250 kVA Dry Cast Resin Transformers-10/0.4 kV|Jojiya 2025

250 kVA Dry Cast Resin Transformers-10/0.4 kV|Jojiya 2025

Ƙasa: Jojiya 2025
Yawan aiki: 250kVA
Wutar lantarki: 10/0.4kV
Feature: tare da CT
Aika Aikace-aikacen

 

 

dry cast resin transformers

Eco{0}majagaba na abokantaka, ingantaccen inganci, resin simintin gyare-gyare yana ƙarfafa gaba!

 

 

01 Gabaɗaya

1.1 Bayanin Aikin

250 kVA resin cast dry type transformer an isar da shi zuwa Jojiya a shekarar 2025. Ƙarfin wutar lantarkin shine 250 kVA tare da sanyaya ONAN. Babban ƙarfin lantarki shine 10 kV tare da ± 2 * 2.5% tapping range (NLTC) ta hanyar danna hanyoyin haɗin gwiwa, ƙarfin lantarki na biyu shine 0.4 kV, sun kafa ƙungiyar vector na Dyn11.

Wannan resin - busasshen na'ura mai ɗaukar nauyi - nau'in transformer yana da fasalin ci-gaba da ƙira da nufin cimma ingantacciyar watsa wutar lantarki. Tsarin kula da yanayin zafinta ya ƙunshi na'urar sarrafa zafin jiki na -E{4}} na kasar Sin da na'urori masu zaman kansu na PT100. An keɓance na'urorin bincike guda uku na PT100 musamman don lura da zafin iska, yayin da ake amfani da bincike ɗaya don lura da ainihin zafin jiki. Wannan tsari mai sassauƙa yana tabbatar da daidaitaccen sarrafa zafin jiki a ƙarƙashin yanayin aiki daban-daban, yadda ya kamata ya hana haɗarin zafi fiye da kima da tsawaita rayuwar kayan aiki.

Bugu da ƙari, na'urar taranfofi tana sanye da na'urar taransifoma (CT) na yanzu don gano magudanar ruwa a ƙasa a ƙaramin gefen wutar lantarki, yana ba da damar gano kuskure cikin sauri da haɓaka aminci da amincin tsarin. Tare da aikin sa na musamman, ƙira mai ɗorewa, da kuma fitattun fasalulluka na aminci, wannan na'urar ta atomatik ya zama maɓalli mai mahimmanci a cikin tsarin wutar lantarki na zamani, yana ba da tabbacin ƙarfin ƙarfi da aminci ga aikace-aikace daban-daban.

 

 

 

1.2 Ƙayyadaddun Fasaha

250 kVA guduro simintin busassun nau'in taswira ƙayyadaddun bayanai da takaddar bayanai

Isarwa zuwa
Jamaica
Shekara
2025
Nau'in
Guduro simintin busassun nau'in taswira
Babban abu
Silicon karfe takardar hatsi daidaitacce
Daidaitawa
Saukewa: IEC60076
Ƙarfin Ƙarfi
250kVA
Yawanci
50HZ
Ƙungiyar Vector
Domin 11
Mataki
3
Nau'in Sanyi
ONAN
Babban Voltage
10 kV
Na biyu Voltage
0.4 kV
Abubuwan Iska
Aluminum
Impedance
6%
Matsa Canji
Farashin NLTC
Taɓa Range
± 2*2.5%@gefen farko ta hanyar latsa hanyoyin haɗi
Babu Asara Load
0.52 kW
Akan Rasa Load
3.8 kW
Matsayin rufi
F

 

 

1.3 Zane

250 kVA guduro simintin busassun nau'in taswira zane da girman.

dry cast resin transformers drawing

 

 

02 Masana'antu

2.1 Kori

Tushen guduro{0}}sashen bushewa{1}nau'in na'urar taswira wani abu ne mai mahimmanci, wanda aka yi shi da manyan faranti na ƙarfe na maganadisu kuma an ƙirƙira shi a cikin wani lamintaccen tsari don rage hasarar da ake samu a halin yanzu da haɓaka aiki. Ana amfani da abin rufe fuska tsakanin laminations don hana gajeriyar kewayawa, inganta da'irar maganadisu, da tabbatar da ingantaccen watsawa na yanzu. Wannan ƙira yana kiyaye aiki mai ƙarfi a cikin yanayin zafi mai ƙarfi da ɗanɗano, yayin da kuma yana ba da damar ɓarkewar zafi mai kyau don sakin zafin da aka samar yayin aiki yadda ya kamata, yana hana zafi fiye da kima. Ƙaƙƙarfan tsari na ainihin yana ba da damar shigarwa da sarrafa taswirar ta yau da kullun a cikin sararin samaniya{6}}ƙaƙƙarfan mahalli, ta haka inganta ingantaccen aiki da aminci gabaɗaya, tare da ƙara dawwama.

laminated core of transformer

 

2.2 Guda

resin material

Nau'in guduro{0}simin busheshe{1}nau'in taswira wani muhimmin sashi ne da ke da alhakin juyawa da watsa wutar lantarki, yana tasiri sosai da aiki da inganci. Anyi daga manyan kayan aikin rufewa-, yana ba da kyakykyawan rufin asiri da juriya mai girma{4}} don hana zubewar yanzu. Coil ɗin yana fasalta ingantattun dabarun jujjuyawar waya don tsattsauran tsarin waya da rarraba iri ɗaya, haɓaka aikin lantarki da rage hasara mai ƙima.

An tsara shi don ingantaccen zafi a lokacin aiki, yana hana lalacewa daga zafi mai zafi. Coil ɗin yana jujjuya simintin gyare-gyare don ƙarfafawa, wanda ke ƙarfafa yawa da kwanciyar hankali, yana tabbatar da daidaiton aiki a ƙarƙashin yanayi daban-daban.

Bugu da ƙari, kayan guduro yana ba da juriya na lalata, yana ba shi damar yin aiki da aminci a cikin yanayi mai ɗanɗano ko gurɓataccen yanayi, yana haɓaka dorewa.

 

2.3 Taron Karshe

1. Gyaran Kwangila:Tabbatar shigar da pre{0} simintin simintin simintin gyare-gyare a kan ainihin bisa ga buƙatun ƙira, tabbatar da cewa jagora, hanyoyin haɗin gwiwa, da tazarar coils sun bi ƙayyadaddun ƙira don tabbatar da aikin wutar lantarki na yau da kullun.

2. Haɗin Wutar Lantarki:Haɗa manyan igiyoyin wutar lantarki{0}} da ƙananan{1}, tabbatar da duk hanyoyin haɗin gwiwa suna da tsaro kuma sun dace da ƙa'idodi.

3. Shigar da Na'urorin haɗi:Shigar da na'urorin haɗi daban-daban kamar ƙafafun, insulators, masu kula da zafin jiki, PT100 zazzabi bincike, da CTs (masu canza wuta na yanzu) don tabbatar da aikin da ya dace na kayan taimako.

transformer accessories

 

 

03 Gwaji

A'a.

Gwajin Abun

Naúrar

Dabi'un Karɓa

Ƙimar Ma'auni

Kammalawa

1

Auna juriya na iska

/

Matsakaicin juriya rashin daidaituwa

Juriya na layi: Kasa da ko daidai da 2%

HV (layi)

LV (layi)

Wuce

0.41%

0.61%

2

Auna ma'aunin ƙarfin lantarki da duba ƙaurawar lokaci

/

Haƙuri na ƙimar ƙarfin lantarki akan babban tapping: ± 1/10

Alamar haɗi: Dyn11

0.03% ~ 0.13%

Domin 11

Wuce

3

Auna Gajerun -Tsarin Tasirin kewayawa da Rasa Load

/

kW

kW

t: 120 digiri

Z%: ƙimar da aka auna

Pk: ƙimar ƙima

Pt: ƙima mai ƙima

6.14%

2.458

3.455

Wuce

4

Auna A'a{0}}Asara da A halin yanzu a 90% da 110% na ƙimar ƙarfin lantarki

/

kW

I0 :: bayar da ma'auni darajar

P0: ba da ƙima mai ƙima

90% Ur

0.50

0.437

Wuce

100% Ur

0.56

0.486

110% Ur

0.616

0.534

5

Gwajin Karfin Wutar Lantarki

/

HV: 28kV 60s

LV: 3kV 60s

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

6

Jarrabawar Juriya da Wutar Lantarki

/

Wutar lantarki mai aiki (KV):

2 Ur

Ƙarfin wutar lantarki (KV): 0.8

Duration(s):40

Mitar (HZ): 150

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

7

Gwajin fitar da Bangaranci

pC

Matsakaicin matakin sakin juzu'i zai zama 10 pC

<10

Wuce

 

types of testing of transformer
Partial Discharge Test

 

 

04 Shiryawa da jigilar kaya

Solid wood base
customs clearance procedures
 
 
 

 

05 Yanar Gizo da Takaitawa

A ƙarshe, resin simintin busassun nau'in tasfom ɗin ya tsaya a matsayin shaida ga ƙirƙira a cikin injiniyoyin lantarki, yana ba da ingantaccen aminci, aminci, da juriyar muhalli idan aka kwatanta da na'urorin canji na gargajiya. Ƙaƙƙarfan ƙira ɗin sa da ingantaccen kaddarorin rufewa suna tabbatar da ingantaccen aiki a aikace-aikace daban-daban, yana mai da shi kyakkyawan zaɓi don tsarin rarraba wutar lantarki na zamani. Kamar yadda masana'antu ke ƙara ba da fifiko ga dorewa da ingancin kuzari, an saita injin simintin busasshen na'ura mai canzawa don taka muhimmiyar rawa wajen tsara makomar watsa makamashi. Ƙarfinsa don yin aiki a wurare daban-daban, haɗe tare da ƙarancin buƙatun kulawa, sanya shi a matsayin babban kadara don saduwa da haɓakar buƙatu don amintattun hanyoyin samar da wutar lantarki na eco{3}. Yayin da muke ci gaba da ci gaba a cikin fasaha da buƙatun makamashi, injin simintin busasshen na'ura mai ba da wutar lantarki ba shakka zai ci gaba da kasancewa a sahun gaba wajen haɓaka kayan aikin lantarki.

electrical engineering

 

Hot Tags: busassun guduro transfoma, masana'anta, mai kaya, farashi, farashi

Aika Aikace-aikacen