50 KVA Pole Dutsen Mai Canjawa 3 Phase-2.4/0.6 KV|Kanada 2025

50 KVA Pole Dutsen Mai Canjawa 3 Phase-2.4/0.6 KV|Kanada 2025

Kasar: Kanada 2025
Yawan aiki: 50kVA
Wutar lantarki: 2.4/0.6 kV
Siffar: tare da IFD da anti{0}} bin diddigi
Aika Aikace-aikacen

 

image001

Sauƙaƙe Grid ɗinku. Ƙayyade Maɗaukakin Motsa Jiki Guda Daya.

 

 

01 Gabaɗaya

1.1 Bayanin Aikin

50 kVA single fase pole mounted transformer an isar da ita zuwa Kanada a cikin 2025. Ƙarfin wutar lantarkin shine 50 kVA tare da sanyaya ONAN. Babban ƙarfin lantarki shine 2.4 kV, ƙananan ƙarfin lantarki shine 0.6 kV, sun kafa ƙungiyar vector na II6.

An ƙera shi don juriya a cikin manyan aikace-aikace{{0}ciki har da ɗimbin unguwannin birni, faffadan masu ciyar da noma, da samar da wutar lantarki mai mahimmanci na kasuwanci{1}wannan taranfoma yana haɗa Na'urar Gano Laifin Ciki (IFD) tare da Anti{2}}Tsarin sa ido. IFD tana ba da hankali na tsinkaya don canza kulawa daga mai aiki zuwa mai aiki, yana rage lokutan fita, yayin da Anti{4}}Bibiyan gidaje yana tabbatar da aiki mara ja-gora a gurɓataccen gurɓataccen ruwa ko mafi girma - wuraren da ɗanshi. Wannan fasahar dual kai tsaye tana rage jimillar farashin mallakar kayan masarufi kuma yana ƙarfafa amincin ikon al'umma.

 

 

 

1.2 Ƙayyadaddun Fasaha

167 kVA iyakacin duniya saka na'ura mai ba da hanya tsakanin hanyoyin sadarwa da takardar bayanai

Isarwa zuwa
Kanada
Shekara
2025
Nau'in
Pole mounted transformer
Daidaitawa
CSA C2.2-06
Ƙarfin Ƙarfi
50 kVA
Yawanci
60HZ
Mataki
1
Polarity
Ƙara
Nau'in Sanyi
ONAN
Babban Voltage
2.4 kv
Na biyu Voltage
0.6 kV
Abubuwan Iska
aluminum
Ƙungiyar Vector
Ii6
Impedance
2.1%(±10%)
Matsa Canji
N/A
Babu Asara Load
0.044 kW
Akan Rasa Load
0.7 kW

 

1.3 Zane

50 kVA sandar sandar da aka ɗora zane da girma.

image003 image005

 

 

02 Masana'antu

2.1 Kori

image007

Taswirar tana fasalta ainihin rauni da aka yi da hatsi{0}}ƙarfe na silicon. Wannan ƙirar da ba ta da kyau tana rage girman asara da magnetizing halin yanzu, yana haɓaka inganci. Hakanan yana rage hayaniyar aiki kuma yana haɓaka ƙarfin injin don tsawon rayuwar sabis.

 

2.2 Guda

Wannan na'urar taswira tana amfani da ci-gaba na iskar aluminium, tare da ƙaramin iskar wutar lantarki da aka yi a matsayin foil mai yadudduka da babban juzu'in wutar lantarki a matsayin na'ura mai saukar ungulu. Wannan foil -da{4}} haɗewar waya yana tabbatar da ingantaccen ƙarfin injina da ingantaccen zafi. Duk aikin ginin aluminium{6} yana ba da sauƙi mai sauƙi da tsada{7} bayani mai inganci ba tare da lalata aikin ba.

image009

 

2.3 Tanko

image011

An gina shi don karɓuwa na ƙarshe, wannan tafsiri yana da tanki wanda aka yi da bakin karfe gaba ɗaya. Wannan zaɓin abu yana ba da ingantaccen tsarin tsari da juriya ga yanayin yanayi da lalata sinadarai. Ginin da ba shi da kyau, mai waldadi yana ba da garantin yoyon aikin hujja da ingantaccen aiki a cikin mafi yawan aikace-aikacen waje.

 

2.4 Taron Karshe

Haɗin ƙarshe na gunkin karfe ɗaya{1} wanda aka ɗora shi yana haɗa na'ura mai mahimmanci{2} da - na'urar coil, an riga an gwada shi sosai, a cikin tankin bakin karfe wanda aka cika da ruwa mai tsafta. Ana yin wannan tsari mai mahimmanci a ƙarƙashin tsananin bushewa don kawar da danshi, yana tabbatar da ingantacciyar rufi. Ana shigar da mahimman abubuwan haɗin waje{7}}bushings, IFD da anti-bio{9}} sannan ana shigar dasu amintacce, suna ƙarewa a cikin cikakkiyar hatimi, mai ƙarfi, kuma abin dogaro wanda aka shirya na shekaru da yawa na sabis.

image013

 

 

03 Gwaji

Guda ɗaya{0}}ƙara{1}wanda aka ɗora tafsiri (samfurin: 50kVA-2.4/0.6kV) ta SCOTECH yana manne da ka'idojin CSA C2.2{32}}06(R2022) da CSA C802.1-13(R2022). Gwaje-gwaje na yau da kullun sun haɗa da ma'aunin juriya na iska (HV: 0.5552Ω, LV: 36.26mΩ a digiri na 31), gwajin rabo (raɓawa: -0.02% Kasa da ko daidai da 0.5%, ƙungiyar vector: Ii6), gwajin polarity (ƙari, mai yarda), gwaji mara nauyi, zuwa 18} asara: {10}% 0.95%), gwajin gwaji (asarar: 602W a digiri na 85, ƙarfin lantarki na impedance: 2.15% a cikin ± 10% haƙuri, asarar duka: 642W, inganci: 99.30% Mafi girma ko daidai da 99.20%), gwajin gwajin gwaji (LV: 10kV, babu gwajin ƙarfin lantarki tare da 60s) 150Hz don 48s, babu rushewa), ma'aunin juriya na rufi (LV-HV zuwa ƙasa: 89.9GΩ), 20kPa gwajin leak (12h, babu yatsa / nakasawa), da gwajin mai (ƙarfin dielectric: 57.4kV, danshi: 9.4mg / kg, da dai sauransu).

A'a.

Gwajin Abun

Naúrar

Karba

Darajoji

Ƙimar Ma'auni

Kammalawa

1

Ma'aunin Juriya

/

/

/

Wuce

2

Gwajin Rabo

/

Bambancin rabon ƙarfin lantarki akan babban tapping: ƙasa da ko daidai da 0.5%

Alamar haɗi: ii6

-0.02

Wuce

3

Gwajin polarity

/

Ƙara

Ƙara

Wuce

4

A'a -asara da tashin hankali na halin yanzu

%

I0 :: bayar da ma'auni darajar

0.95

Wuce

kW

P0: ba da ƙima mai ƙima

0.040

/

juriyar rashin hasara shine +15%

/

5

Load asarar, impedance ƙarfin lantarki, jimlar asarar da kuma yadda ya dace

/

t:85 ku

haƙuri ga impedance shine ± 10%

juriyar jimlar asarar kaya shine +8%

/

Wuce

%

Z%: ƙimar da aka auna

2.15

kW

Pk: ƙimar ƙima

0.602

kW

Pt: ƙima mai ƙima

0.642

%

Ingancin ba kasa da 99.20%

99.30

6

Gwajin Karfin Wutar Lantarki

/

LV: 10kV 60s

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

7

Jarrabawar Juriya da Wutar Lantarki

/

Wutar lantarki mai aiki (KV): 1.2

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

Duration(s):48

Mitar (HZ): 150

8

Ma'aunin Resistance Insulation

GΩ

LV -HV zuwa Ground

89.9

Wuce

9

Gwajin Leaka

/

matsa lamba: 20kPA

Babu yabo kuma babu

Lalacewa

Wuce

Tsawon lokaci: 12h

10

Gwajin Mai

kV

Ƙarfin Dielectric

57.4

Wuce

mg/kg

Abubuwan Danshi

9.4

%

Factor Dissipation

0.00251

mg/kg

Furan Analysis

0.03

/

Gas Chromatography Analysis

/

 

image015
image017

 

 

04 Shiryawa da jigilar kaya

4.1 Shiryawa

image019

Sansanin gwanayen zamani - guda ɗaya - ɗin da aka ɗora shi an tattara shi a cikin katako mai ƙarfi da aka yi da katako. Da farko dai, ana nannade na’urar taransifoma a cikin kwandon filastik don kare shi daga danshi da kura. Ana ƙarfafa shari'ar katako tare da sasanninta na ƙarfe don haɓaka daidaiton tsari yayin sufuri, kuma an yi masa alama da alamun kulawa masu mahimmanci (kamar alamun ɗagawa, alamun sake amfani da su) da alamun bayanin samfur. Bugu da ƙari, an sanya shari'ar a kan katako na katako, wanda ke ba da izini don saukewa da sauƙi, saukewa, da sufuri ta hanyar maɗaukaki ko pallet jacks.

 

4.2 Shipping

Don zirga-zirga a ƙarƙashin CIF Montreal,- igiyoyin wutar lantarki guda ɗaya - ana jigilar su ta ruwa. Mai siyarwar yana da alhakin yin kwangila tare da mai ɗaukar kaya, biyan kuɗin kaya zuwa tashar jiragen ruwa na Montreal, da samun inshorar ruwa. Ana jigilar na’urorin taransfoma ne daidai da ka’idojin jigilar kayayyaki na ruwa, tare da kulawa da kyau yayin lodin jirgin ruwa da wucewa don tabbatar da isa tashar jiragen ruwa na Montreal cikin yanayi mai kyau.

image021

 

 

05 Yanar Gizo da Takaitawa

A taƙaice, ɗan sandar mu guda ɗaya -ƙara - wanda aka ɗora tafsiri yana wakiltar mafi kyawun haɗakar ƙirƙira, dorewa, da inganci. Tare da ingantattun fasalulluka kamar jigon rauni don rage asara, lalata{3}} tankin bakin karfe mai juriya, da amintaccen foil na aluminum{4}}rauni, an ƙera shi don isar da kyakkyawan aiki da ƙarancin ƙimar mallaka. Wannan na'ura mai taswira ba kawai wani abu ba ne amma dogon lokaci ne, abin dogaro don sabunta kayan aikin grid ɗin ku, tabbatar da aminci da kwanciyar hankali isar da wutar lantarki ga al'ummomi na shekaru masu zuwa.

image023

 

Hot Tags: igiya saka transformer 3 lokaci, manufacturer, maroki, farashin, farashi