630 kVA 3 Tsarin Busassun Nau'in Canji-6.6 / 0.55 kV|Afirka ta Kudu 2025

630 kVA 3 Tsarin Busassun Nau'in Canji-6.6 / 0.55 kV|Afirka ta Kudu 2025

Ƙasa: Afirka ta Kudu 2024
Yawan aiki: 630kVA
Wutar lantarki: 6.6/0.55kV
Fasalin: Insulation matakin H
Aika Aikace-aikacen

 

 

630 kVA 3 phase dry type transformer

Ƙirƙirar Ƙira don Ƙarfafa Gaba: Zaɓi Busassun Simintin Resin - Nau'in Masu Canzawa!

 

01 Gabaɗaya

1.1 Fagen Aikin

An isar da tasfoman busasshen busasshen mai nauyin kVA 630 zuwa Afirka ta Kudu a cikin 2024; Matsakaicin ƙarfin wutar lantarki shine 630 kVA. Babban ƙarfin wutar lantarki na wannan nau'in taswirar busassun shine 6.6 kV, ƙananan ƙarfin lantarki shine 0.55 kV. Wannan babban na'urar busasshen wutan lantarki yana sanye da wani mai canza canjin kaya, kewayon tapping shine ± 2 * 2.5% a gefen farko. Sanyaya shine KNAF, sun kafa ƙungiyar vector na Dyn11.

Resin simintin busassun - nau'in tasfoma suna jagorantar hanya a ƙirar taransfoma, suna samar da ingantaccen aikin lantarki da injina. Ƙarfinsu mai ɗorewa, wanda aka samu ta hanyar shigar da iska a cikin resin epoxy, yana ba da ƙarfin injin da bai dace da shi ba, mai mahimmanci don cimma burin muhalli da dorewa.

An ƙera shi don ƙaƙƙarfan mahalli, waɗannan eco{0}waɗanda suka haɗa da tasfofi suna da ƙaramin ƙira{1}mai kula, mai{2}}ƙira kyauta wanda ke rage farashin aiki. Harshen harshen su{4}}mai dagewa, da kansa{5}}in kashe rufin yana tabbatar da ingantaccen tsaro, yayin da ƙaramin ƙirar ke adana sararin shigarwa mai mahimmanci.

Ta hanyar amfani da manyan kayan rufe fuska{0} da ingantattun sifofi masu ƙarfi, resin ɗinmu ya bushe{1}} nau'in tasfoma yana ba da ingantaccen aminci da dorewa. Zaɓi na'urorin lantarki na mu don ingantacciyar hanyar samar da wutar lantarki, aminci, da dorewa waɗanda ke ba ku gasa gasa a tsarin wutar lantarki na zamani.

 

 

1.2 Ƙayyadaddun Fasaha

630 kVA guduro simintin busassun nau'in taswira ƙayyadaddun bayanai da takaddar bayanai

Isarwa zuwa
Jojiya
Shekara
2024
Nau'in
Guduro simintin busassun nau'in taswira
Babban abu
Silicon karfe takardar hatsi daidaitacce
Daidaitawa
Saukewa: IEC60076
Ƙarfin Ƙarfi
630 kVA
Yawanci
50HZ
Ƙungiyar Vector
Domin 11
Mataki
3
Nau'in Sanyi
KNAN/KNAF
Babban Voltage
6.6 kv
Na biyu Voltage
0.55 kV
Abubuwan Iska
Aluminum
Impedance
4.5%
Matsa Canji
Farashin NLTC
Taɓa Range
± 2 * 2.5% @ ƙarfin lantarki na farko
Babu Asara Load
1.3KW
Akan Rasa Load
5.96KW
Matsayin rufi
H

 

1.3 Zane

630 kVA guduro simintin busassun nau'in taswira zane da girman.

630 kVA resin cast dry type transformer drawing

 

02 Masana'antu

2.1 Kori

An gina tushen wutar lantarki daga inganci mai inganci, sanyi{1} birgima, hatsi{2}}karfe na silicon karfe tare da haɗin gwiwa{3}} don rage asarar kuzari. Yana da ƙafafu uku waɗanda aka jera su cikin jirgi ɗaya kuma suna haɗuwa da karkiya mai ƙarfi. Kowace kafa madauwari ce kuma an haɗa ta tare da karkiya, yayin da ake jujjuya ainihin a kusurwar digiri 45 don rage hayaniya da asara. An keɓe shi kuma an kiyaye shi daga lalata tare da murfin resin.

Firam ɗin ya ƙunshi tashoshi na ƙarfe na sama da na ƙasa suna riƙe da tsakiya da coils tare, tare da duk sassan ƙarfe da aka lulluɓe cikin lalata{0}} fentin epoxy mai jurewa don ingantaccen dorewa. Wannan zane yana tabbatar da ingantaccen aiki da aminci a cikin yanayi daban-daban.

630 kVA 3 phase dry type transformer iron core

 

2.2 Guda

630 kVA 3 phase dry type transformer winding

Siffofin gine-ginen iska mai girma{0}masu keɓancewar darajojin da aka shirya a sassa da yawa don rage matsakaicin matsakaicin ƙarfin lantarki. Ana jefar da iskar wutar lantarki mai girma{2} a cikin injin injina ta amfani da na'urar kwamfuta ta ci-gaba{3}}ananan tsari, tare da tabbatar da babu kurakurai a cikin coils.

Ana ƙara ƙarfafa iska da fiberglass don haɓaka ƙarfin injina. Bayan haɗuwa, duk manyan naɗaɗɗen wutan lantarki{1} ana yin gwajin fitarwa na ɗan lokaci don tabbatar da babu komai{2}}sharadi da tabbatar da ingantaccen aiki-. Wannan ƙayyadaddun ƙira yana ba da tabbacin dorewa da dogaro a cikin mahalli masu buƙata.

 

2.3 taro na ƙarshe

Shigar da Coil: Gudun da aka gwada - simintin simintin gyare-gyare ana sanya shi a hankali a cikin firam ɗin taswira, yana tabbatar da daidaitaccen jeri.

Babban Haɗin kai: An ɗora iska a cikin aminci zuwa ainihin don rage damuwa da tabbatar da kwanciyar hankali.

Haɗin Wutar Lantarki: An kafa haɗin wutar lantarki tare da madaidaici, haɗawa da iska zuwa tashar wutar lantarki da kuma tabbatar da haɗin kai mai kyau tare da tsarin lantarki.

Guduro Zubawa: Ana zuba resin epoxy mai inganci- akan taron, yana ba da kariya daga danshi da kuma inganta rufin.

Tsarin Magani: Ana warkewar wutar lantarki don taurare guduro, yana tabbatar da kayan aikin injiniya da lantarki da ake so.

630 kVA 3 phase dry type transformer assembly

 

 

03 Gwaji

A'a.

Gwajin Abun

Naúrar

Dabi'un Karɓa

Ƙimar Ma'auni

Kammalawa

1

Auna juriya na iska

/

Matsakaicin juriya rashin daidaituwa

Juriya na layi: Kasa da ko daidai da 2%

HV (layi)

LV (layi)

Wuce

 

0.41%

0.44%

2

Auna ma'aunin ƙarfin lantarki da duba ƙaurawar lokaci

/

Haƙuri na ƙimar ƙarfin lantarki akan babban tapping: ± 1/10

Alamar haɗi: Dyn11

-0.14% ~ 0.07%

Domin 11

Wuce

 

3

Auna Gajerun -Tsarin Tasirin kewayawa da Rasa Load

/

kW

kW

t: 120 digiri

Z%: ƙimar da aka auna

Pk: ƙimar ƙima

Pt: ƙima mai ƙima

4.5%

3.98

5.456

Wuce

 

4

Auna A'a{0}}Asara da A halin yanzu a 90% da 110% na ƙimar ƙarfin lantarki

/

kW

I0:: bayar da ma'auni darajar

P0: ba da ƙima mai ƙima

90% Ur

0.477

1.029

Wuce

 

100% Ur

0.53

1.144

110% Ur

0.583

1.258

5

Gwajin Karfin Wutar Lantarki

/

HV: 20kV 60s

LV: 3kV 60s

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

 

6

Jarrabawar Juriya da Wutar Lantarki

/

Wutar lantarki mai aiki (KV): 2 Ur

Ƙarfin wutar lantarki (KV): 1.1

Duration(s):40

Mitar (HZ): 150

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

 

7

Gwajin fitar da Bangaranci

pC

Matsakaicin matakin sakin juzu'i zai zama 10 pC

<10

Wuce

 

 

630 kVA 3 phase dry type transformer testing
630 kVA 3 phase dry type transformer factory test

 

 

04 Shiryawa da jigilar kaya

630 kVA 3 phase dry type transformer packing
630 kVA 3 phase dry type transformer shipping

 

05 Yanar Gizo da Takaitawa

Resin simintin busassun nau'in taswirar mu shine ingantaccen kuma amintaccen maganin wuta wanda aka tsara don biyan manyan buƙatun masana'antu da na kasuwanci. An yi shi da babban resin epoxy mai girma{2} da kuma yin amfani da tsarin simintin gyare-gyare, kowane taswira yana fuskantar gwaji mai tsauri don tabbatar da keɓaɓɓen rufin lantarki da juriya na danshi. Masu canjin mu suna da kyawawan halaye na sarrafa zafi, suna ba da damar aiki mai ƙarfi a cikin yanayin muhalli daban-daban yayin rage farashin kulawa da tsawaita rayuwar kayan aiki. Ƙirƙirar ƙira da ingantaccen aikin kariya na resin simintin busassun nau'in taswirar sa ya zama kyakkyawan zaɓi don tsarin wutar lantarki na zamani, yana tabbatar da aminci da ingantaccen watsa makamashi. Zaɓi na'urorin lantarki na mu don tabbatar da ci gaba da ingantaccen aiki na tsarin wutar lantarki.

630 kVA 3 phase resin cast  dry type transformer

 