1500 KVA Cast Resin Transformer-6.6/0.55 KV|Afirka ta Kudu 2025
Yawan aiki: 1500kVA
Wutar lantarki: 6.6/0.55kV
Siffar: Tare da Mai Kula da Zazzabi & Magoya bayan sanyaya
Jiangshan Scotech Electric Co., Ltd yana ɗaya daga cikin amintattun masana'antun da masu samar da na'ura mai ba da wutar lantarki 1500 kva -6.6/0.55 kv|Afirka ta Kudu 2025 a China. Da fatan za a ji kyauta don siyan kayayyaki masu inganci don siyarwa anan kuma ku sami zane-zane daga masana'anta. Tuntube mu don ƙarin bayani.

01 Gabaɗaya
1.1 Muhallin Aikace-aikacen
Wannan aikin yana goyan bayan tsarin rarraba wutar lantarki na cikin gida{0} a wani wurin masana'antu a Afirka ta Kudu. Samar da kayan aiki yana zuwa a 6.6 kV kuma an sauka zuwa 0.55kV don ciyar da layukan samarwa da nau'ikan kayan taimako iri-iri a fadin shuka.
Ana shigar da transfoma a cikin gida. Sarari yana da iyaka, amma yanayin aiki ba komai bane illa mai sauƙi. Yanayin yanayi na iya yin girma, kuma bayanin martaba yana canzawa koyaushe. Ana sa ran ci gaba da aiki -rana a cikin, rana{4}} tare da juriya kaɗan don raguwar lokacin da ba zato ba tsammani. Wadannan abubuwan sun rinjayi yawancin yanke shawara na ƙira tun daga farko.
1.2 Bukatun Abokin ciniki
Daga bangaren abokin ciniki, tsammanin ya fito fili. Suna buƙatar babban tasfo mai bushewa mai ƙarfi{1} wanda ya dace da shigarwa na cikin gida{2}wanda ke guje wa tashin gobara da abubuwan da ke tattare da muhalli wanda akafi haɗa da man fetur{3}}cikakken kayan aiki.
Ayyukan thermal wani mahimmin batu ne. Dole ne taswirar ta kasance a karye a ƙarƙashin madaidaicin lodi, gami da lokacin buƙatu mafi girma, ba tare da dogaro da sa hannun hannu akai-akai ba. Don haka sarrafa sanyaya ta atomatik yana da mahimmanci, ba a matsayin ƙarin fasali ba, amma azaman buƙatu mai amfani don ingantaccen aiki na yau da kullun.
1.3 Ƙimar Fasaha
1500kVA simintin ƙarfe busassun nau'in taswira da takaddun bayanai
|
Isarwa zuwa
Afirka ta Kudu
|
|
Shekara
2025
|
|
Nau'in
Cast coil dry type transformer
|
|
Daidaitawa
Saukewa: IEC60076
|
|
Ƙarfin Ƙarfi
1500 KVA
|
|
Yawanci
50HZ
|
|
Mataki
Uku
|
|
Yawan iska
2
|
|
Nau'in Sanyi
AN/AF
|
|
Babban Voltage
6.6 kv
|
|
Na biyu Voltage
0.55 kV
|
|
Ƙungiyar Vector
Domin 11
|
|
Abubuwan Iska
Aluminum
|
|
Babban abu
Silicon karfe takardar hatsi daidaitacce
|
|
Matsayin rufi
F
|
|
Impedance
6%
|
|
Matsa Canji
Farashin NLTC
|
|
Taɓa Range
±2*2.5%
|
|
Babu Asara Load
2.45 kW
|
|
Akan Rasa Load
11.73 kW
|
|
Na'urorin haɗi
Tare da Mai Kula da Zazzabi & Magoya bayan sanyaya
|
1.3 Zane
1500kVA simintin busassun nau'in taswira zane da farantin suna

02 Halayen Zane da Bayanin Ayyuka
2.1 Ƙididdiga na Wutar Lantarki da Ƙira-Tsarin iska

A tsakiyar aikin shine 1500 kVA, nau'in simintin simintin busasshen lokaci guda uku{1} wanda aka ƙera don aiki na 50 Hz. An ƙididdige babban ƙarfin lantarki a 6.6 kV, tare da 0.55 kV na sakandare, an saita shi a cikin ƙungiyar Dyn11 vector - wanda ya dace da ƙananan masana'antu{8} tsarin rarraba wutar lantarki.
An magance tsarin daidaitawa ta matakin 6% na rashin ƙarfi, yayin da a kashe{1}}mai canza canjin kewayawa (NLTC) tare da kewayon bugun ± 2 × 2.5% yana ba da damar daidaita wutar lantarki yayin shigarwa ko yanayin grid.
Don da'irar maganadisu, ana amfani da hatsi{0}}ƙarfan silicon mai daidaitacce don kiyaye babu{1}}asara a ƙarƙashin sarrafawa. An zaɓi iskar aluminium don babban aikace-aikacen masana'antu na yanzu, daidaita aikin lantarki, yanayin zafi, da tsarin tattalin arzikin tsarin gabaɗaya. Babu wani abu mai ban mamaki{5}}kawai tabbataccen zaɓin ƙira da aka yi amfani da su a inda suke da ma'ana.
2.2 Tsarin Insulation da Wuta{1}}Safet Design
An ƙididdige tsarin rufin Class F, yana ba da isasshiyar gefen zafi don ci gaba da aiki a ƙarƙashin yanayi mai buƙata. Dukkan iska an lullube su cikin simintin simintin gyaran kafa, wanda ke ƙara ƙarfin injina kuma yana taimakawa kiyaye kwanciyar hankali na tsawon lokaci.
Domin wannan ƙirar busassun ce, babu mai insulating kwata-kwata. Babu haɗarin yatsa. Babu wata gobara da ta yada damuwa mai alaƙa da rufewar ruwa. Wannan ya sa na'urar ta sauya fasalin ta dace musamman ga ruɓaɓɓen ɗakunan lantarki na cikin gida, inda aminci, yarda, da sauƙin aiki komai komai.
2.3 Ayyukan Asara da Ƙarfin Ƙarfi
An magance aikin hasara a farkon lokacin ƙira. Na'urar taswira ta cimma babu{1}}asara na 2.45 kW da kuma asarar nauyi na 11.73 kW, bisa ingantattun matakan magnetic flux da ƙirar madugu.
A cikin dogon lokaci, wannan yana fassarawa zuwa iyawar da ake iya faɗi da kuma rage asarar aiki{0}mahimmanci ga kayan aiki waɗanda ke ci gaba da aiki kuma suna samar da wani yanki na dindindin na kayan aikin wutar lantarki. Ba game da neman lambobi akan takarda ba ne, amma game da tsayayye, ingantaccen aiki tsawon shekaru na sabis.

03 Tsarin sanyaya da Kula da thermal
3.1 Magoya bayan Na'urar sanyaya iska Tilas


An shigar da magoya bayan sanyaya guda shida don samar da sanyaya iska mai tilastawa don taswirar. Kowane fan yana aiki a 1400 r/min tare da ƙimar ƙimar 45 W kuma ana ba da shi ta AC 220 V. Magoya bayan suna isar da kwararar iska na kusan 770 m³/h a kowace naúrar yayin da suke riƙe ƙaramin ƙarar aiki na Kasa da ko daidai da 52 dB, yana tabbatar da bargawar zafi, aiki mai shiru, da ingantaccen aiki} ci gaba da sabis na dogon lokaci{.
3.2 Mai Kula da Zazzabi


Amintaccen aiki na busassun na'urar taswira{0}} ya dogara da ingantaccen sarrafa zafin iska. Wannan mai kula da zafin jiki yana amfani da na'urori masu auna juriya na platinum da na'ura mai sarrafawa{2} tushen fasaha don saka idanu da zafin jiki tare da daidaito mai tsayi da ƙudurin digiri 0.1. Yana sarrafa magoya bayan sanyaya ta atomatik, tare da ƙararrawar zafi sama da{5} da abubuwan tafiya don kariya. Ƙaddamar da AC 220 V, wanda ya dace da tsarin 50/60 Hz; an ƙera shi don isar da ƙaƙƙarfan ƙaƙƙarfan ƙaƙƙarfan kariyar zafin rana yayin ci gaba da aiki mai canzawa.
04 Shiryawa da sufuri


05 Yanar Gizo da Takaitawa
An yi nasarar tura wannan busasshen resin na simintin gyare-gyare a cikin masana'antu a Afirka ta Kudu, yana samar da amintaccen, aminci, da makamashi{1} ingantaccen rarraba wutar lantarki. Tsarin sa na al'ada yana tabbatar da tsayayyen aiki a ƙarƙashin ci gaba da kaya masu canzawa, yana mai da shi kyakkyawan mafita don matsakaicin masana'antu{3}} cibiyoyin rarraba wutar lantarki inda lokacin aiki, aminci, da inganci ke da mahimmanci.
Hot Tags: simintin guduro transformer, masana'anta, maroki, farashin, farashi
You Might Also Like
500 kVA Dry Resin Transformer-13.8 / 0.46 kV|Afirka ...
400 kVA Busassun Nau'in Canjin Lantarki-0.55 / 0.46 ...
630 kVA 3 Tsarin Busassun Nau'in Canji-6.6 / 0.55 kV...
2500 kVA Dry Transformer-10 / 0.4 kV|Jojiya 2025
630 kVA Cast Coil Transformer-6.6 / 0.55 kV|Afirka t...
1500 KVA Matsakaici Nau'in Wutar Lantarki na Busassu...
Aika Aikace-aikacen