗora ƙayyadaddun canji da takaddar bayanai

Isarwa zuwa
Amurka
Shekara
2025
Nau'in
Uku fanni kushin Dutsen transformer
Daidaitawa
IEEE Std C57.12.34-2022
Ƙarfin Ƙarfi
2250 kVA
Yawanci
60HZ
Ciyarwa
Madauki
Gaba
Matattu
Mataki
Uku
Nau'in Sanyi
KNAN
Liquid insulant
Farashin FR3
Babban Voltage
12.47 kV
Na biyu Voltage
0.6 kv
Ƙungiyar Vector
YNyn0
Abubuwan Iska
Aluminum
Impedance
5.75%
inganci
99.52%
Matsa Canji
Farashin NLTC
Taɓa Range
±2*2.5%
Babu Asara Load
2.4 kW
Akan Rasa Load
15.79 kW
Na'urorin haɗi
Daidaitaccen Kanfigareshan

 

1.3 Zane

2250 kVA kushin da aka ɗora girman mai canzawa da cikakkun bayanai masu nauyi

2250 kva pad mounted transformer diagram 2250 kva pad mounted transformer nameplate

 

 

02 Masana'antu

2.1 Kori

Ƙirar ainihin ƙafar ƙafa guda biyar{0} tana tabbatar da ingantaccen sarrafa sifili{1}}juyawar jeri da yanayin lodi mara daidaituwa, waɗanda suka zama ruwan dare a tsarin makamashin da aka rarraba. Madaukinsa -abinci da matattu- gini na gaba yayi dai-dai da ka'idojin aminci na Amurka kuma yana ba da damar shigar dacewa a filayen hasken rana, tashoshin jiragen ruwa, da wuraren shiga jama'a{7}}.

2250 kva pad mounted transformer five leg core

 

2.2 Guda

2250 kva pad mounted transformer

Wannan 2250 kva pad ɗorawa tafsiri yana fasalta babban iskar wutar lantarki tare da ƙirar waya{2}}, yana ba da adadi mai yawa don tabbatar da rarraba wutar lantarki iri ɗaya da kyakkyawan aikin rufewa. Ƙarƙashin wutar lantarki - yana amfani da ginin foil don sarrafa igiyoyin ruwa da kyau da kyau yayin rage asara. Tsarin ƙungiyar vector na YNyn0 yana goyan bayan tsaka-tsakin tsaka-tsaki akan duka manyan ɓangarorin ƙarfin lantarki da ƙarancin ƙarfi, haɓaka amincin tsarin da kwanciyar hankali{7}}mahimmin buƙatun don aikace-aikacen hotovoltaic. Bugu da ƙari, ƙididdiga masu ƙarancin ƙarfi guda biyu{9}} yana ba da damar haɗin kai masu sassauƙa zuwa saitunan kaya daban-daban, haɓaka amincin tsarin gabaɗaya da daidaitawa cikin ayyukan wutar lantarki.

 

2.3 Tanko

2250 kva kushin da aka ɗora wutar lantarki ya haɗa da tankin mai da aka hatimi da aka yi da ƙarfe mai laushi, wanda aka lulluɓe shi da ƙaƙƙarfan farin foda (RAL 9003) don haɓaka juriya na lalata. Rufin da aka kulle yana tabbatar da kafaffen hatimi, yana kare mai mai a ciki.

Taswirar yana fasalta radiyon da aka haɗa ta ɓangarorin biyu da kuma bayan tankin mai, waɗanda ke aiki azaman abubuwa masu sanyaya jiki ta hanyar haɓaka sararin samaniya na waje don jujjuyawar iska. Waɗannan na'urorin watsa shirye-shiryen suna waldawa da hatimi{1}} an haɗa su zuwa babban jikin tanki don tabbatar da yabo{2}} kyauta a ƙarƙashin hawan keke. Madaidaicin walda a wurin mu'amala yana tabbatar da ƙarfin injina da mai{4}} m, yayin da kuma yana ba da damar faɗaɗa zafin rana ba tare da lahani natsuwar tsari ko aikin sanyaya ba.

2250 kva pad mounted transformer sealed oil tank

 

2.4 Taron Karshe

2250 kva pad mounted transformer finall assembly

A mataki na ƙarshe na taro, wannan 2250 kVA pad - na'ura mai ɗaukar wuta da aka ƙera don aikace-aikacen makamashin hasken rana an sanye shi da 200A mai keɓance bushings na HV, tsararren tsaka-tsaki (H0), da resin -Spade spade{5}} nau'in LV bushings da ke da tashoshi 12-hole.

Tsarin kariyar taswira ya haɗa da fis ɗin bayoneti guda uku, na yanzu{0}}limiting fuses (CLF), da gwiwar hannu{1}} nau'in masu kama walƙiya tare da bambance-bambancen ƙarfe oxide waɗanda suka dace da ka'idodin IEEE 386, yana tabbatar da ƙaƙƙarfan ƙaƙƙarfan ƙaƙƙarfan ƙaƙƙarfan ƙaƙƙarfan kariya da kuskure a cikin matattu{3}} saitin gaba.

Gilashin ƙasa da aka sanya akan bangarorin HV da LV biyu suna haɓaka amincin shigarwa da amincin aiki.

 

 

03 Gwaji

Gwajin Na yau da kullun da Matsayin Gwaji

1. Ma'aunin Juriya: Dangane da IEEE C57.12.90-2021 Sashe na 5

2. Gwajin Rabo: Dangane da IEEE C57.12.90-2021 Sashe na 7

3. Mataki na -Gwajin dangantaka: Dangane da IEEE C57.12.90-2021 Sashe na 6

4. Babu Asara Load kuma Babu Load A halin yanzu: Dangane da IEEE C57.12.90-2021 Sashe na 8

5. Haɓaka Load, Ƙarfin Wutar Lantarki da inganci: Dangane da IEEE C57.12.90-2021 Sashe na 9

6. Gwajin Ƙarfin Wutar Lantarki: Dangane da IEEE C57.12.90-2021 Sashe na 10.6

7. Gwajin Jurewar Wutar Lantarki: Dangane da IEEE C57.12.90-2021 Sashe na 10.5.1

8. Ma'aunin Juriya na Insulation

9. Gwajin Leak tare da Matsi don Masu Canjin Ruwa na Ruwa: Za a gudanar da gwajin zubar da ruwa a 20KPa don 12h ba tare da yaduwa ba. Babu nakasar dindindin.

 

Sakamakon Gwaji

A'a.

Gwajin Abun

Naúrar

Dabi'un Karɓa

Ƙimar Ma'auni

Kammalawa

1

Ma'aunin Juriya

%

Matsakaicin juriya rashin daidaituwa

1.97

Wuce

2

Gwajin Rabo

%

Bambancin rabon ƙarfin lantarki akan babban tapping: ƙasa da ko daidai da 0.5%

Alamar haɗi: YNyn0

-0.14% ~ 0.11%

Wuce

3

zango{0}}gwajin dangantaka

/

YNyn0

YNyn0

Wuce

4

A'a -asara da tashin hankali na halin yanzu

/

I0:: bayar da ma'auni darajar

0.22%

Wuce

P0: bayar da ƙima (t:20 digiri)

2.200kW

Hakuri don babu asarar kaya shine +10%

/

5

Load hasarar impedance ƙarfin lantarki da inganci

/

t:85 ku

Haƙuri don impedance shine ± 7.5%

Haƙuri don jimlar asarar kaya shine +6%

/

Wuce

Z%: ƙimar da aka auna

5.88%

Pk: ƙimar ƙima

14.325 kW

Pt: ƙima mai ƙima

16.525 kW

Ingancin ba kasa da 99.52%

99.52%

6

Gwajin Karfin Wutar Lantarki

kV

HV/: 34kV 60s

LV/: 10kV 60s

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

7

Jarrabawar Juriya da Wutar Lantarki

kV

Wutar lantarki mai aiki (KV):2Ur

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

Duration(s):48

Mitar (HZ): 150

8

Gwajin Leaka

kPa

Aiwatar da matsa lamba: 20kPA

Babu yabo kuma babu

Lalacewa

Wuce

Tsawon lokaci: 12h

9

Ma'aunin Resistance Insulation

GΩ

HV{0}LV zuwa Ground:

2.01

/

LV -HV zuwa Ground:

1.66

HV&LV zuwa Ground

1.03

 

2250 kva pad mounted transformer test
2250 kva pad mounted transformer testing
2250 kva pad mounted transformer routine test
2250 kva pad mounted transformer leakage test

 

 

04 Shiryawa da jigilar kaya

2250 kva pad mounted transformer packing
2250 kva pad mounted transformer shipping
 

05 Yanar Gizo da Takaitawa

Wannan 2250 kVA guda uku -kushin lokaci{2}} wanda aka ɗora shi an tsara shi ne musamman don abubuwan amfani{3}} ma'aunin PV na hasken rana a kasuwar Amurka. Yana goyan bayan rarraba wutar lantarki mai ƙarfi da aminci tare da fasalulluka waɗanda suka dace da ƙa'idodin amincin Amurka, tabbatar da haɗin kai cikin gonakin hasken rana da tsarin makamashi mai sabuntawa.

An sanye shi da injuna na ci gaba da sanyaya, yana ba da ingantaccen aiki, eco{0}maƙasudi don aikace-aikacen makamashi mai tsabta. Abubuwan kariya masu ƙarfi suna tabbatar da aiki mai aminci a cikin matsanancin yanayi na waje.

An kera injiniyoyinmu don biyan buƙatun da ake buƙata na sashin makamashi na Amurka. Tuntuɓe mu don keɓantattun hanyoyin magance wutar lantarki ayyukan ku na hasken rana.

2250 kva pad mounted transformer-right-45-degree-view

 

Hot Tags: 2250 kva kushin saka transformer, manufacturer, maroki, farashin, farashi

Aika Aikace-aikacen