500 kVA Kushin Dutsen Mai Canjawa-24 * 13.8 * 12 / 0.416 * 0.24 kV|Jamaica 2025

500 kVA Kushin Dutsen Mai Canjawa-24 * 13.8 * 12 / 0.416 * 0.24 kV|Jamaica 2025

Ƙasa: Jamaica 2025
Yawan aiki: 500kVA
Wutar lantarki: 24GrdY/13.8*13.8D*12GrdY/6.9-0.416Y/0.24*0.24/0.12kV
Feature: tare da sau biyu irin ƙarfin lantarki
Aika Aikace-aikacen

 

 

500 kva pad mount transformer

Daga Rarraba zuwa Garuruwan Smart - Pad{0}Mounted Transformers suna Ci gaba da Gudun Makamashi.

 

 

01 Gabaɗaya

1.1 Bayanin Aikin

An kai 500 kVA pad mounted transformer zuwa Jamaica a 2025. Ƙarfin wutar lantarkin shine 500 kVA tare da sanyaya ONAN. Babban ƙarfin lantarki shine 24 / 13.8 * 13.8D * 12 / 6.9 kV tare da kewayon tapping ± 2 * 2.5% (NLTC), ƙarfin lantarki na biyu shine 0.416 / 0.24 * 0.24D / 0.12 kV, sun kafa ƙungiyoyin vector na YNyn0 da YNd11.

Taswirar mu{0} da aka ɗora taswira ƙaƙƙarfan ce, cikakken tsarin rarraba wutar lantarki wanda aka tsara don aminci, aminci, da inganci a cikin saitunan birni da masana'antu. An ƙirƙira shi don haɗawa mara kyau zuwa grid na zamani, yana da fasalin kashewa{2}}mai canjin kewayawa da maɓallan wutar lantarki biyu don sassauƙan aiki, yana ba da damar daidaita wutar lantarki mai sauƙi ba tare da katse sabis ba.

Don ingantacciyar kariya, rukunin ya haɗa da masu kama gwiwar hannu da lodi{0}masu haɗa haɗin gwiwar gwiwar hannu, tabbatar da tsagaitawar amintaccen cire haɗin gwiwa da kuma dakatar da tiyata. Ciyarwar{2} ta hanyar sakawa yana ba da damar sarrafa ingantaccen kebul, yayin da ana ba da sa ido na gaba ta hanyar ma'aunin zafin jiki na mai, mai nuna matakin ruwa, da ma'aunin matsa lamba na ainihin- bincike na lokaci.

An ba da fifikon tsaro tare da Bay{0}O-Net fuse da na yanzu{2}}iyakance fis don hana yin nauyi, tare da jujjuyawar ɗaukar nauyi don keɓantacce lokacin kiyayewa. An gina shi don tsayayya da matsananciyar mahalli, wannan tafsiri yana ba da ingantaccen aiki tare da ƙarancin kulawa - madaidaici don kayan aiki, rukunin kasuwanci, da aikace-aikacen makamashi mai sabuntawa.

 

 

 

1.2 Ƙayyadaddun Fasaha

500 kVA na'ura mai ba da hanya tsakanin hanyoyin sadarwa da takaddun bayanai

Isarwa zuwa
Amurka
Shekara
2025
Nau'in
Taranfoma na Substation
Daidaitawa
IEEE Std C57.12.34-2022
Ƙarfin Ƙarfi
500 kVA
Yawanci
50HZ
Mataki
3
Nau'in Sanyi
ONAN
Babban Voltage
24/13.8*13.8D*12/6.9 kV
Na biyu Voltage
0.416/0.24*0.24D/0.12 kV
Abubuwan Iska
Copper
Matsala ta kusurwa
YNyn0, YNd11
Impedance
5%
Matsa Canji
Farashin NLTC
Taɓa Range
±2*2.5%
Babu Asara Load
Kasa da ko daidai da 0.767kW
Akan Rasa Load
Kasa da ko daidai da 7.2kW

 

 

1.3 Zane

500 kVA madaidaicin zane zane da girman.

500 kva pad mount transformer drawing 500 kva pad mount transformer nameplate

 

 

02 Masana'antu

2.1 Kori

Taswirar tana da ƙaƙƙarfan ƙwaƙƙwaran ƙarfe na ƙarfe{0} wanda aka gina daga ƙirar ƙira mai ƙima{1}} silikon karfe laminations. Kowane lamination laser daidai yake - an yanke shi kuma an jera shi tare da madaidaicin mataki -gadon cinya don rage ɗigon ruwan maganadisu da rage hasara-. An lulluɓe ainihin da murfin oxide mai rufewa don hana igiyar ruwa, yayin da ƙaƙƙarfan ƙira ɗin sa yana haɓaka kwanciyar hankali na inji kuma yana rage ƙarar amo{7}mahimmanci ga shigarwar birane. Da kyar da aka ƙera don ingantacciyar ƙarfin maganadisu, wannan ainihin yana tabbatar da canjin makamashi mai santsi a cikin saitunan wutar lantarki guda biyu, yana kiyaye inganci ko da a ƙarƙashin kaya masu canzawa.

high-efficiency stacked iron core

 

2.2 Guda

copper winding

Gilashin foil na LV yana amfani da tsiri na jan karfe, yana tabbatar da rarrabuwar kawuna na yanzu, gajeriyar juriyar kewayawa, da ingantacciyar zubar da zafi. A halin yanzu, iska na HV Layer yana ɗaukar keɓaɓɓun madugu na jan ƙarfe da aka raunata a cikin fayafai masu tattara bayanai, tare da takardar kraft mai tsaka-tsaki don ƙimar ƙarfin dielectric. Ana amfani da dabarun jujjuyawar don rage yawan asara, yayin da axial da radial na sanyaya ducts ke inganta sarrafa zafi.

 

2.3 Tanko

The transformer tank is a robust, corrosion-resistant steel enclosure featuring 3D corrugated walls for oil expansion and integrated cooling fins for passive heat dissipation. Tare da cikakken welded, aikin da aka gwada ta hanyar rediyo, ya haɗa da tashar jiragen ruwa da aka haƙa a baya tare da shuwagabannin ƙasa, da gina{4}}a cikin wuraren ɗagawa/matsakaicin cokali mai yatsu. Ciki yana haɗa da faranti don mafi kyawun kwararar mai, yayin da UV{6}} fenti mai jurewa yana tabbatar da dorewar dogon lokaci{7} a muhallin waje.

UV-resistant transformer tank

 

2.4 Taron Karshe

transformer core-coil assembly

Haɗin ƙarshe na wannan kushin{0}mai na'ura mai ɗaukar nauyi yana haɗe babban taro na coil, tanki, da na'urorin haɗi zuwa tsarin haɗin kai. Busasshen cibiya -ana saukar da naúrar iska a hankali a cikin tankin ƙarfe mai juriya, sannan sai shigar da bushes, fins mai sanyaya, da abubuwan sarrafawa. Matakai masu mahimmanci sun haɗa da:

• Cike mai a ƙarƙashin injin don cika cikawar ciki

• Daidaita injina na masu sauya hutun lodi & masu haɗin kebul

Gwajin aiki na duk na'urorin sa ido (ma'auni, ƙararrawa)

 

 

03 Gwaji

A'a.

Gwajin Abun

Naúrar

Dabi'un Karɓa

Ƙimar Ma'auni

Kammalawa

1

Ma'aunin Juriya

%

Matsakaicin juriya rashin daidaituwa

0.76

Wuce

2

Gwajin Rabo

%

Bambancin rabon wutar lantarki akan babban tapping: ƙasa da ko daidai da ± 0.5%

Alamar haɗi: YNyn0/YNd11

0.14% ~ 0.15%

Wuce

3

Mataki{0}}gwajin dangantaka

/

YNyn0/YNd11

YNyn0/YNd11

Wuce

4

A'a -asara da tashin hankali na halin yanzu

%

kW

I0 :: bayar da ma'auni darajar

P0: ba da ƙima mai ƙima

juriyar rashin hasara shine +0%

0.59%

0.7535

Wuce

5

Load hasarar impedance ƙarfin lantarki da inganci

%

kW

kW

t:85 ku

haƙuri ga impedance shine ± 7.5%

juriyar jimlar asarar kaya shine +0%

/

Wuce

Z%: ƙimar da aka auna

5.02%

Pk: ƙimar ƙima

6.649 kW

Pt: ƙima mai ƙima

7.4025 kW

Ingancin ba kasa da 99.05%

99.10%

6

Gwajin Karfin Wutar Lantarki

kV

HV: 40kV 60s

LV: 10kV 60s

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

7

Jarrabawar Juriya da Wutar Lantarki

kV

Wutar lantarki mai aiki (KV):2Ur

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

Duration(s):40

Mitar (HZ): 150

8

Gwajin Leaka

kPa

matsa lamba: 20kPA

Tsawon lokaci: 12h

Babu yabo kuma babu

Lalacewa

Wuce

9

Ma'aunin Resistance Insulation

GΩ

HV{0}LV zuwa Ground:

11.0

/

LV -HV zuwa Ground:

9.51

HV&LV zuwa Ground:

20.1

10

Gwajin Dielectric Oil

kV

Yafi ko daidai da 45

58.6

Wuce

 

500 kva pad mount transformer test
green box transformer routine test

 

 

04 Shiryawa da jigilar kaya

4.1 Shiryawa

Wannan pad ɗin da aka ɗora tasfoma yana kunshe ne ta hanyar fara ɗora ɗigon jakar foil ɗin kwano a kan tire ɗin taransfoma sannan a rufe tasfoman da jakar foil ɗin kwano. Lokacin da aka rufe jakar jakar kwano, ya kamata a bar budewa, ta inda za a yi amfani da injin tsabtace iska don fitar da iskar gas, sannan kuma a rufe budewar da injin rufewa. A halin yanzu, ana sanya desiccant a cikin kunshin don hana tsatsa. Bayan shafe-shafe, ana sanya masu kare kusurwa da aka yi da kumfa, filastik, ko kwali (masu kariya na kusurwa na musamman da aka matse daga kwali) a kusa da taswirar, sannan a nannade da fim ɗin kariya. A ƙarshe, an cushe shi a cikin akwati na katako, wanda ya kamata a fesa alamar cokali mai yatsa da tsakiyar alamar nauyi.

500 kva pad mount transformer packing

 

4.2 Shipping

export documents of transformer

Wannan pad{0} za a aika da tiransifoma a ƙarƙashin sharuɗɗan FOB (Free On Board), tare da mai kawo kaya da ke da alhakin kai kayan zuwa tashar jiragen ruwa na Yiwu da kuma kammala lodin kan jirgin. Mallaka da haɗarin haɗari ga mai siye da zarar kayan sun wuce titin jirgin ruwa a tashar Yiwu. Mai siye zai shirya jigilar kaya na teku na gaba da isar da saƙo na ƙarshe zuwa Jamaica ta mai siye. Lokacin wucewa, kayan aikin dole ne a ɗaure su cikin aminci don hana girgiza da danshi, tare da cikakkun jerin abubuwan tattarawa da takaddun fitarwa da aka tanadar don izinin kwastam.

 

 

05 Yanar Gizo da Takaitawa

Tare da ingantacciyar inganci, ƙaƙƙarfan ƙira, da dorewa mai ƙarfi, wannan Pad{0}Mounted Transformer shine kyakkyawan zaɓi don tsarin wutar lantarki na masana'antu, kasuwanci, da jama'a. An kera shi cikin ƙaƙƙarfan yarda da ƙa'idodin ƙasa da ƙasa, kowace naúrar tana ba da tabbacin ingantaccen aiki da aminci. Ko kuna buƙatar ingantaccen rarraba wutar lantarki ko keɓance hanyoyin magance ƙalubale, ƙungiyarmu a shirye take don ba da tallafin ƙwararru. Tuntuɓe mu a yau don cikakkun bayanai dalla-dalla ko keɓaɓɓen sabis- mun himmatu wajen isar da tsayayyen hanyoyin samar da wutar lantarki don buƙatun ku!

public utility power systems

 

Hot Tags: 500 kva kushin Dutsen Transformer, Manufacturer, maroki, farashin, farashi

Aika Aikace-aikacen