167 kVA Cooper Kushin Haɗa Mai Canjawa-13.8 / 0.24 kV|Guyana 2024

167 kVA Cooper Kushin Haɗa Mai Canjawa-13.8 / 0.24 kV|Guyana 2024

Kasar: Guyana 2024
Yawan aiki: 167kVA
Wutar lantarki: 13.8/0.24kV
Feature: tare da jan karfe
Aika Aikace-aikacen

 

 

image001

Canza makomar wutar lantarki -guda ɗaya{1}}ƙarshen lokaci{2}waɗanda aka ɗora mafita don ingantaccen aiki mara misaltuwa.

 

01 Gabaɗaya

1.1 Fagen Aikin

Wannan 167kVA lokaci guda na sandar sandar wutan lantarki an fitar dashi zuwa Guyana a watan Yuli, 2024. Ƙarfin wutar lantarki na busassun nau'in tasfoma shine 167 kVA, ƙarfin farko shine 13.8 kV kuma ƙarfin lantarki na biyu shine 0.24/0.12 kV. A cikin hanyar rarraba wutar lantarki da aka rarraba, transfomar lokaci guda{{7} a matsayin na'ura mai rarrabawa yana da fa'idodi masu yawa, yana iya rage tsayin ƙaramin layin rarraba wutar lantarki, rage asarar layi, haɓaka ingancin wutar lantarki. An karɓi ƙira mai girma da ƙarfin ceton coil core, injin tafsiri yana da amfani da dakatarwar da aka ɗora, ƙarami, ƙaramin saka hannun jari, rage ƙananan radius na samar da wutar lantarki, na iya rage asarar layin fiye da 60%. Mai canzawa yana ɗaukar cikakken tsarin da aka rufe, ƙarfin yin nauyi mai ƙarfi, babban aminci a cikin ci gaba da aiki da sauƙi mai sauƙi. Ya dace da tashoshin wutar lantarki na karkara, wuraren tsaunuka masu nisa, ƙauyuka warwatse, samar da noma, hasken wuta da amfani da wutar lantarki, kuma ana iya amfani da shi don makamashi{14}} ceton canjin layukan rarraba ginshiƙai a cikin hanyoyin jirgin ƙasa da hanyoyin wutar lantarki na birni.

An ƙera taswirar sandar sandar 167kVA tare da fasahar ci gaba kuma tana ɗaukar kayan inganci da abubuwan haɗin gwiwa waɗanda ke haifar da ingantaccen inganci da tsawon lokacin aiki.

Mun tabbatar da cewa kowane ɗayan rukunin da aka kawo mu ya yi cikakken gwajin karɓa. Muna ba da sabis na fakiti ɗaya{1} daga tuntuba, ambato, masana'anta, shigarwa, ƙaddamarwa, horarwa zuwa sabis na siyarwa, samfuranmu yanzu suna aiki a fiye da larduna 50 a duniya. Muna nufin zama mafi amintaccen mai samar da ku da kuma mafi kyawun abokin tarayya a cikin kasuwanci!

 

1.2 Ƙayyadaddun Fasaha

50 kVA igiya guda ɗaya na sandar sandar da aka ɗora ƙayyadaddun taswira da takaddar bayanai

Isarwa zuwa
Guyana
Shekara
2024
Nau'in
Pole Dutsen Transformer
Daidaitawa
IEEE C57.12.20
Ƙarfin Ƙarfi
167 kVA
Yawanci
60HZ
Mataki
1
Nau'in Sanyi
ONAN
Ƙungiyar Vector
li0
Babban Voltage
13.8kV
Na biyu Voltage
0.24 / 0.12 kV
Abubuwan Iska
Copper
Polarity
Ragewa
Impedance
2.5%
Hakuri
±10%
inganci
99.05%
Taɓa Range
± 2 * 2.5% tare da NLTC
Liquid insulant
Ma'adinan Mai
Babu Asara Load
0.395KW
Akan Rasa Load
1.790KW
Na'urorin haɗi
Daidaitaccen Kanfigareshan

 

1.3 Zane

167 kVA sandar sandar da aka ɗora zane da girman hoto.

pole mounted transformer drawing pole mounted transformer nameplate

 

 

02 Masana'antu

2.1 Kori

Guda --lokaci guda masu ɗorawa na wutan lantarki suna amfani da tsarin coil core, coil core an yi shi ne da takardar silicon karfe tare da babban ƙarfin maganadisu, wanda ke ba shi damar ɗaukar babban ƙarfin maganadisu a cikin ƙaramin ƙara, don haka inganta ingantaccen kayan aikin. An ƙera maɓallin coil ɗin don rage asarar ƙarfe (ciki har da asarar hysteresis da asarar eddy na yanzu), kuma tsarin masana'anta na coil core yana ba da damar haɓaka ƙirar ƙira, wanda za'a iya daidaita shi zuwa buƙatun takamaiman aikace-aikacen. Misali, ta hanyar canza lissafi, abu ko iska na ainihin, ana iya inganta aikin kayan aiki don saduwa da buƙatun fasaha daban-daban. Zane na coil core yana rage hayaniyar lantarki, wanda ke da mahimmanci musamman ga aikace-aikacen mita mai yawa. Rage amo ba kawai inganta yanayin aiki ta'aziyya na kayan aiki ba, amma kuma yana inganta ingantaccen aiki na kayan aiki. Saboda tsarin ƙirar coil core yana ba da damar ingantacciyar iska da ɓarkewar zafi, yana iya watsar da zafi sosai a cikin aikace-aikacen wuta mai girma{6}, ta haka ne ke guje wa matsalolin zafi da haɓaka aminci da rayuwar sabis na kayan aiki.

 

2.2 Guda

image007

Saboda ƙirar ƙirar sa, iska mai ƙarfi na iya rage tsangwama ta hanyar lantarki (EMI) da amo na lantarki yadda ya kamata. Tsarinsa yana sa rarrabawar filin maganadisu ya zama daidai kuma yana rage tsangwama na lantarki a cikin iska. Idan aka kwatanta da jujjuyawar coil na gargajiya, jujjuyawar foil na iya rage juriya da asarar kuzari yadda ya kamata. Faɗin fage na tsare yana ba da babban yanki na gudanarwa na yanzu kuma yana rage juriya na iska. Idan aka kwatanta da jujjuyawar coil na gargajiya, jujjuyawar foil na iya rage juriya da asarar kuzari yadda ya kamata. Faɗin fage na tsare yana ba da babban yanki na gudanarwa na yanzu kuma yana rage juriya na iska. Zane-zanen iska na iya rage ƙimar inductance na iskar, wanda ke da mahimmanci musamman ga wasu manyan aikace-aikacen mitoci-. A lokaci guda, iska mai iska na iya jure babban nauyi na yanzu.

 

2.3 Tanko

Zane-zanen tankin na'ura mai ɗaukar hoto guda ɗaya -yawan sandar sandar sandar wuta yawanci karami ne kuma ya dace da amfani a sararin samaniya{1}}iyakantaccen mahalli. Tsarinsa na ginshiƙi yana adana sarari yayin da yake samar da isasshen abin rufe fuska da zafi. Tankin mai da mai na cikin gida yana da kyakkyawan juriya na zafin jiki kuma yana iya kula da ingantaccen aiki yayin aikin na'urar. An ƙera masu canji tare da juriyar zafin mai a hankali, don tabbatar da cewa baya rushewa ko rasa ikon sa na rufewa a ƙarƙashin yanayin zafi mai girma.

image009

 

2.4 Taron Karshe

image011
image013

 

 

03 Gwaji

A'a.

Gwajin Abun

Naúrar

Karba

Darajoji

Ƙimar Ma'auni

Kammalawa

1

Ma'aunin Juriya

/

/

/

Wuce

2

Gwajin Rabo

/

Bambancin rabon ƙarfin lantarki akan babban tapping: ƙasa da ko daidai da 0.5%

Alamar haɗi: Ii0

-0.02

Wuce

3

Gwajin polarity

/

Ragewa

Ragewa

Wuce

4

A'a -asara da tashin hankali na halin yanzu

%

kW

I0 : bayar da ma'auni darajar

P0: ba da ƙima mai ƙima

juriyar rashin hasara shine +10%

0.62

0.389

Wuce

5

Hasara mai ɗaukar nauyi, wutar lantarki mai ƙarfi, jimillar asara da inganci

/

kW

kW

t:85 ku

Z%: ƙimar da aka auna

Pk: ƙimar ƙima

Pt: ƙima mai ƙima

haƙuri ga impedance shine ± 10%

juriyar jimlar asarar kaya shine +6%

2.73

1.788

2.177

99.06

Wuce

6

Gwajin Karfin Wutar Lantarki

/

HV: 34KV 60s

LV: 10kV 60s

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

7

Jarrabawar Juriya da Wutar Lantarki

/

Wutar lantarki mai aiki (KV): 2 Ur

Duration(s): 48

Mitar (HZ): 150

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

8

Ma'aunin Resistance Insulation

GΩ

HV{0}LV zuwa Ground

LV -HV zuwa Ground

HV&LV zuwa Ground

83.9

69.4

68.1

/

9

Gwajin Leaka

/

matsa lamba: 20kPA

Tsawon lokaci: 12h

Babu yabo kuma Babu Lalacewa

Wuce

10

Gwajin Dielectric Oil

kV

Yafi ko daidai da 45

53.23

Wuce

 

image015
image017

 

 

04 Shiryawa da jigilar kaya

image019
image021

 

05 Yanar Gizo da Takaitawa

Na gode don sha'awar ku da goyan bayan ku a cikin tiransifoma mai hawa guda ɗaya -lokacin lokaci{1}}! Tare da ingantaccen jujjuyawar makamashinsa, kyawawan fasalulluka na aminci, da ingantaccen aiki, wannan samfurin yana da amfani sosai ga tsarin rarraba wutar lantarki da filayen masana'antu. A koyaushe muna ɗaukar ƙa'idar inganci ta farko da kyakkyawar sabis, muna ƙoƙarin samar muku da amintaccen, eco{3}, da ingantattun hanyoyin samar da wutar lantarki. Idan kuna da wasu buƙatu ko tambayoyi, da fatan za ku iya tuntuɓar mu. Muna fatan yin aiki tare da ku don ƙirƙirar makoma mai haske tare!

image023

 

Hot Tags: cooper pad mounted transformer, manufacturer, maroki, farashin, farashi