Jiangshan Scotech Electric Co., Ltd yana ɗaya daga cikin amintattun masana'anta da masu samar da sandar tarho na kva 75 kva{7}13.8/0.24/0.12 kv|Guyana 2025 in China. Da fatan za a ji kyauta don siyan kayayyaki masu inganci don siyarwa anan kuma ku sami zane-zane daga masana'anta. Tuntube mu don ƙarin bayani.

 

transformer telephone pole

Guda ɗaya sandar sandar da aka ɗora tafsiri: Ingantacce, mai ɗorewa, sarari{0}}ƙarar sandar ajiya{1}} babban bayani.

 

 

01 Gabaɗaya

1.1 Bayanin Aikin

75 kVAlokaci guda iyakacin duniya saka taransifomaAn isar da shi zuwa Guyana a cikin 2025. Ƙididdigar ƙarfin wutar lantarki shine 75 kVA tare da sanyaya ONAN. Babban ƙarfin lantarki shine 13.8 kV tare da ± 2 * 2.5% tapping range (NLTC), ƙananan ƙarfin lantarki shine 0.12 / 0.24 kV, sun kafa ƙungiyar vector na Ii0.

An tsara kuma an gwada su daidai daIEEE da ANSI C57.12.00ma'auni. An ƙididdige shi don60Hzaiki, tare da babban ƙimar ƙarfin lantarki (HV) na13.8kVda ƙarancin ƙimar wutar lantarki (LV) na{{0}120/240V. Wannan fitowar wutar lantarki mai dual tana ba da damar samar da 120V na lokaci guda don haskakawa da 240V don wutar lantarki ko ƙananan kaya na kasuwanci, yana mai da shi kyakkyawan zaɓi don tsaga{3}tsarin rarraba lokaci da aka saba amfani da shi a Arewacin Amurka da sauran yankuna don zama, lantarki na karkara, da aikace-aikacen kasuwanci mai haske.

Wurin lantarki yana amfani da shikayan jujjuyawar jan ƙarfe don duka HV da LV coils, yana ba da ƙarfin aiki mai ƙarfi, kyakkyawan juriya mai raɗaɗi, da ƙaƙƙarfan ɗan gajeren lokaci{0}}wajen jure iyawa na dogon lokaci{1}. A polarity neragewakuma rukunin vector shineIo, Sauƙaƙe daidaitawar polarity lokacin da ake sarrafa tasfofi da yawa a layi daya ko jeri. An sanye shi da5 babu{1}} loda wuraren matsasamar da kewayon famfo na± 2×2.5% (jimlar kewayon 10%), wanda ya dace da ramawa ga bambancin wutar lantarki na layi kuma yana ba da damar daidaita tsarin wutar lantarki a ƙarƙashin yanayi daban-daban.

A taƙaice, wannan sandal ɗin tarho mai karfin 75kVA ya haɗu da ƙaƙƙarfan gini, ingantaccen aiki, ƙarancin asara, faffadan famfo, da ingantaccen ƙarfin walƙiya. Yana da kyakkyawan bayani don hanyoyin sadarwar rarrabawa suna buƙatar abin dogaro da tattalin arziƙi guda ɗaya - samar da wutar lantarki na lokaci ɗaya, gami da haɓaka wutar lantarki na karkara, rarrabawar kewayen birni, samar da wutar lantarki na ɗan lokaci, da haɗe-haɗen grid na lokaci ɗaya{{3} don tsarin ajiya na hotovoltaic ko makamashi.

 

 

 

1.2 Ƙayyadaddun Fasaha

Nau'in ƙayyadaddun igiyoyin tarho na 75 kVA da takaddar bayanai

Isarwa zuwa
Guyana
Shekara
2025
Nau'in
Pole mounted transformer
Daidaitawa
IEEE & ANSI C57.12.00
Ƙarfin Ƙarfi
75 kVA
Yawanci
60HZ
Mataki
1
Polarity
Ragewa
Nau'in Sanyi
ONAN
Babban Voltage
13.8 kV
Na biyu Voltage
0.12 / 0.24 kV
Abubuwan Iska
Copper
Matsala ta kusurwa
Ii0
Impedance
2%
Matsa Canji
± 2*2.5%(jimlar kewayon{2}}%)
Babu Asara Load
0.214 kW
Akan Rasa Load
0.713 kW
Jimillar hasara
0.927 kW
Basic lighting impulse (HV)
95kV ku
Ƙarfin haske na asali (LV)
30kV

 

1.3 Zane

75 kVA taswira zanen sandar tarho zane da girman.

transformer telephone pole diagram transformer telephone pole nameplate

 

 

02 Masana'antu

2.1 Kori

transformer telephone pole core made of low-loss grain-oriented silicon steel

Ana kera core transformer daga babban -maki, ƙananan{1}}asarar hatsi{2}}ƙarshen silicon mai daidaitacce. Babban ƙirar ƙira yana rage ƙanƙara da asara a halin yanzu, cimma ma'aunia'a - asarar nauyi na 210 W kawai(an gwada a rated ƙarfin lantarki, 26 digiri na yanayi), da kyau a cikin IEEE C57.12.20 bukatun haƙuri. Babban abin da aka yanke shi ne daidai -, an share shi don rage damuwa na ciki, kuma an danne shi don jure ƙarfin injina yayin sufuri da aiki na tsawon lokaci-.

 

2.2 Guda

Dukansu manyan wutar lantarki (13.8kV) da ƙananan ƙarfin lantarki (120/240V) suna da rauni tare dahigh - jan karfe mai tsafta(COPPER/COPPER), yana tabbatar da kyakkyawan aiki, gajeriyar iya jure wa da'ira, da dogayen aminci. An auna juriya na iska na HV a wuraren famfo (misali, Tap 3: 57.279 Ω tsakanin H1-H2), kuma an yi rikodin juriya na LV (misali, X1-X3: 0.003122 Ω). Siffofin na'urar wuta5 babu{1}} loda wuraren matsada kewayon± 2 × 2.5% (jimlar 10%), ƙyale daidaitawar wutar lantarki mai sauƙi don rama faɗuwar layin.

 transformer telephone pole high-purity copper winding

 

2.3 Tanko

transformer telephone pole tank undergo 20 kPa pressure leakage test

An kirkiro tanki dagakarfe mai laushitare da girma 1085 mm (H) × 735 mm (W) × 705 mm (L). An ƙera shi don ɗorawa sama - sanyawa tare da mai - immersed self-sanyi (ONAN). Tankin yana sanye da shi2 HV bushingkuma3 LV guda(Subtractive polarity, vector group Iio). A20 kPa an gudanar da gwajin zubar da jini na tsawon awanni 12ba tare da yabo ba kuma babu nakasu na dindindin, yana tabbatar da amincin hatimin tanki.

 

2.4 Taron Karshe

A lokacin taro na ƙarshe, babban taro - yana bushewa a hankali kuma an bushe shi da injin{1} tare da babban{2}} man mai hana ruwa (jimlar nauyin mai: 81 kg). Dukkan hanyoyin haɗin ciki, mai canza famfo, bushings, da abubuwan waje na waje (masu ɗagawa, tashoshi na ƙasa, farantin suna, maƙallan hawa) an shigar dasu amintattu. Cikakken taro yana cike da mai a ƙarƙashin injin don kawar da aljihunan iska, tabbatar da ingantaccen aikin dielectric.

transformer telephone pole final assembly

 

 

03 Gwaji

A'a.

Gwajin Abun

Naúrar

Karba

Darajoji

Ƙimar Ma'auni

Kammalawa

1

Ma'aunin Juriya

/

/

/

Wuce

2

Gwajin Rabo

/

Bambancin rabon wutar lantarki akan babban tapping: ƙasa da ko daidai da 0.5%

Alamar haɗi: Ii0

0.00

Wuce

3

Gwajin polarity

/

Ragewa

Ragewa

Wuce

4

A'a -asara da tashin hankali na halin yanzu

%

Kw

A

I0 :: bayar da ma'auni darajar

P0: ba da ƙima mai ƙima

juriyar rashin hasara shine +10%

I0 :: 根据测量值

P0: 根据测量值

空载损耗偏差+10%

0.54

0.210

1.688

Wuce

合格

5

Hasara mai ɗaukar nauyi, wutar lantarki mai ƙarfi, jimillar asara da inganci

/

kW

kW

t:85 ku

Z%: ƙimar da aka auna

Pk: ƙimar ƙima

Pt: ƙima mai ƙima

haƙuri ga impedance shine ± 10%

juriyar jimlar asarar kaya shine +6%

2.08

0.713

0.923

99.02

Wuce

6

Gwajin Karfin Wutar Lantarki

/

HV: 34KV 60s

LV: 10kV 60s

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

7

Jarrabawar Juriya da Wutar Lantarki

/

Wutar lantarki mai aiki (KV):

2 Ur

Duration(s): 40(50HZ)/48(60HZ)

Mitar (HZ): 150

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

8

Ma'aunin Resistance Insulation

HV{0}LV zuwa Ground

LV -HV zuwa Ground

HV&LV zuwa Ground

85.9

39.4

40.2

Wuce

9

Gwajin Leaka

/

Aiwatar da matsa lamba: 20kPA

Tsawon lokaci: 12h

Babu yabo kuma babu

Lalacewa

Wuce

10

Gwajin Dielectric Oil

kV

Yafi ko daidai da 45

64.62

Wuce

 

transformer telephone pole test
transformer telephone pole testing

 

 

04 Shiryawa da jigilar kaya

4.1 Shiryawa

Kafin shiryawa, sandal ɗin tarho na wutan lantarki yana zub da shi cikin aminci (ko a tura shi da mai kowane buƙatun abokin ciniki). Ana kiyaye duk bushings da na'urorin haɗi tare da danshi{1}}hujja. Ana ɗaure tafsifofi zuwa wani katako mai nauyi - ƙwanƙolin katako ko skid na ƙarfe, an ɗaure shi da kumfa, kuma an lulluɓe shi a cikin akwati na plywood mai daraja. An haɗe jaka mai hana ruwa mai ɗauke da rahoton gwaji, cikakkun bayanan farantin suna, da umarnin kulawa an haɗa su zuwa waje.

 

4.2 Shipping

Pol ɗin tarho na transfoma ya dace da jigilar ruwa, iska, ko ƙasa. Cushe girma ne dan kadan ya fi girma fiye da tanki (1085×735×705 mm). Jimlar nauyin jigilar kaya shine361 kg(ciki har da kilogiram 81 na mai mai hana ruwa). Ana ƙididdige transfoma don aiki a tsayi har zuwa2500 mda yanayin zafi har zuwa45 digiri, yana sa ya dace da yanayin yanayi daban-daban. Ana amfani da lakabin da ya dace (tsakiyar nauyi, wuraren ɗagawa, maras ƙarfi, wannan gefen sama) a cikin akwati.

 

 

05 Yanar Gizo da Takaitawa

A taƙaice, an ƙera tafsirin mu guda ɗaya{0}}ƙara - don samar da ingantaccen, inganci, kuma amintaccen rarraba wutar lantarki don aikace-aikacen kasuwanci na zama, noma, da haske. Tare da ƙaƙƙarfan gini, ingantaccen tsarin wutar lantarki, da sandar sanda mai sauƙi - Dutsen shigarwa, suna samar da farashi{4}mafifi mai inganci don faɗaɗa hanyoyin sadarwar lantarki a cikin saitunan karkara da na birni.