2100 kVA Busassun Nau'in Rarraba Mai Canjawa-13.8 / 0.46 kV|Afirka ta Kudu 2024
Yawan aiki: 2100kVA
Wutar lantarki: 13.8/0.46 kVA
Siffar: Tare da CT (5000/1)

Ingantacciyar 2100 kVA busassun nau'in rarraba wutar lantarki tare da ingantaccen rufi da kariya mai kaifin baki.
01 Gabaɗaya
1.1 Bayanin Aikin
An kera shi don abokin ciniki na Afirka ta Kudu a cikin 2024, wannan busasshen nau'in rarraba busassun nau'in 2100 kVA yana da fasalin iska mai cike da rudani a cikin resin epoxy. Kasancewar mai - kyauta, yana rage haɗarin gobara da gurɓacewar muhalli. Tare da rufin Class F wanda aka ƙididdige don yanayin aiki har zuwa digiri 155.
An ƙididdige wutar lantarki a 2100 kVA, tare da ƙarfin farko na 13.8 kV da ƙarfin lantarki na 0.468 kV (468 V). Yana da manufa don ƙarfafa hoists mine da kayan aiki masu nauyi waɗanda ke aiki a 468 V.
Rukunin vector ɗin sa shine D ({0}} digiri )d0, inda babban{2}} gefen ƙarfin lantarki ya ƙunshi motsin digiri na +15. Wannan ƙira ta cika buƙatun tsarin lokaci kuma yana taimakawa rage jituwa da zagayawa yayin aiki a layi daya.
An yi ainihin abin da aka yi da karfen siliki mai madaidaicin hatsi, wanda ke ba da asara mai ƙanƙanta da babban juzu'in maganadisu, yana ba da gudummawa ga ƙarancin asarar 3.2 kW.
An sanye shi da mai sarrafa zafin jiki da na'ura mai canzawa na yanzu (5000/1 CT), mai canzawa yana goyan bayan kula da yanayin zafin jiki da kariya, da kuma aunawa na yanzu, yana sauƙaƙe haɗawa cikin tsarin kariya da kulawa.
1.2 Ƙayyadaddun Fasaha
2100kVA Resin simintin busassun nau'in taswira da takaddun bayanai
|
Isarwa zuwa
Afirka ta Kudu
|
|
Shekara
2024
|
|
Nau'in
Guduro simintin busassun nau'in taswira
|
|
Babban abu
Silicon karfe takardar hatsi daidaitacce
|
|
Daidaitawa
Saukewa: IEC60076
|
|
Ƙarfin Ƙarfi
2100 kVA
|
|
Yawanci
60HZ
|
|
Mataki
Uku
|
|
Ƙungiyar Vector
D ({0}} digiri ) d0
|
|
Nau'in Sanyi
AN
|
|
Babban Voltage
13.8 kV
|
|
Na biyu Voltage
0.468 kV
|
|
Abubuwan Iska
AL
|
|
Impedance
7.5%
|
|
Matsa Canji
/
|
|
Taɓa Range
/
|
|
Babu Asara Load
3.2 kW
|
|
Akan Rasa Load
3.2 kW
|
|
Matsayin rufi
F
|
|
Na'urorin haɗi
Mai sarrafa zafin jiki, CT (5000/1)
|
1.3 Zane
2100kVA Resin simintin busassun nau'in taswira zane

02 Masana'antu
2.1 Kori
2100 kVA uku -lokacin busassun nau'in rarraba kayan wutan lantarki na amfani da hatsi{2}}madaidaicin zanen gadon ƙarfe na siliki tare da babban ƙarfin maganadisu, haɓaka ƙarfin lantarki da rage hasara. Waɗannan zanen gado suna da ƙaƙƙarfan kaddarorin inji don jure aiki da damuwa na tsawon lokaci-. SCOTECH yana tabbatar da burs Kasa da ko daidai da 0.02mm kuma babu lahani. An lulluɓe tushen tushen da danshi{8}} hujjar resin epoxy don ƙarin dorewa da kariya mai zafi.

2.2 Guda

Nau'in canjin busassun busassun yana da iska guda biyu, duka an gina su tare da ɗorewa na aluminum don tabbatar da kyakkyawan aiki da tsawon sabis. Dukkanin iskar da aka keɓe an rufe su da kayan rufin Class F, kuma gabaɗayan coil ɗin yana cikin injin da aka yi masa ciki tare da resin Epoxy Class F, yana samar da ƙaƙƙarfan ɗanshi mai juriya da tsayayyen tsarin rufewa.
2.3 taro na ƙarshe
Abubuwan da aka ƙirƙira da abubuwan da aka ƙirƙira suna haɗuwa, yayin da ake yin haɗin wutar lantarki, rufewa, da gyare-gyaren tsari.
Karkashin injin, resin epoxy yana zubowa tsakanin iskoki da ainihin, yana samar da ingantaccen tsari mai warkewa.
Bayan haɗawa da warkewa, ana yin jerin gwaje-gwajen lantarki da na injina don tabbatar da cewa na'urar ta atomatik ta cika ƙa'idodin ƙira da aminci.

03 Gwaji


Gwajin yau da kullun
1. Auna juriya na iska
2. Ma'auni na ƙarfin lantarki da kuma duba ƙaurawar lokaci
3. Ma'auni na gajere - hanawa da kuma asarar kaya
4. Ma'auni na babu{1}}asara da na yanzu
5. Gwajin wutar lantarki da aka yi amfani da shi
6. Gwajin jurewar wutar lantarki da aka haifar
7. Gwajin fitar da bangare
8. Gwajin Dielectric Oil
Sakamakon Gwaji
|
A'a. |
Gwajin Abun |
Naúrar |
Dabi'un Karɓa |
Ƙimar Ma'auni |
Kammalawa |
|
|
1 |
Auna juriya na iska |
/ |
Matsakaicin juriya rashin daidaituwa Juriya na layi: Kasa da ko daidai da 2% |
HV (layi) |
LV (layi) |
Wuce |
|
0.18% |
1.61% |
|||||
|
2 |
Auna ma'aunin ƙarfin lantarki da duba ƙaurawar lokaci |
/ |
Haƙuri na ƙimar ƙarfin lantarki akan babban tapping: ± 1/10 Alamar haɗi: D ({0}} digiri ) d0 |
-0.18% ~ -0.07% D ({0}} digiri ) d0 |
Wuce |
|
|
3 |
Auna Gajerun -Tsarin Tasirin kewayawa da Rasa Load |
/ kW kW |
t: 120 digiri Z%: ƙimar da aka auna Pk: ƙimar ƙima Pt: ƙima mai ƙima |
8.13% 12.662 16.261 |
Wuce |
|
|
4 |
Auna A'a{0}}Asara da A halin yanzu a 90% da 110% na ƙimar ƙarfin lantarki |
/ kW |
I0 :: bayar da ma'auni darajar P0: ba da ƙima mai ƙima |
90% Ur |
110% Ur |
Wuce |
|
0.162% |
0.198% |
|||||
|
2.3265 |
2.8435 |
|||||
|
5 |
Gwajin Karfin Wutar Lantarki |
/ |
HV: 38kV 60s LV: 3kV 60s |
Babu rushewar ƙarfin gwajin da ke faruwa |
Wuce |
|
|
6 |
Jarrabawar Juriya da Wutar Lantarki |
/ |
Wutar lantarki mai aiki (KV): 2 Ur Ƙarfafa ƙarfin lantarki (KV): 0.936 Duration(s):40 Mitar (HZ): 150 |
Babu rushewar ƙarfin gwajin da ke faruwa |
Wuce |
|
|
7 |
Gwajin fitar da Bangaranci |
pC |
Matsakaicin matakin sakin juzu'i zai zama 10 pC |
<10 |
Wuce |
|
04 Shiryawa da jigilar kaya


05 Yanar Gizo da Takaitawa
Wannan 2100 kVA resin simintin busassun nau'in na'ura mai rarrabawa an tsara shi musamman don abokin ciniki na Afirka ta Kudu. Wannan na'ura mai canzawa ya dace musamman ga injina masu nauyi{2}, manyan injuna, da na'urori masu sarrafawa a cikin ma'adinai da aikace-aikacen masana'antu waɗanda ke buƙatar ƙarfin ɗaukar nauyi. SCOTECH yana shirye don samar da ƙwararrun gyare-gyare da sabis mai inganci don biyan buƙatun ku.
A matsayin ƙwararrun masana'antar taswira mai bushewa, SCOTECH tana ba da samfuran da suka dace da ƙa'idodin ƙasashen duniya kamar IEC, ANSI/IEEE, NEMA, CSA, da BS. Resin simintin busassun nau'in taswira yana rufe ikon da aka ƙima daga 50 kVA har zuwa 15 MVA, tare da manyan ƙarfin lantarki har zuwa 36 kV. Dukkan mitoci 50 Hz da 60 Hz suna samuwa, tare da haɗin delta ko tauraro. Matsakaicin iskar wutar lantarki an lullube shi a cikin resin epoxy, tare da azuzuwan rufi waɗanda ke kama da A, E, B, F zuwa H, da matakan kariya waɗanda za'a iya daidaita su daga IP 2X zuwa IP 4X.
Zaɓuɓɓukan sanyaya sun haɗa da sanyaya iska ta yanayi (ONAN) da sanyaya iska mai tilastawa (ONAF), sanye take da na'urori masu auna zafin jiki da yawa da kuma relays na zafi don ingantaccen kariya ta zafi. Muna kuma samar da na'urorin haɗi kamar ƙafafu, masu canji na yanzu, akan{1}}masu sauya famfo (OLTC), da akwatunan marshalling don biyan buƙatun abokin ciniki iri-iri.

Hot Tags: busassun nau'in rarraba wutar lantarki, masana'anta, mai kaya, farashi, farashi
You Might Also Like
400 kVA Busassun Nau'in Canjin Lantarki-0.55 / 0.46 ...
250 kVA Dry Cast Resin Transformers-10/0.4 kV|Jojiya...
630 kVA 3 Tsarin Busassun Nau'in Canji-6.6 / 0.55 kV...
630 kVA Nau'in Busassun Nau'in Rubutun Mataki na Uku...
2500 kVA Dry Transformer-10 / 0.4 kV|Jojiya 2025
630 kVA Cast Coil Transformer-6.6 / 0.55 kV|Afirka t...
Aika Aikace-aikacen