1500 KVA Matsakaici Nau'in Wutar Lantarki na Busassun Nau'in Canjin-15/0.55 KV|Afirka ta Kudu 2025
Yawan aiki: 1500 kVA
Wutar lantarki: 15/0.55kV
Feature: tare da sanyaya magoya

Cast Coil Dry Type Transformer: Gina Mai Tauri don Neman Muhalli.
01 Gabaɗaya
1.1 Bayanin Aikin
1500kVA Cast Coil dry type transformer an isar da ita zuwa Afirka ta Kudu a shekarar 2025. Ƙarfin wutar lantarkin shine 1500 kVA tare da sanyaya KNAN/KNAF. Babban ƙarfin lantarki shine 15 kV tare da ± 2 * 2.5% tapping range (NLTC), ƙarfin lantarki na biyu shine 0.55 kV, sun kafa ƙungiyar vector na Dyn11.
Nau'in Canji na Cast Coil Dry yana wakiltar koli na aminci, aminci, da dorewar muhalli a fasahar rarraba wutar lantarki. Ba kamar ruwa na gargajiya -cikakke ko busasshiyar iska{2}} nau'in tasfoma, babban{3}}ƙarar wutar lantarki da ƙananansa{4} ana lulluɓe shi da ingantaccen resin epoxy a ƙarƙashin matsa lamba. Wannan ci-gaba na tsarin simintin gyare-gyare yana haifar da na'ura mai canzawa wacce ke kusan kulawa-wacce kuma mara gafala ga mahalli.
An yi gyare-gyaren Cast Coil Transformer don yin aiki na musamman. Ba shi da -mai ƙonewa, baya fitar da hayaki mai guba, kuma yana haifar da haɗarin ɗigowar mai, yana mai da shi mafi kyawun zaɓi don amintaccen shigarwa a cikin gida, manufa{2}mahimman aikace-aikace kamar manyan gine-gine, asibitoci, cibiyoyin bayanai, masana'antu, da wuraren aikin waje.
Tare da mafi girman juriya ga danshi, sinadarai, da gurɓatawa, haɗe tare da babban ƙarfin wutan lantarki da gajere na musamman{0} kewayawa jure iyakoki, Cast Coil Dry Type Transformer yana tabbatar da samar da wutar lantarki mara yankewa da tsawon rayuwar sabis, yana ba da kwanciyar hankali na ƙarshe da ƙarancin ƙimar mallaka.
1.2 Ƙayyadaddun Fasaha
1500 kVA simintin busassun nau'in taswira ƙayyadaddun bayanai da takaddar bayanai
|
Isarwa zuwa
Afirka ta Kudu
|
|
Shekara
2025
|
|
Nau'in
busassun irin na'ura mai canzawa
|
|
Babban abu
Silicon karfe takardar hatsi daidaitacce
|
|
Daidaitawa
Saukewa: IEC60076
|
|
Ƙarfin Ƙarfi
1500kVA
|
|
Yawanci
50HZ
|
|
Ƙungiyar Vector
Domin 11
|
|
Mataki
3
|
|
Nau'in Sanyi
ONAN/ONAF
|
|
Babban Voltage
15kV
|
|
Na biyu Voltage
0.55kV
|
|
Abubuwan Iska
Aluminum
|
|
Impedance
6%
|
|
Matsa Canji
Farashin NLTC
|
|
Taɓa Range
± 2 * 2.5% @ gefe na farko
|
|
Babu Asara Load
2.45KW
|
|
Akan Rasa Load
11.5KW
|
|
Basic pulse lighting withstand voltage primary side (BIL)
95kV ku
|
|
Mitar wutar lantarki jure wa wutar lantarki{0}}bangaren farko
38kV
|
|
Mitar wutar lantarki jure wa wutar lantarki{0}bangare na biyu
3kV ku
|
|
Hawan zafin jiki mai iska @ yanayin sabis
100K
|
|
Matsayin rufi
F
|
1.3 Zane
1500 kVA simintin guduro busassun nau'in taswira zane da girman.
![]() |
![]() |
02 Masana'antu
2.1 Kori
Babban simintin coil bushe{0} nau'in transfomer yawanci ana yin shi ne daga ƙarfe mai girma{1}}, sanyi{2}} hatsin da aka yi birgima{3}}madaidaicin (CRGO) silicon karfe. Laminations an jera su daidai kuma an danne su don samar da da'irar maganadisu mai ƙarfi, mai ƙarfi. Wannan ƙira yana rage girman asara (hysteresis da eddy igiyar ruwa), yana tabbatar da kyakkyawan kwanciyar hankali na inji don jure gajeriyar runduna mai kewayawa-.
2.2 Guda
Juyawar simintin simintin busasshen na'ura yawanci ana yin shi ne da manyan madugu na jan ƙarfe ko aluminum, waɗanda aka raunata su a cikin coils sannan a lulluɓe su a cikin resin epoxy ta hanyar fasahar simintin ƙarfe. Wannan simintin simintin gyare-gyaren yana kawar da gibin iska, yana samar da kyakkyawan aikin rufewa, juriyar danshi da ƙarfin injina, yayin da yake danne juzu'i da tabbatar da kwanciyar hankali har ma a cikin yanayi mara kyau.

2.3 Taron Karshe

Haɗin ƙarshe na simintin simintin busasshen nau'in taswira yana farawa tare da ɗora jigon baƙin ƙarfe a kan firam ɗin tushe. Sa'an nan, injin- simintin girma -ƙarar wutar lantarki da ƙarancin wutar lantarki{3} ana ɗagawa kuma ana ɗora su sosai akan ginshiƙan ginshiƙan, tare da sanya na'urori masu ɗaukar hoto don kula da madaidaicin giɓi. Bayan haka, ana haɗa wayoyi masu guba zuwa tarkace, masu sanyaya masu sanyaya (idan an haɗa su) da na'urorin kula da yanayin zafi suna sakawa, sannan su dace da shingen kariya. Gwaje-gwajen lantarki na ƙarshe suna tabbatar da yardawar taro.
03 Gwaji
Gwaje-gwaje don simintin busassun nau'in tashoshi, irin su 1500kVA{11}}15/0.55kV, manne da ka'idojin IEC 60076 (1, 3, 11) kuma sun haɗa da maɓalli na yau da kullun: ma'aunin juriya (tabbatar rashin daidaituwa Kasa da ko daidai da 2%), ƙimar ƙarfin lantarki/maɓallin lokaci, 0D ±1, 0D, 0D, 0D, 0D. gajere -asarawar kewayawa/nauyin nauyi da asarar nauyi/na gwaje-gwaje na yanzu, gwaje-gwajen dielectric (38kV da aka yi amfani da wutar lantarki don 60s, 1.1kV mai haifar da wutar lantarki a 150Hz na 40s), da gwajin fitarwa na juzu'i (max Kasa da ko daidai da 10pC), duk suna tabbatar da ƙwararrun lantarki da ƙima.
|
A'a. |
Gwajin Abun |
Naúrar |
Karba Darajoji |
Ƙimar Ma'auni |
Kammalawa |
|
|
1 |
Auna juriya na iska |
/ |
Matsakaicin juriya rashin daidaituwa Juriya na layi: Kasa da ko daidai da 2% |
HV (layi) |
LV (layi) |
Wuce |
|
0.17% |
0.32% |
|||||
|
2 |
Auna ma'aunin ƙarfin lantarki da duba ƙaurawar lokaci |
/ |
Haƙuri na ƙimar ƙarfin lantarki akan babban tapping: ± 1/10 Alamar haɗi: Dyn11 |
0.03% ~ 0.19% Domin 11 |
Wuce |
|
|
3 |
Auna Gajerun -Tsarin Tasirin kewayawa da Rasa Load |
/ kW kW |
t: 120 digiri Z%: ƙimar da aka auna Pk: ƙimar ƙima Pt: ƙima mai ƙima |
6.01% 8.437 10.437 |
Wuce |
|
|
4 |
Auna A'a{0}}Asara da A halin yanzu a 90% da 110% na ƙimar ƙarfin lantarki |
/ kW |
I0 :: bayar da ma'auni darajar P0: ba da ƙima mai ƙima |
90% Ur |
0.27 2.331 |
Wuce |
|
100% Ur |
0.30 2.59 |
|||||
|
110% Ur |
0.33 2.849 |
|||||
|
5 |
Gwajin Karfin Wutar Lantarki |
/ |
HV: 38kV 60s LV: 5kV 60s |
Babu rushewar ƙarfin gwajin da ke faruwa |
Wuce |
|
|
6 |
Jarrabawar Juriya da Wutar Lantarki |
/ |
Wutar lantarki mai aiki (KV): 2 Ur Ƙarfin wutar lantarki (KV): 1.1 Duration(s):40 Mitar (HZ): 150 |
Babu rushewar ƙarfin gwajin da ke faruwa |
Wuce |
|
|
7 |
Gwajin fitar da Bangaranci |
pC |
Matsakaicin matakin sakin juzu'i zai zama 10 pC |
<10 |
Wuce |
|


04 Shiryawa da jigilar kaya
4.1 Shiryawa

Nau'in canjin busasshen simintin simintin gyare-gyare an cika shi a cikin akwati mai ƙarfi na katako. A ciki, an lulluɓe shi da firgita{1}} kumfa mai ɗaurewa don guje wa lalacewar karo, an daidaita shi tare da faɗuwar ƙarfe don hana motsi, kuma ana buga harka na waje tare da bayyanannun alamun jigilar kaya, samfurin samfur da nauyi don sauƙin sarrafawa.
4.2 Shipping
Karkashin sharuɗɗan CIF, ana jigilar simintin simintin busasshen nau'in taswira (a cikin ƙaƙƙarfan katako) zuwa Durban. Mai siyarwa yana tsara jigilar teku, yana biyan kaya, da siyan inshora akan asara/lalacewa yayin tafiya. Ana kammala jigilar kaya lokacin da kayan ke cikin jirgin, kuma za a kai kayan zuwa tashar jiragen ruwa na Durban kamar yadda aka tsara.

05 Yanar Gizo da Takaitawa
Tare da ingantacciyar simintin resin sa mai ƙarfi, ingantaccen nau'in ƙira mai bushewa{0}}, da daidaiton aiki, na'urar busasshen busasshen simintin mu yana tsaye a matsayin amintaccen maganin wutar lantarki don buƙatun masana'antu, kasuwanci, da abubuwan more rayuwa. An ƙirƙira shi don aminci, ƙarancin kulawa, da daidaitawa zuwa yanayin aiki dabam-dabam, yana ba da tsayayyen goyan bayan wutar lantarki don ci gaba da gudanar da ayyukanku cikin sauƙi. Ko kuna neman dorewa, inganci, ko bin ƙaƙƙarfan ƙa'idodi, muna shirye mu taimaka{3}}bari wannan na'urar ta atomatik ya ɗaukaka amincin tsarin wutar lantarki.

Hot Tags: matsakaici irin ƙarfin lantarki bushe irin transformers, ma'aikata, maroki, farashin, tsada
You Might Also Like
500 kVA Dry Resin Transformer-13.8 / 0.46 kV|Afirka ...
630 kVA Simintin Gudun Busassun Nau'in Canji-66.6/0....
400 kVA Busassun Nau'in Canjin Lantarki-0.55 / 0.46 ...
250 kVA Dry Cast Resin Transformers-10/0.4 kV|Jojiya...
160 kVA Nau'in Busassun Nau'in Cikin Gida-10 / 0.4 k...
2500 kVA Dry Transformer-10 / 0.4 kV|Jojiya 2025
Aika Aikace-aikacen