50 kVA Mai Canjawa A kan Layin Wuta-7.97 / 0.277 kV|Kanada 2024

50 kVA Mai Canjawa A kan Layin Wuta-7.97 / 0.277 kV|Kanada 2024

Ƙasar Bayarwa: Kanada 2024
Yawan aiki: 50kVA
Wutar lantarki: 7.97/13.8Y-0.277kV
Feature: Amorphous core
Aika Aikace-aikacen

 

 

50 kva transformer on power line-front-view

Ingantacciyar, abin dogaro, da muhalli{0}abokantaka-masu iko da hanyar sadarwar rarraba ku tare da sandar taswirar 50 kVA na Scotech{3}}

 

01 Gabaɗaya

1.1 Bayanin Aikin

Wannan 50 kVA guda ɗaya - mai canzawa akan layin wuta shineƙera ta Scotechda kuma fitar dashi zuwa Kanada. Taswirar ta cika cika ka'idodin IEEE C57.12.20, yana tabbatar da ingantaccen aiki don cibiyoyin rarraba kasuwanci na zama da haske.

Wannan tsari ya haɗa da raka'a 20 na igiyoyin wuta guda 20 da aka ɗora su -ƙara{2}}, daga cikinsu akwai raka'a 5 na wannan ƙirar kVA 50. An ƙera kowace taransfoma don babban ƙarfin lantarki na 7.97/13.8Y kV da ƙarfin lantarki na biyu na 277 V, yana nuna manyan manyan injina na lantarki guda biyu da ƙananan ƙananan bushings guda biyu. An sanye tafsirin da babu{12}}mai sauya matsa lamba (NLTC) tare da kewayon ± 2×2.5%.

Mai taswirar kVA 50 akan layin wuta yana amfani da madaidaicin alloy core, yana rage asara zuwa 0.043 kW da asara zuwa 0.5 kW. Yana da makamashi - ceton da kuma kare muhalli, yana rage tsadar wutar lantarki.

Nauyin taranfomar na da nauyin kilogiram 327, ciki har da kilogiram 81 na mai. Man yana taimakawa tare da sanyaya da kuma rufewa. Girmansa shine 645 × 715 × 1115 mm. Ƙirar ƙanƙan da madaidaicin ƙira ya dace da kyau a kan sandar sandar da aka ɗora layin wutar lantarki{8}. Babban mai kama shugaban yana ba da damar haɗa kayan kariya cikin sauƙi, haɓaka aminci da aminci.

An ƙera shi tare da iska mai ƙarfi na aluminium, ƙarar polarity, da sanyaya yanayi na ONAN, wannan mai canzawa akan layin wutar lantarki yana da ƙarfi, inganci, kuma abin dogaro sosai. Gine-ginen Aluminum da ƙira mai wayo suna ba da mafita mai sassauƙa don tsarin rarraba wutar lantarki na zamani, yana tabbatar da ingantaccen makamashi da ingantaccen aiki.

 

 

 

1.2 Ƙayyadaddun Fasaha

50kVA mai canzawa akan ƙayyadaddun layin wutar lantarki da takaddar bayanai

Isarwa zuwa
Kanada
Shekara
2024
Nau'in
Juzu'i guda sandar sandar da aka saka taransifoma
Daidaitawa
IEEE C57.12.20
Ƙarfin Ƙarfi
50 kVA
Yawanci
60HZ
Polarity
Ƙara
Ƙungiyar Vector
Ii6
Babban Voltage
7.97/13.8Y kV
Na biyu Voltage
277 V
Abubuwan Iska
Aluminum
Impedance
2.1%
Hanyar sanyaya
ONAN
Matsa Canji
Farashin NLTC
Taɓa Range
±2X2.5%
Babu Asara Load
0.043 kW
Akan Rasa Load
0.5 kW
Na'urorin haɗi
Surge kama shugaba

 

 

1.3 Zane

50kVA mai canzawa akan girman layin wutar lantarki da cikakkun bayanai masu nauyi

50 kva transformer on power line-engineering-drawing 50 kva transformer on power line-nameplate

 

 

02 Masana'antu

2.1 Kori

Canjin wutar lantarki na 50kVA akan layin wutar lantarki yana amfani da asalin ƙarfe amorphous, kayan maganadisu mai laushi mai isotropic tare da babban juriya, yana rage hasara na yanzu. Idan aka kwatanta da sanyi - karfen silicon na birgima, yana rage hasarar ainihin da kashi 70 – 80%, yana samun asara -asara na 0.043 kW da asarar nauyi na 0.5 kW. Sirarriyar ribbon ɗin sa na 0.03 mm yana sauƙaƙa masana'anta, haɓaka inganci, da ba da makamashi{10}}ajiya, eco{11} mafita.

50 kva transformer on power line-amorphous-core

 

2.2 Guda

50 kVA transformer on power line-foil-wound low-voltage coils

Ingantattun ƙirar na'ura yana fasallan foil{0}}rauni -ƙarar ƙarfin lantarki da waya{2}}rauni mai girma{3}}ƙaramar wutar lantarki. Abokan ciniki na iya zaɓar aluminium don murɗa na LV, rage farashi da nauyi yayin kiyaye aminci da tsawon rayuwa kama da jan karfe. Polarity ƙari ne kuma mai taswira yana biye da rukunin Ii6, yana ba da alaƙar lokaci daidai da ingantaccen aiki.

 

2.3 Tanko

An ƙera shi don hawan igiya, an gama wannan tankin na'ura mai canzawa da launin toka mai haske kuma an gina shi daga ƙaramin ƙarfe mai inganci- ta amfani da tsarin zane don ƙirƙirar silinda. Jikin tanki yana amfani da fasaha na hatimi, tare da murfin da ƙasa da aka kafa daga tambarin takarda, rage nauyi yayin tabbatar da ƙarfin tsari.

50 kVA transformer on power line cylindrical structure tank

 

2.4 Taron Karshe

50 kVA transformer on power line active part fastening

Tsaftace Sashe Mai Aiki & Daure

1. Tsaftacewa

Cire duk ƙarfe da tarkacen ƙarfe wanda ba - ana iya gani.

2. Azumi

Ƙarƙashin karkiya da santsi.

Amintaccen taye{0}}band, makullin goro, mannen waya, goyan baya, baka, da kusoshi na allo; tabbatar da sassan rufi a layi.

Aiwatar da matsa lamba axial daidai gwargwado akan ɓangarorin HV/LV, aƙalla zagayowar 2.

Ƙarfafa wayoyi da yuwuwar ƙusoshin haɗin gwiwa tare da maƙarƙashiya mai ƙarfi.

3. Dubawa

Bincika rufi da jagora don lalacewa ko datti.

Tabbatar cewa babu sassan da suka ɓace.

Kirga duk kayan aikin da aka yi amfani da su.

 

 

03 Gwaji

Gwajin yau da kullun

1. Ma'aunin Juriya

2. Gwajin Rabo

3. Mataki -Gwajin dangantaka

4. Babu Asara Load Kuma Babu Load A Yanzu

5. Load Loss, Impedance Voltage da Inganci

6. Gwajin Karfin Wutar Lantarki

7. Gwajin Juriya da Ƙarfin Wutar Lantarki

8. Gwajin Leak tare da Matsi don Masu Canjin Ruwa na Immersed

9. Ma'aunin Juriya na Insulation

10. Gwajin Dielectric Oil

11. Gwajin Ƙarfafawar Walƙiya

 

50 kva transformer on power line-routine-test
50 kva transformer on power line-factory-test

 

Sakamakon Gwaji

A'a.

Gwajin Abun

Naúrar

Dabi'un Karɓa

Ƙimar Ma'auni

Kammalawa

1

Ma'aunin Juriya

%

/

/

Wuce

2

Gwajin Rabo

%

Bambancin rabon ƙarfin lantarki akan babban tapping: ƙasa da ko daidai da 0.5%

Alamar haɗi: ii6

-0.17

Wuce

3

zango{0}}gwajin dangantaka

/

Ƙara

Ƙara

Wuce

4

A'a -asara da tashin hankali na halin yanzu

%

kW

t:85 ku

I0 :: bayar da ma'auni darajar

P0: ba da ƙima mai ƙima

juriyar rashin hasara shine +10%

1.20(100%)

2.35(105%)

0.043(100%)

0.056(105%)

Wuce

5

Load hasarar impedance ƙarfin lantarki da inganci

%

kW

kW

t:85 ku

Z%: ƙimar da aka auna

Pk: ƙimar ƙima

Pt: ƙima mai ƙima

haƙuri ga impedance shine ± 10%

juriyar jimlar asarar kaya shine +6%

2.28

0.481

0.526

99.39

Wuce

6

Gwajin Karfin Wutar Lantarki

kV

HV: 34kV 60s

LV: 10kV 60s

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

7

Jarrabawar Juriya da Wutar Lantarki

kV

Wutar lantarki mai aiki (KV):

15.94

Duration(s):40

Mitar (HZ): 150

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

8

Gwajin Leaka

kPa

matsa lamba: 20kPA

Tsawon lokaci: 12h

Babu yabo kuma babu

Lalacewa

Wuce

9

Ma'aunin Resistance Insulation

HV&LV zuwa Ground:

51.7

/

HV{0}LV zuwa Ground

24.5

LV -HV zuwa Ground

31.5

10

Gwajin Dielectric Oil

kV

Yafi ko daidai da 45

52.05

Wuce

11

Gwajin bugun walƙiya

kV

cikakken igiyar ruwa, Rabin igiyar ruwa

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

 

 

04 Shiryawa da jigilar kaya

50 kVA transformer on power line-wooden crate packaging
50 kva transformer on power line-export-packing

 

05 Yanar Gizo da Takaitawa

50 kVAGuda ɗaya -ƙaran sandar lokaci{1}mai hawa tafsiri isar da shi zuwa Kanada a cikin 2024 yana nuna fifikon Scotech akan inganci, inganci, da ƙirƙira. Yana da core amorphous karfe core, aluminum windings, da ONAN na halitta sanyaya. Wannan ƙirar tana rage asara, tana aiki da dogaro, kuma tana adana kuzari don cibiyoyin kasuwanci na zama da haske. Ƙaƙƙarfan ƙirar sa, sandar sandar sa{4}} ɗorawa, tanki mai ƙarfi, da haɗe-haɗen shugaban mai kama shi yana tabbatar da aminci, dorewa, da sauƙin shigarwa.

Scotech yana yin babban aiki, eco{1} na'urar wuta ta zamani don tsarin wutar lantarki na zamani. Wannan aikin yana nuna ƙwarewarmu a aikin injiniya, masana'antu, da sarrafa inganci. Muna ba da samfuran abin dogaro waɗanda ke adana kuzari da haɓaka aikin grid.