2000 kVA Kushin Dutsen Mai Canjawa-25 / 0.6 kV|Kanada 2025
Yawan aiki: 2000 kVA
Ƙarfin wutar lantarki: 25-0.6Y/0.347 kV
Feature: tare da zobe na kusurwa

Fasaha Mai Hankali, Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwaƙwalwa na Ƙaddamarwa na Ƙarfafawa na Ƙarfafawa ) Ya Sake Fahimtar Tsaro da Dogaran Ƙarfi!
01 Gabaɗaya
1.1 Bayanin Aikin
2000 kVA three phase pad mounted transformer an isar da ita zuwa Kanada a shekarar 2025. Ƙarfin wutar lantarkin shine 2000 kVA tare da sanyaya ONAN. Babban ƙarfin lantarki shine 25 kV tare da ± 2 * 2.5% tapping range (NLTC), ƙarfin lantarki na biyu shine 0.6Y/0.347 kV, sun kafa ƙungiyar vector na Dyn1.
Na'urar Wutar Lantarki ta Fuskar Fuskokin Uku Uku ce mai ƙarfi, ta waje{0} na'urar lantarki mai dacewa da ita wacce ake amfani da ita a cikin tsarin rarraba wutar lantarki na birni da ƙauye. Babban aikinsa shi ne canza babban{2}}ƙarfin wutar lantarki zuwa ƙananan ƙarfin lantarki{3}} don biyan bukatun masu amfani da zama, kasuwanci, da masana'antu, samar da ingantaccen tallafin wutar lantarki.
Wannan na'urar galibi tana sanye take da na'urori masu aminci da na'urori daban-daban don tabbatar da ingantaccen aiki da aminci. Daga cikin waɗannan, fis ɗin bayonet da na yanzu{1} iyakance fis ɗin suna kare da'irar yadda ya kamata, suna cire haɗin wutar lantarki ta atomatik yayin yin nauyi ko gajeriyar yanayi{2} don hana lalacewar kayan aiki. Maɓallin fashewar kaya yana bawa masu aiki damar canza kewayawa cikin aminci cikin aminci, sauƙaƙe kulawa da dubawa. Ana amfani da mai canza fam ɗin mai kuzari don daidaita ƙarfin fitarwa na taransfoma cikin aminci don ɗaukar yanayi daban-daban, yana tabbatar da sassauci da kwanciyar hankali a cikin wutar lantarki.
Bugu da ƙari, babban ma'aunin zafin jiki na mai da ma'aunin mai na iya sa ido kan yanayin zafi da matakin ruwa na mai na ciki a ainihin lokacin, tare da faɗakar da masu aiki da sauri don sake mai da kuma kula da lafiyar kayan aikin. Ma'aunin matsa lamba na injin yana taimakawa wajen lura da yanayin injin na'ura mai canzawa, yana hana danshi da ƙazanta shiga, ta yadda zai tsawaita tsawon rayuwar kayan aiki. Na'urar taimakon matsa lamba na iya sakin matsa lamba ta atomatik lokacin da matsa lamba na ciki ya yi yawa, yana tabbatar da amincin kayan aiki.
Waɗannan cikakkun fasalulluka sun mai da Fasin Pad Dutsen Transformer na Mataki na Uku ya zama abin da ba dole ba ne a cikin tsarin rarraba wutar lantarki na zamani, yana tabbatar da amincinsa da kwanciyar hankali a ƙarƙashin yanayin aiki daban-daban.
1.2 Ƙayyadaddun Fasaha
2000 kVA kushin da aka ɗora nau'in ƙayyadaddun bayanai da takaddun bayanai
|
Isarwa zuwa
Kanada
|
|
Shekara
2025
|
|
Nau'in
Tashin wutar lantarki
|
|
Daidaitawa
CSA C227.4:21
|
|
Ƙarfin Ƙarfi
2000 kVA
|
|
Yawanci
60HZ
|
|
Mataki
3
|
|
Ciyarwa
Madauki
|
|
Gaba
Matattu
|
|
Nau'in Sanyi
ONAN
|
|
Babban Voltage
25 kv
|
|
Na biyu Voltage
0.6Y/0.347 kV
|
|
Abubuwan Iska
Aluminum
|
|
Matsala ta kusurwa
Dyn1
|
|
Impedance
5.75%
|
|
Matsa Canji
Farashin NLTC
|
|
Taɓa Range
±2*2.5%
|
|
Babu Asara Load
2.22 kW
|
|
Akan Rasa Load
18.3 kW
|
|
Na'urorin haɗi
Daidaitaccen Kanfigareshan
|
1.3 Zane
2000 kVA kushin da aka ɗora zane da girma.
![]() |
![]() |
02 Masana'antu
2.1 Kori
Rukunin rukunin {{0}sashi na uku{1} uku shine tsarin ciki na na'ura mai canzawa, wanda ke da alhakin gudanar da motsin maganadisu da kyau. Ana yin wannan ginshiƙi ta laminating silicon karfe zanen gado don rage wutar lantarki da kuma inganta yadda ya dace na irin ƙarfin lantarki canji. Tsarin ginshiƙi guda uku- yana nufin cewa ainihin yana ƙunshe da da'irorin maganadisu masu zaman kansu guda uku, kowanne ya yi daidai da lokacin watsawa na yanzu. Wannan tsari yana haɓaka yawan juzu'in maganadisu, yana ba da damar jigilar maganadisu don yaɗuwa da kyau a cikin ainihin, don haka haɓaka aiki da kwanciyar hankali na gabaɗayan tsarin. Zane-zanen ginshiƙi guda uku{{7} ba wai yana tallafawa watsa na'urorin zamani guda uku kawai ba amma har ma yana rage ɗigowar yanayin filin maganadisu, yana tabbatar da ingantaccen aikin na'urar wuta. Ƙirar gabaɗaya tana nufin ba da damar tsarin wutar lantarki don samar da ingantaccen ƙarfin watsa wutar lantarki.

2.2 Guda

Mataki na uku{0}Pad Mounted Transformer yana fasalta ƙirar iska tare da zoben kusurwa waɗanda ke taka muhimmiyar rawa. Zobe na angular yana aiki don gyara manyan iska da maɗaukakiyar iskar gas zuwa ginshiƙi mai canzawa, yana tabbatar da cewa zasu iya jure wa matsalolin lantarki da na inji da aka haifar yayin aiki, don haka kiyaye kwanciyar hankali da aminci. Hakanan yana ba da keɓancewar lantarki tsakanin iska, hana gajeriyar kewayawa da haɓaka amincin lantarki.
Bugu da ƙari, zoben angular yana haɓaka aikin lantarki da aminci ta hanyar ƙara rufin rufi da ƙarfin injina na iska, rage girgizawa da ƙaura, da haɓaka dorewa da kwanciyar hankali. Yana taimakawa wajen zubar da zafi, yana ƙyale mai canza wuta yayi aiki a cikin kewayon zafin jiki na yau da kullun kuma yana ƙara tsawon rayuwarsa. Haka kuma, yana rage tsangwama na lantarki tsakanin iska, inganta ingantaccen makamashi da amfani.
2.3 Tanko
Bisa ga ƙa'idodin Ƙungiyoyin Ƙididdiga na Kanada (CSA), tankin mai na wani nau'i na nau'i uku{0}Pad Mounted Transformer yana da abubuwa masu mahimmanci da yawa: an tsare ƙofar da kusoshi guda uku don haɓaka aminci da aikin rufewa; babu rabuwa tsakanin babban -ƙarar wutar lantarki da ƙananan - ɗakunan wutar lantarki, sauƙaƙe kwararar mai da kuma tabbatar da ingantaccen zafi; kuma an shigar da sandar jan ƙarfe na ƙasa a cikin ƙaramin ɗakin wutan lantarki don aminta da kai tsaye zuwa ƙasa idan wani laifi ya faru. Wadannan abubuwan ƙirar da aka haɗa suna tabbatar da aminci, amintacce, da ingancin tankin mai, suna bin ka'idodin CSA don ƙarfi yayin da suke la'akari da dacewa da kulawa.

2.4 Taron Karshe

1. Shigar da Coil:Ana kiyaye coles ɗin iska akan ainihin.
2. Haɓaka Sashe Mai Aiki:Bangaren da aka haɗa (windings da core) ana ɗaga shi a hankali cikin tankin mai.
3. Sanya Na'urorin haɗi:Na'urorin haɗi kamar bawul ɗin taimako na matsa lamba, fuse baynet, da ma'aunin matakin mai ana shigar dasu don amintaccen aiki da sa ido.
4. Haɗin Wutar Lantarki:Ana yin haɗin wutar lantarki mai dacewa tsakanin iska na farko da na sakandare.
5. Cika da Mai:An cika mai mai canzawa a cikin tanki don nutsar da sashin aiki cikakke, yana tabbatar da sanyaya da rufi.
2000 kVA Kushin Dutsen Canji Na'urorin haɗi
| MUSULUNCI DA FUSKA | |
![]() |
Bayoneti Fuse 3 Ƙayyadaddun Fuse na Yanzu (CLF) 3 |
![]() |
Load Break Switch 1 Mai Canjin Taɓa Mai kuzari 1.- |
| KAYANA & KAYAN HAKA | |
![]() |
Mafi kyawun Thermometer mai 1 Matsayin Matsayin Mai 1 |
![]() |
Ma'aunin Matsala 1 Valve Drain mai tare da Samfurin Valve 1 |
04 Gwaji


05 Kiɗa da jigilar kaya


Za a yi jigilar na'ura ta Pad Mounted Transformer guda uku a ƙarƙashin sharuɗɗan CIF (Cost, Insurance, and Freight) zuwa tashar jiragen ruwa na Montreal, Kanada. Za a yi jigilar kayan ta hanyar ruwa don tabbatar da aminci da inganci. Mai jigilar kaya zai samar da inshora ga kayan don kariya daga duk wata hasarar da za a iya yi ko lahani yayin tafiya. Bayan isowa a Montreal, kayan za su fuskanci hanyoyin kawar da kwastam, tabbatar da duk takaddun da suka dace sun cika don sarrafa su cikin sauƙi. Bayan an cire na’urar ta kwastam, za a kwashe na’urar taransfoma lafiya zuwa inda ta ke.
06 Yanar Gizo da Takaitawa
Mataki na uku{0}Pad Mounted Transformer yana taka muhimmiyar rawa a cikin tsarin rarraba wutar lantarki, yana ba da ingantacciyar jujjuyawar wutar lantarki da mafita na rarrabawa. Ƙaƙƙarfan ƙira ɗin sa da fitaccen aikin sa ya sa ya zama kyakkyawan zaɓi don aikace-aikace daban-daban. Yayin da buƙatun wutar lantarki ke ci gaba da ƙaruwa da haɓaka haɓakar makamashin da ake iya sabuntawa, na'ura mai sarrafa wutar lantarki guda uku{3} za su kasance masu mahimmanci a nan gaba na kayan aikin lantarki, tare da haɓaka ci gaba mai dorewa a masana'antar wutar lantarki.

Hot Tags: 2000 kva kushin Dutsen Transformer, Manufacturer, maroki, farashin, farashi
You Might Also Like
750 kVA Liquid Cika Masu Canji-12.47 / 0.6 kV|Amurka...
750 kVA Kushin Haɓaka Mai Canja wurin Mai amfani-34....
3000 kVA Mai Canjawa-25 / 0.6 kV|Kanada 2025
500 kVA Kushin Dutsen Mai Canjawa-24 * 13.8 * 12 / 0...
3000 kVA Kushin Haɓaka Mai Canjawa-25 / 0.6 kV|Kanad...
2000 kVA Kushin Haɓaka Mai Rarraba Rarraba-4.16/0.08...
Aika Aikace-aikacen