2000 kVA Kushin Haɗa Mai Canjawa-24 / 0.48 kV|Amurka 2024
Yawan aiki: 2000kVA
Wutar lantarki: 24000-480GrdY/277 V
Feature: DOE 2016 inganci

Inganci, mai aminci, da grid{0} shirye -Scotech's 2000 kVA pad -wanda aka ɗora tasfoma yana ba da ƙarfin kayan aikin zamani tare da kwarin gwiwa.
01 Gabaɗaya
1.1 Bayanin Aikin
Wannan 2000 kVA pad{1} da aka ɗora tafsiri ya dace da sabbin ƙa'idodin Amurka, gami da IEEE C57.12.34-2022 da DOE 2016 buƙatun dacewa. Yana saukar da ƙarfin wutar lantarki na farko daga 24kV zuwa fitarwa ta biyu na 480GrdY/277 V.
Yana nuna iskar jan ƙarfe da ƙungiyar vector Dyn1, sanyaya KNAN ɗin sa yana tabbatar da aiki mai ƙarfi. Muhimmin haɓakar muhalli da aminci ya fito ne daga amfani da ruwa na FR3 - haɓaka ƙimar ginin kore tare da rage haɗarin wuta sosai, yana mai da shi manufa don mahimman abubuwan more rayuwa da manyan saitunan birane.
Tare da aikin ciyarwar madauki, taswira yana haɗawa cikin sauƙi cikin zobe{0}} nau'in tsarin rarrabawa, yana haɓaka amincin tsarin da ba da damar kiyayewa na yau da kullun ba tare da katse sabis ba. Matattu{2} ƙiren gaba yana haɓaka amincin ma'aikaci.
An yi amfani da shi da farko a cikin rarraba wutar lantarki, wannan taranfomar tana yin ƙasa mai girma{0} shigar da wutar lantarki don haɗawa tare da tsarin sarrafa makamashi da kayayyakin samar da wutar lantarki ta ƙasa.
1.2 Ƙayyadaddun Fasaha
2000kVA uku lokaci kushin saka gidan wuta ƙayyadaddun bayanai da takardar bayanai
|
Isarwa zuwa
Amurka
|
|
Shekara
2024
|
|
Nau'in
Uku fanni kushin Dutsen transformer
|
|
Daidaitawa
IEEE Std C57.12.34-2022
|
|
Ƙarfin Ƙarfi
2000 kVA
|
|
Yawanci
60HZ
|
|
Ciyarwa
Madauki
|
|
Gaba
Matattu
|
|
Mataki
Uku
|
|
Nau'in Sanyi
KNAN
|
|
Liquid insulant
Farashin FR3
|
|
Babban Voltage
24 kv
|
|
Na biyu Voltage
0.48 kV
|
|
Ƙungiyar Vector
Dyn1
|
|
Abubuwan Iska
Copper
|
|
Impedance
5.75%
|
|
Ƙimar inganci da hasara
DOE 2016
|
|
Matsa Canji
Farashin NLTC
|
|
Taɓa Range
±2*2.5%
|
|
Babu Asara Load
1.420 kW
|
|
Akan Rasa Load
15.600 kW
|
|
Na'urorin haɗi
Daidaitaccen Kanfigareshan
|
1.3 Zane
2000kVA uku lokaci kushin saka transformer girma da nauyi cikakken bayani
![]() |
![]() |
02 Masana'antu
2.1 Kori
Gina tare da laminonin ƙarfe na silicon da yawa waɗanda aka keɓance ta hanyar varnish ko resin, SCOTECH cores suna danne magudanar ruwa yadda ya kamata kuma suna rage asara mai yawo. Wannan lamintaccen ƙira kuma yana rage asarar hysteresis, musamman yayin maimaita maganadisu. Yana tabbatar da inganci mafi girma kuma yana tsawaita rayuwar sabis na transfoma.

2.2 Guda

Wannan 2000 kVA Dyn1 mai taswira yana fasalta iskar jan ƙarfe tare da tsarin foil a gefen LV da jujjuyawar silindi mai yawa{2} Layer a gefen HV. Zane yana tabbatar da tsayin daka{4}} juriya na kewayawa, ƙaramin juzu'i, da kyakkyawan aikin zafi don ingantaccen aiki a ƙarƙashin shigar mai amfani 24kV.
2.3 Tanko
An sanye shi da na'urori kamar bawul ɗin taimako na matsa lamba, alamun matakin mai, da ma'aunin injin, tankin yana ba da damar sa ido na gaske na yanayin cikin gida{0}. Waɗannan fasalulluka suna goyan bayan rigakafin kuskure kuma suna haɓaka aminci a duk lokacin aikin taswira.

2.4 Taron Karshe

Scotech yana tabbatar da cewa an gano duk taswirar da aka isar da su a fili kuma an yi musu lakabi bisa ga ka'idodin "Lantarki na Lantarki" na 26. Yayin shigarwa, muna ba da shawarar cewa a ƙarfafa duk hanyoyin haɗin lantarki da tashoshi kowane UL 486A da UL 486B don tabbatar da dorewar dogon lokaci{{4}.
03 Gwaji
Gwajin Na yau da kullun da Matsayin Gwaji
1. Ma'aunin Juriya bisa ga IEEE C57.12.90-2021 Sashe na 5
2. Mataki na -Gwajin dangantaka bisa ga IEEE C57.12.90-2021 Sashe na 6
3. Gwajin Ratio bisa ga IEEE C57.12.90-2021 Sashe na 7
4. Babu Asara Load kuma Babu Load A halin yanzu bisa ga IEEE C57.12.90-2021 Sashe na 8
5. Haɓaka Load, Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarfafawa bisa ga IEEE C57.12.90-2021 Sashe na 9
6. Gwajin Juriya da Wutar Lantarki bisa ga IEEE C57.12.90-2021 Sashe na 10.5.1
7. Gwajin Ƙarfin Wutar Lantarki bisa ga IEEE C57.12.90-2021 Sashe na 10.6
8. Gwajin Leak tare da Matsi don Masu Canza Liquid Immersed - gwajin yayyo a 15 kPa za a gudanar da shi na sa'o'i 12 ba tare da yabo ba. Babu nakasar dindindin.
9. Ma'aunin Juriya na Insulation
10. Gwajin Dielectric Oil


Sakamakon Gwaji
|
A'a. |
Gwajin Abun |
Naúrar |
Dabi'un Karɓa |
Ƙimar Ma'auni |
Kammalawa |
|
1 |
Ma'aunin Juriya |
% |
Matsakaicin juriya rashin daidaituwa |
0.356 |
Wuce |
|
2 |
Gwajin Rabo |
% |
Bambancin rabon ƙarfin lantarki akan babban tapping: ƙasa da ko daidai da 0.5% Alamar haɗi: Dyn1 |
-0.02% |
Wuce |
|
3 |
zango{0}}gwajin dangantaka |
/ |
Dyn1 |
Dyn1 |
Wuce |
|
4 |
A'a -asara da tashin hankali na halin yanzu |
% kW |
I0:: bayar da ma'auni darajar P0: ba da ƙima mai ƙima Hakuri don babu asarar kaya shine +0% |
0.18% 0.985 |
Wuce |
|
5 |
Load asarar impedance ƙarfin lantarki da inganci |
% kW kW |
t:85 ku Z%: ƙimar da aka auna Pk: ƙimar ƙima Pt: ƙima mai ƙima Haƙuri don impedance shine ± 7.5% Haƙuri don jimlar asarar kaya shine +0% Ingancin ba kasa da 99.43% |
5.61% 7.740 8.725 99.46% |
Wuce |
|
6 |
Gwajin Karfin Wutar Lantarki |
kV |
HV: 40kV 60s LV: 10kV 60s |
Babu rushewar ƙarfin gwajin da ke faruwa |
Wuce |
|
7 |
Jarrabawar Juriya da Wutar Lantarki |
kV |
Wutar lantarki mai aiki (KV): 0.960 Duration(s):40 Mitar (HZ): 180 |
Babu rushewar ƙarfin gwajin da ke faruwa |
Wuce |
|
8 |
Gwajin Leaka |
kPa |
matsa lamba: 15kPA Tsawon lokaci: 12h |
Babu yabo kuma babu Lalacewa |
Wuce |
|
9 |
Ma'aunin Resistance Insulation |
GΩ |
HV{0}LV zuwa Kasa: LV -HV zuwa Ground: HV&LV zuwa Ground: |
2.51 2.60 3.88 |
/ |
|
10 |
Gwajin Dielectric Oil |
kV |
Yafi ko daidai da 40 |
52.0 |
Wuce |
04 Shiryawa da jigilar kaya


05 Yanar Gizo da Takaitawa
Scotech's 2000 kVA pad - wanda aka ɗora tasfoma an ƙirƙira shi don saduwa da sabbin ƙa'idodin Amurka, gami da IEEE C57.12.34-2022 da DOE 2016 buƙatun dacewa. Yana saukar da ƙarfin lantarki na farko na 24 kV zuwa fitarwa na biyu na 480GrdY/277 V, yana nuna iskar jan ƙarfe da ƙungiyar vector Dyn1 tare da sanyaya KNAN don tabbatar da abin dogaro, ingantaccen aiki. Amfani da ruwan FR3 mai mutunta muhalli yana rage haɗarin wuta kuma yana goyan bayan ƙa'idodin ginin kore, yana mai da shi manufa don mahimman abubuwan more rayuwa da muhallin birni.
Tankin ƙarfe mai ƙarfi ya haɗa da bawul ɗin taimako na matsa lamba, alamun matakin mai, da ma'aunin injin don sa ido na gaske{0}} da ƙarin amincin aiki. Scotech yana bin ƙaƙƙarfan lakabi da ƙa'idodin shigarwa don tabbatar da abin dogaro, ingantaccen isarwa mai inganci da tsayin lokaci{3}.
A matsayin amintaccen masana'anta na matsakaici - kayan aikin rarraba wutar lantarki, Scotech ya himmatu wajen samar da ingantacciyar, aminci, da kushin da ke da alhakin muhalli{1}masu tafsiri don tallafawa hanyoyin wutar lantarki na zamani da aikace-aikacen masana'antu.

Hot Tags: 2000 kva kushin saka transformer, manufacturer, maroki, farashin, farashi
You Might Also Like
2500 kVA Uku Pad -wanda aka ɗora Transformer-13.8/0....
225 kVA Kushin Dutsen Mai Canjawa-34.5 / 0.208 kV|Am...
2500 kVA Kushin Haɓaka Masu Canjin Rarraba-25/0.6 kV...
1000 kVA Kushin Haɗa Mai Canjawa-13.2 / 0.48 kV|Amur...
500 kVA Kushin Dutsen Mai Canjawa-24 * 13.8 * 12 / 0...
2000 kVA Kushin Haɓaka Mai Rarraba Rarraba-4.16/0.08...
Aika Aikace-aikacen