630 kVA Cast Coil Transformer-6.6 / 0.55 kV|Afirka ta Kudu 2025
Yawan aiki: 630kVA
Wutar lantarki: 6.6/0.55kV
Siffar: tare da mai sarrafa zafin jiki da magoya baya

Cast Resin Dry Type Transformer - Harshen Harshen -Maganin Makamashi Silent!
01 Gabaɗaya
1.1 Bayanin Aikin
An kai 630 kVA busasshen taransfoma zuwa Afirka ta Kudu a cikin 2025. Ƙarfin wutar lantarki na wutar lantarki shine 630 kVA tare da sanyaya ONAN/ONAF. Babban ƙarfin lantarki shine 6.6 kV tare da ± 2 * 2.5% tapping range (NLTC), ƙarfin lantarki na biyu shine 0.55 kV, sun kafa ƙungiyar vector na Dyn11.
The Cast Resin Dry Type Transformer shine yanke{0}} maganin lantarki wanda aka ƙera don ingantaccen aminci, inganci, da aminci. Ba kamar man fetur na gargajiya{2}}cikakkun tasfoma ba, yana amfani da wuta{3}} resin epoxy resin don rufe iska, yana kawar da haɗarin ɗigowar mai, gobara, da kuma haɗarin muhalli.
Mafi dacewa don shigarwa na cikin gida, waɗannan tafkunan suna aiki a shiru, suna buƙatar kulawa kaɗan, kuma suna da matukar juriya ga danshi, ƙura, da kuma gurɓataccen yanayi.
Tare da ingantacciyar kwanciyar hankali da kaddarorin kashe kai{0}, suna tabbatar da ƙarfi mara yankewa a cikin mahimman aikace-aikace kamar gine-ginen kasuwanci, asibitoci, cibiyoyin bayanai, da masana'antu. Zaɓan Canjin Busassun Nau'in Cast Resin yana nufin saka hannun jari a cikin tsaftataccen tsari, eco -, kuma dogon{3}}tsarin rarraba wutar lantarki mai dorewa wanda ke ba da fifiko ga aminci da aiki.
1.2 Ƙayyadaddun Fasaha
630 kVA busassun nau'in canji da takaddun bayanai
|
Isarwa zuwa
Afirka ta Kudu
|
|
Shekara
2025
|
|
Nau'in
Busassun nau'in transfoma
|
|
Babban abu
Silicon karfe takardar hatsi daidaitacce
|
|
Daidaitawa
Saukewa: IEC60076
|
|
Ƙarfin Ƙarfi
630 kVA
|
|
Yawanci
50HZ
|
|
Ƙungiyar Vector
Domin 11
|
|
Mataki
3
|
|
Nau'in Sanyi
ONAN/ONAF
|
|
Babban Voltage
6.6kv
|
|
Na biyu Voltage
0.55kV
|
|
Abubuwan Iska
Aluminum
|
|
Impedance
6%
|
|
Matsa Canji
Farashin NLTC
|
|
Taɓa Range
± 2 * 2.5% @ gefe na farko
|
|
Babu Asara Load
1.3KW
|
|
Akan Rasa Load
6.5KW
|
1.3 Zane
630 kVA simintin guduro busassun nau'in taswira zane da girman.

02 Masana'antu
2.1 Kori
Nau'in na'ura mai mahimmanci wanda aka gina tare da babban -ciwon sanyi - birgima silikon karfe laminations a cikin wani mataki{2}}tsarin daidaita cinya don rage ƙwanƙwasa da hasarar halin yanzu. Tsarin Nau'in Core yana tabbatar da ko da rarrabawar iska da haɓakar zafi. Tare da abin rufe fuska mai lalata-, yana ba da aiki shiru, haɓakar ƙananan zafin jiki, da ingantaccen ƙarfin kuzari don ingantaccen aiki.

2.2 Guda

Na'urar taswirar tana fasalta motsin guduro na epoxy, yana tabbatar da ingantaccen rufi da ƙarfin injina. Ana yin iskar HV/LV da masu jagoranci na aluminium tare da rufin interlayer don haɓaka ƙarfin dielectric. Ana shigar da bushes a cikin taswira a tashoshi masu iska don amintattun hanyoyin haɗin lantarki da sauƙin kulawa. Gudun iskar danshi ne-hujja da kura{4}}mai jurewa, mai kyau ga mahalli masu tsauri.
2.3 Taron Karshe
Na'urar taswira ta ɗauki ingantaccen ƙira, mai nuna iskar epoxy{0}}resin simintin gyare-gyare da mataki{1}}waɗanda aka haɗe tare da ingantattun ɓangarorin rufin wuta. Naúrar tana haɗa mai sarrafa zafin jiki mai hankali da masu sanyaya sanyi waɗanda ke daidaita kwararar iska ta atomatik bisa yanayin kaya. Tare da cikakken keɓaɓɓen, lalata{4}} bushewar bushes da tashoshi, tsarinsa na buɗe{5}} tare da ingantattun tashoshi na iska yana tabbatar da ingantaccen zafi don ingantaccen aiki a ƙarƙashin yanayi daban-daban.

03 Gwaji
|
A'a. |
Gwajin Abun |
Naúrar |
Dabi'un Karɓa |
Ƙimar Ma'auni |
Kammalawa |
|
|
1 |
Auna juriya na iska |
/ |
Matsakaicin juriya rashin daidaituwa Juriya na layi: Kasa da ko daidai da 2% |
HV (layi) |
LV (layi) |
Wuce |
|
0.06% |
0.61% |
|||||
|
2 |
Auna ma'aunin ƙarfin lantarki da duba ƙaurawar lokaci |
/ |
Haƙuri na ƙimar ƙarfin lantarki akan babban tapping: ± 1/10 Alamar haɗi: Dyn11 |
-0.02% ~ 0.16% Domin 11 |
Wuce |
|
|
3 |
Auna Gajerun -Tsarin Tasirin kewayawa da Rasa Load |
/ kW kW |
t: 120 digiri Z%: ƙimar da aka auna Pk: ƙimar ƙima Pt: ƙima mai ƙima |
6.02% 4.55 6.28 |
Wuce |
|
|
4 |
Auna A'a{0}}Asara da A halin yanzu a 90% da 110% na ƙimar ƙarfin lantarki |
/ kW |
I0:: bayar da ma'auni darajar P0: ba da ƙima mai ƙima |
90% Ur |
0.414 0.985 |
Wuce |
|
100% Ur |
0.46 1.095 |
|||||
|
110% Ur |
0.506 1.204 |
|||||
|
5 |
Gwajin Karfin Wutar Lantarki |
/ |
HV: 20kV 60s LV: 3kV 60s |
Babu rushewar ƙarfin gwajin da ke faruwa |
Wuce |
|
|
6 |
Jarrabawar Juriya da Wutar Lantarki |
/ |
Wutar lantarki mai aiki (KV): 2 Ur Ƙarfin wutar lantarki (KV): 1.1 Duration(s):40 Mitar (HZ): 150 |
Babu rushewar ƙarfin gwajin da ke faruwa |
Wuce |
|
|
7 |
Gwajin fitar da Bangaranci |
pC |
Matsakaicin matakin sakin juzu'i zai zama 10 pC |
<10 |
Wuce |
|


04 Shiryawa da jigilar kaya
4.1 Shiryawa
The Cast Resin Dry Type Transformer an cika shi lafiyayye a cikin akwatunan plywood masu nauyi{0}, yana ba da kariya mai ƙarfi yayin sufuri da ajiya.
Ƙarfe{0}}ƙarfan gefuna suna haɓaka juriyar tasiri, yayin da kwantar da tarzoma na al'ada yana kiyaye ainihin da iska. Alamar waje (cibiyar nauyi, faɗakarwar danshi, wuraren ɗagawa) sun dace da ƙa'idodin dabaru na duniya.

4.2 Shipping

Ana jigilar tasfoman ne a karkashin tsarin CIF (Cost, Insurance & Freight) ta teku daga manyan tashoshin jiragen ruwa na kasar Sin zuwa Durban, Afirka ta Kudu. Harkokin sufurin na'ura ya haɗa da cikakken inshorar ruwa wanda ke rufe jimlar ƙimar kaya. Ana ba da sabis na isar da kayayyaki na ƙwararrun don izinin kwastam da dubawa a tashar jirgin ruwa.
Ana ba da shawarar ɗauka da sauri bayan isowa don hana cajin kuɗi.
05 Yanar Gizo da Takaitawa
A matsayin ingantaccen bayani don tsarin wutar lantarki, Cast Resin Dry Type Transformer ya fito fili tare da ƙirar mai kyauta, juriya na wuta, kariya da ɗanshi, da aiki kyauta, yana mai da shi dacewa ga gine-ginen kasuwanci, masana'antu, da aikace-aikacen makamashi mai sabuntawa. Tare da ingantacciyar injiniya da ingantaccen kulawar inganci, kowane rukunin yana ba da ingantaccen inganci, aminci, da dorewa.
Ta zabar mu, ba za ku sami mafi kyawun samfur kawai ba har ma da goyan bayan fasaha na ƙwararru da cikakkiyar sabis na tallace-tallace. Don cikakkun bayanai na fasaha ko mafita na musamman, tuntuɓi ƙungiyar injiniyarmu a yau!

Hot Tags: Cast coil transformer, ma'aikata, maroki, farashin, farashi
You Might Also Like
3 MVA Dry Type Transformers-13.8 / 0.48 kV|Jamaica 2025
1.25 MVA Cast Resin Nau'in Mai Canjawa-0.415/3.3*6.6...
630 kVA Simintin Gudun Busassun Nau'in Canji-66.6/0....
400 kVA Busassun Nau'in Canjin Lantarki-0.55 / 0.46 ...
160 kVA Nau'in Busassun Nau'in Cikin Gida-10 / 0.4 k...
630 kVA 3 Tsarin Busassun Nau'in Canji-6.6 / 0.55 kV...
Aika Aikace-aikacen