75 kVA Mai Canjin Wutar Lantarki-13.8 / 0.24 kV|Guyana 2025

75 kVA Mai Canjin Wutar Lantarki-13.8 / 0.24 kV|Guyana 2025

Ƙasar Bayarwa: Guyana 2025
Yawan aiki: 75kVA
Wutar lantarki: 13.8kV-240/120V
Aika Aikace-aikacen

 

 

image001

75 kVA na'urar taswirar wutar lantarki - an amince da shi don tsayayyen rarrabawa a cikin wahala{2}}zuwa{3}}
 

01 Gabaɗaya

1.1 Fagen Aikin

Dangane da karuwar buƙatun makamashi a ƙauye da yankunan karkara na Guyana, abokin cinikinmu ya ba da odar 2025 mai zuwa don raka'a 30 na 75 kVA guda ɗaya -ƙaran sandar zamani- masu hawa tafsiri. Wannan odar ya dogara ne akan siyan da suka gabata na nau'ikan kVA 50 kuma yana nuna buƙatarsu don haɓaka kayan aiki don tallafawa faɗaɗa mazaunin gida, haɓaka aikin noma, da ayyukan wutar lantarki na karkara. Ci gaba da haɗin gwiwar yana nuna amanar da aka sanya a cikin samfuranmu don sadar da ingantaccen kuma ingantaccen hanyoyin rarraba wutar lantarki.

Waɗannan na'urorin wutar lantarki na 75 kVA an gina su zuwa ma'auni na IEEE & ANSI C57.12.00, suna nuna babban ƙarfin lantarki na 13,800 V da na biyu na biyu na 120/240 V, tare da windings na jan karfe, 2% impedance, da ± 2 × 2.5% babu - na'ura mai canzawa ta famfo. Yin aiki a 60 Hz tare da sanyaya ONAN, sun dace da hawa kan sandunan rarrabawa a cikin yankuna tare da faɗaɗa abubuwan more rayuwa da iyakantaccen damar yin amfani da ma'auni.

 

 

1.2 Ƙayyadaddun Fasaha

Ƙimar wutar lantarki ta 75kVA da takaddun bayanai

Isarwa zuwa
Guyana
Shekara
2025
Nau'in
Juzu'i guda sandar sandar da aka saka taransifoma
Daidaitawa
IEEE & ANSI C57.12.00
Ƙarfin Ƙarfi
50 kVA
Yawanci
60HZ
Polarity
Ragewa
Ƙungiyar Vector
Ii0
Babban Voltage
13800V
Na biyu Voltage
120/240V
Abubuwan Iska
KWANA
Impedance
2%
Hanyar sanyaya
ONAN
Matsa Canji
Farashin NLTC
Taɓa Range
± 2X2.5% (Jimlar kewayon =10%)
Babu Asara Load
214W
Akan Rasa Load
713W
Na'urorin haɗi
Daidaitaccen Kanfigareshan

 

1.3 Zane

Girman wutar lantarki 75kVA da cikakkun bayanai masu nauyi

image002

 

 

02 Masana'antu

2.1 Kori

Don haɓaka ƙarfin kuzari da amincin aiki, wannan jeri yana ɗaukar makamashi{0}} ceton ƙwanƙolin rauni sananne ga ƙarancin asara, ƙaramar amo, da dorewa. An lulluɓe ainihin saman don rigakafin -danshi da kariya{3}}lalata, yana tabbatar da ingantaccen aiki a muhallin waje.

image003

 

2.2 Guda

image004

Iskar HV tana ɗaukar fasahar foil ɗin tagulla don rage fitar da ɓangarori da inganta ɓarnawar zafi. An yi iskar LV ɗin da igiyar jan ƙarfe mai ɗaure tare da ƙuƙumi don haɓaka ƙarfin injina. Zane-zanenmu na coil ɗinmu suna ba da fifikon sharewa da aikin zafi na dogon lokaci{2}} amintaccen waje.

 

2.3 Tanko

Tankin yana da wani tsari da aka rufe wanda ya wuce tsattsauran gwajin ɗigon ruwa don tabbatar da kyakkyawan hatimi, yadda ya kamata ya hana ɗigon mai da shigar danshi. Anyi daga karfe mai laushi tare da shafi fenti na epoxy, yana ba da ingantaccen juriya na lalata. An sanye shi da radiyo na ɓangarorin ɓangarorin biyu, tankin yana inganta haɓakar zafin zafi, yana tabbatar da ingantaccen aikin taswira.

image005

 

2.4 Taron Karshe

image006

Taro na ƙarshe yana farawa tare da sanya ɗigon rauni da murɗa cikin tankin da aka rufe a cika shi da mai. Abubuwan da ke waje{1}da suka haɗa da bushings, bawul ɗin taimako na matsa lamba, mai sauya famfo, sassan ƙasa, da fins masu sanyaya{2}} ana ɗora su. An tsaftace rukunin, an duba saman fenti, kuma ana bincika alamomi, tasha, da bayanan farantin suna sosai.

 

 

03 Gwaji

 

Gwajin yau da kullun

1. Ma'aunin Juriya

2. Gwajin Rabo

3. Gwajin Polarity

4. Babu Asara Load Kuma Babu Load A Yanzu

5. Load Loss da Impedance Voltage

6. Gwajin Karfin Wutar Lantarki

7. Gwajin Juriya da Ƙarfin Wutar Lantarki

8. Ma'aunin Juriya na Insulation

9. Gwajin Dielectric Oil

10. Gwajin Leak tare da Matsi don Canjin Ruwa na Immersed

75kVA powerline transformer testing
75kVA powerline transformer testing 1

Matsayin Gwaji

• IEEE C57.12.20-2017

Matsayin IEEE don Sama - Nau'in Rarraba Transformers 500 kVA da Karami; Babban ƙarfin wutar lantarki, 34500 V da ƙasa; Low Voltage, 7970/13 800YV da kasa

• IEEE C57.12.90-2021

IEEE Standard Code Test for Liquid -Rarraba Rarraba, Ƙarfi, da Gudanar da Masu Canji

CSA C802.1-13 (R2022)

Ƙimar Ƙarfin Ƙarfi don Liquid{0}}Cikakken Masu Canza Rarraba

 

Sakamakon gwaji na sandar sandar - da aka ɗora tasfoma daga rukunin raka'a 30

A'a.

Gwajin Abun

Naúrar

Dabi'un Karɓa

Ƙimar Ma'auni

Kammalawa

1

Ma'aunin Juriya

/

/

/

Wuce

2

Gwajin Rabo

/

Bambancin rabon ƙarfin lantarki akan babban tapping: ƙasa da ko daidai da 0.5%

Alamar haɗi: Ii0

-0.06

Wuce

3

Gwajin polarity

/

Ragewa

Ragewa

Wuce

4

A'a -asara da tashin hankali na halin yanzu

%

kW

I0 :: bayar da ma'auni darajar

P0: ba da ƙima mai ƙima

juriyar rashin hasara shine +10%

1.66

0.185

Wuce

5

Load asarar, impedance ƙarfin lantarki, jimlar asarar da kuma yadda ya dace

/

kW

kW

t:85 ku

Z%: ƙimar da aka auna

Pk: ƙimar ƙima

Pt: ƙima mai ƙima

haƙuri ga impedance shine ± 10%

juriyar jimlar asarar kaya shine +6%

2.08

0.714

0.899

99.08

Wuce

6

Gwajin Karfin Wutar Lantarki

/

HV: 34KV 60s

LV: 10kV 60s

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

7

Jarrabawar Juriya da Wutar Lantarki

/

Wutar lantarki mai aiki (KV):

2 Ur

Duration(s): 40(50HZ)/48(60HZ)

Mitar (HZ): 150

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

8

Ma'aunin Resistance Insulation

GΩ

HV{0}LV zuwa Ground

LV -HV zuwa Ground

HV&LV zuwa Ground

101.7

36.1

42.0

Wuce

9

Gwajin Leaka

/

Aiwatar da matsa lamba: 20kPA

Tsawon lokaci: 12h

Babu yabo kuma babu

Lalacewa

Wuce

10

Gwajin Dielectric Oil

kV

Yafi ko daidai da 45

56.71

Wuce

 

 

04 Shiryawa da jigilar kaya

image008
 
image009
 

05 Yanar Gizo da Takaitawa

Wannan na'urar wutar lantarki mai nauyin kVA 75 an ƙera shi ne don biyan buƙatun wutar lantarki a ƙauye da yankunan karkara{1}} na Guyana. Ya dace da - don faɗaɗa ababen more rayuwa, samar da wutar lantarki a yankunan karkara, da haɓaka aikin gona. Tsarin maimaitawar abokin ciniki a cikin 2025 yana nuna ƙarfi mai ƙarfi ga kwanciyar hankali da aikin samfuranmu.

Mai bin ƙa'idodin Arewacin Amurka, wannan jerin na'urar taswira tana ba da ingantaccen ƙarfin kuzari da ƙarfin daidaita yanayin muhalli, yana mai da shi manufa don shigarwa akan sandunan rarrabawa a cikin ƙananan yankuna masu yawa-. Mahimmancin yana da ƙaramin -asara, kuzari{3}} ƙira don inganta ingantaccen aiki, yayin da aka inganta tsarin nada don rufewa da zubar da zafi, yana tabbatar da ingantaccen aiki a cikin yanayin waje mai ɗanɗano. Tankin da aka rufe yana ba da ingantaccen rigakafin zubar da ruwa da juriya na lalata, kuma an sanye shi da radiators don haɓaka sanyaya.

Tare da ƙira da aka mayar da hankali kan kwanciyar hankali na dogon lokaci da ƙarancin kulawa, wannan gidan wutan lantarki yana da kyau ga wuraren da ke da iyakataccen grid da samun wutar lantarki mai tsaka-tsaki, yana tallafawa samar da wadatattun kayayyaki da ci gaban ababen more rayuwa a yankunan karkara da masu tasowa.

75 kVA powerline transformer

 

 

 

Hot Tags: powerline transformer, manufacturer, maroki, farashin, tsada

Aika Aikace-aikacen