100 kVA Dutsen Wuta Mai Canjawa-24.94 / 0.347 kV|Kanada 2024
Yawan aiki: 100 kVA
Wutar lantarki: 24.94GrdY/14.4-0.347 kV
Feature: tare da IFD

Karamin Sawun Sawun, Matsakaicin Dogara - Matsakaicin Tushen Motsi don Ingantacciyar Isar da Wuta.
01 Gabaɗaya
1.1 Bayanin Aikin
100 kVA single fase pole mounted transformer an isar da ita zuwa Kanada a cikin 2025. Ƙarfin wutar lantarkin shine kVA 100 tare da sanyaya ONAN. Babban ƙarfin lantarki shine 24.94GrdY / 14.4 kV tare da ± 2 * 2.5% tapping range (NLTC), ƙarfin lantarki na biyu shine 0.347 kV, sun kafa ƙungiyar vector na Ii6.
Wannan 100 kVA sandal -wanda aka ɗora wutar lantarki an ƙera shi don haɓaka ƙarfin aiki mai ƙarfi a cikin hanyoyin sadarwar lantarki, haɗa aminci, aminci, da daidaitawa don aikace-aikacen karkara da na birni. An ƙera shi don jure buƙatun muhalli da yanayin aiki, ya haɗa mahimman abubuwan kariya da aiki don tabbatar da sabis mara yankewa da tsawaita rayuwar aiki.
Maɓalli masu mahimmanci sun haɗa da na'urar taimakon matsa lamba don fitar da matsa lamba a cikin aminci idan akwai kuskuren ciki, rage haɗarin fashewar tanki. Haɗin kai goyon bayan mai kama yana ba da amintaccen hawa don masu kamawa, yana haɓaka kariya daga faɗuwar walƙiya da ƙarfin wutar lantarki. Don gano kuskuren ci gaba, na'urar ta atomatik sanye take da na'urar gano kuskuren ciki (IFD), wanda ke ba da damar gano abubuwan da ba su dace ba da wuri don hana gazawar bala'i. Bugu da ƙari, mai sauya fam ɗin kewayawa- yana ba da damar daidaita wutar lantarki mai sassauƙa (lokacin da aka ƙara kuzari), yana tabbatar da kyakkyawan aiki a ƙarƙashin yanayi daban-daban.
An gina shi don dorewa da sauƙi na kulawa, wannan na'ura mai canzawa yana ba da ingantaccen rarraba makamashi yayin da yake ba da fifiko ga aminci da ƙarfin aiki, yana mai da shi mafita mai kyau don kayan aikin wutar lantarki na zamani.
1.2 Ƙayyadaddun Fasaha
167 kVA iyakacin duniya saka na'ura mai ba da hanya tsakanin hanyoyin sadarwa da takardar bayanai
|
Isarwa zuwa
Kanada
|
|
Shekara
2025
|
|
Nau'in
Pole mounted transformer
|
|
Daidaitawa
CSA C2.2-06
|
|
Ƙarfin Ƙarfi
100 kVA
|
|
Yawanci
60HZ
|
|
Mataki
1
|
|
Polarity
Ƙara
|
|
Nau'in Sanyi
ONAN
|
|
Babban Voltage
24.94GrdY/14.4kV
|
|
Na biyu Voltage
0.347 kV
|
|
Abubuwan Iska
Aluminum
|
|
Matsala ta kusurwa
Ii6
|
|
Impedance
3%
|
|
Matsa Canji
Farashin NLTC
|
|
Taɓa Range
±2*2.5%
|
|
Babu Asara Load
0.195 kW
|
|
Akan Rasa Load
1.52 kW
|
|
Na'urorin haɗi
Daidaitaccen Kanfigareshan
|
1.3 Zane
167 kVA sandar sandar da aka ɗora zane da girman hoto.
![]() |
![]() |
02 Masana'antu
2.1 Kori
Silicon ɗin tsit ɗin yana ci gaba da yin rauni ta amfani da injunan daidaitaccen injin, yana haifar da haɗin gwiwa{0}} kyauta tare da hanyar maganadisu iri ɗaya, yana rage hasara da hayaniya. Ƙirar mara sumul tana rage girman magnetostriction -jawowar girgiza, yana haifar da ƙananan matakan amo 5- dB 10 fiye da laminated. Hanyar maganadisu mai ma'ana tana haɓaka juriya ga son rai na DC, yana mai da shi dacewa da cibiyoyin rarrabawa tare da manyan juzu'in wutar lantarki. Ƙarfin sararin samaniya na ƙwanƙolin rauni ya dace da ƙaƙƙarfan buƙatun buƙatun sandar sandar da aka ɗora su{7}}wayoyin da aka ɗora, masu dacewa da nau'in harsashi-nau'i da shirye-shiryen iska mai tushe.

2.2 Guda

Pole{0}}wayoyin da aka ɗora su sun ɗauki ingantacciyar ƙirar aluminum LV + tagulla waya HV mai iska: Gefen LV yana amfani da foil aluminum mai rauni (0.2–1.0mm) don mafi kyawun sanyaya, ingancin farashi, da gajeriyar juriya, yayin da gefen HV yana ɗaukar Layer rauni tagulla windings don haɓaka ƙarfin ƙarfi da ƙimar ƙarfin lantarki (5 zuwa ƙimar ƙarfin lantarki). Katangar allo mai rufewa da ɓacin rai yana haɓaka ƙarfin dielectric. Babban yanki na foil yana inganta ɓarkewar zafi, kuma babban yawan jan ƙarfe na yanzu yana tabbatar da ƙarancin ƙarfi. Wannan ƙayyadaddun bayani yana daidaita tattalin arziƙin (Al) da amintacce (Cu), yana rage asara{9}} da kashi 15-25%, yana mai da shi manufa don hanyoyin rarrabawa.
2.3 Tanko
Samfuran mu suna bin ka'idodin juriya na C4. Haɓaka fasaha masu zuwa suna tabbatar da kyakkyawan aiki:
1- Ƙarfafa Sarrafa Tsari
Ana ɗaukar ingantattun hanyoyin sarrafa ƙasa, tare da tsaftataccen tsaftacewa da hanyoyin magani na sinadarai don kawar da gurɓataccen abu gaba ɗaya yayin da ke ba da tabbacin cikakken yarda da ƙayyadaddun kauri.
2- Inganta Tsari
Ana amfani da cikakken{0} fasahar ɗinki na ɗinki zuwa welds masu mahimmanci, yadda ya kamata yana toshe shigar danshi cikin abubuwan da suka haɗa da na'ura mai canzawa na ciki da inganta ingantaccen aiki na dogon lokaci-.

2.4 Taron Karshe

1. Shigar da iska:Zamar da babban{0}}ƙarfin wutar lantarki da ƙaramar iskar wutar lantarki zuwa kan lamintaccen cibiya, tabbatar da daidaitawar rufin da ya dace da ingantaccen gyara injina.
2. Haɗin Wutar Lantarki:Haɗa iska tana kaiwa zuwa mai canza famfo, bushings, da sauran abubuwan haɗin gwiwa, sannan tabbatar da juriyar lamba.
3. Core -Bushewar Naɗi:Sanya sashin da aka haɗa (core + windings) a cikin tanda mai bushewa don dumama ruwa don cire danshi da tabbatar da ingancin rufi.
4. Wurin Tanki:Sanya busasshen sashin aiki a cikin tanki kuma a kiyaye shi tare da kusoshi na tushe.
5. Shigar Na'ura:Dutsen bushings, IFD, bawul ɗin taimako na matsa lamba, da sauran kayan haɗi, suna rufe duk haɗin gwiwa.
6. Ciko Mai & Rufewa:Vacuum{0}}cika mai mai hana ruwa zuwa matakin da aka kayyade, sannan a gwada ingancin mai da tsantsar tanki bayan an daidaita.
03 Gwaji
|
A'a. |
Gwajin Abun |
Naúrar |
Dabi'un Karɓa |
Ƙimar Ma'auni |
Kammalawa |
|
1 |
Ma'aunin Juriya |
/ |
/ |
/ |
Wuce |
|
2 |
Gwajin Rabo |
/ |
Bambancin rabon ƙarfin lantarki akan babban tapping: ƙasa da ko daidai da 0.5% Alamar haɗi: ii6 |
-0.04 |
Wuce |
|
3 |
Gwajin polarity |
/ |
Ƙara |
Ƙara |
Wuce |
|
4 |
A'a -asara da tashin hankali na halin yanzu |
% |
I0 :: bayar da ƙima (100%) |
0.17 |
Wuce |
|
kW |
P0: bayar da ƙima (100%) |
0.161 |
|||
|
% |
I0 :: bayar da ƙima (105%) |
0.33 |
|||
|
kW |
P0: bayar da ƙima (105%) |
0.204 |
|||
|
/ |
juriyar rashin hasara shine +15% |
/ |
|||
|
5 |
Hasara mai ɗaukar nauyi, wutar lantarki mai ƙarfi, jimillar asara da inganci |
/ |
t:85 ku haƙuri ga impedance shine ± 7.5% juriyar jimlar asarar kaya shine +8% |
/ |
Wuce |
|
% |
Z%: ƙimar da aka auna |
3.16 |
|||
|
kW |
Pk: ƙimar ƙima |
1.377 |
|||
|
kW |
Pt: ƙima mai ƙima |
1.538 |
|||
|
% |
Ingancin ba kasa da 98.94% |
99.07 |
|||
|
6 |
Gwajin Karfin Wutar Lantarki |
/ |
LV: 10kV 60s |
Babu rushewar ƙarfin gwajin da ke faruwa |
Wuce |
|
7 |
Jarrabawar Juriya da Wutar Lantarki |
/ |
Wutar lantarki mai aiki (KV):2Ur |
Babu rushewar ƙarfin gwajin da ke faruwa |
Wuce |
|
Duration(s):48 |
|||||
|
Mitar (HZ): 150 |
|||||
|
8 |
Ma'aunin Resistance Insulation |
GΩ |
LV -HV zuwa Ground |
43.3 |
Wuce |
|
9 |
Gwajin Leaka |
/ |
Aiwatar da matsa lamba: 20kPA |
Babu yabo kuma babu Lalacewa |
Wuce |
|
Tsawon lokaci: 12h |
|||||
|
10 |
Gwajin Mai |
kV |
Ƙarfin Dielectric |
57.4 |
Wuce |
|
mg/kg |
Abubuwan Danshi |
9.3 |
|||
|
% |
Factor Dissipation |
0.00254 |
|||
|
mg/kg |
Furan Analysis |
0.03 |
|||
|
/ |
Gas Chromatography Analysis |
/ |


04 Shiryawa da jigilar kaya
4.1 Shiryawa
Ƙaƙƙarfan igiya ɗaya -iyali{1} da aka ɗora tasfoma yana cike a cikin wani akwati na katako na lalata, wanda aka tanadar cikin ciki tare da ƙugiya da gigita{3}}ƙarashin ɓangarorin roba, da sassa masu rauni ana kiyaye su da kumfa. Akwatin an lulluɓe shi da masana'anta mai juriya da ruwan sama, an ɗaure shi da madaurin nailan, kuma an rufe rigunan. Ana haɗa ramukan samun iska a sama. Marubucin yana da alamun ɗagawa, desiccants, da jakar takarda mai hana ruwa, yana tabbatar da dacewa da jigilar ruwa da waje.

4.2 Shipping

Ƙarƙashin sharuɗɗan CIF, mai siyar ya aika da sandar sandar{0}yana hawa tafsiri zuwa tashar jirgin ruwa ta Montreal, Kanada, wanda ke ɗaukar farashi, inshorar ruwa, da kaya. Ana ƙera masu canji amintacce (firam ɗin itace/karfe) kuma ana jigilar su ta jigilar kaya ta teku (kwantena ko ɓarna), tare da All Risks inshora. Bayan isowa, mai siye yana kula da izinin kwastam da jigilar manyan motoci na ƙarshe. Mahimman takaddun sun haɗa da B/L, daftarin kasuwanci, lissafin tattarawa, da takardar shaidar inshora. Kalubalen sun haɗa da kariyar yanayin hunturu da jinkirin kwastam.
05 Yanar Gizo da Takaitawa
Pole{0}}wayoyin da aka ɗora tafsiri suna ba da ƙaƙƙarfan, farashi{1}mai inganci, kuma ingantaccen bayani don rarraba wutar lantarki a cikin hanyoyin sadarwa na birane da karkara. An tsara shi don dorewa da sauƙi mai sauƙi, suna tabbatar da ingantaccen canjin wutar lantarki tare da ƙarancin kulawa. Ko don kayan aiki, aikace-aikacen masana'antu, ko haɗakarwar makamashi mai sabuntawa, injiniyoyinmu sun cika ka'idojin ƙasa da ƙasa (IEEE, IEC, CSA) kuma an gina su don matsananciyar yanayi. Tuntube mu a yau don keɓance hanyoyin warwarewa waɗanda suka dace da buƙatun grid ɗin ku.

Hot Tags: Pole Dutsen Transformer, Manufacturer, Supplier, Price, Cost
You Might Also Like
150 kVA Pmt Mai Canjawa-19.92 / 0.24 * 0.12 kV|Kanad...
500 kVA Mai Canja Wuta-4.16 / 0.6 kV|Kanada 2024
50 kVA Single Phase Pole Mounted Distribution Transf...
100 kVA Mai Canja Wuta Mai Wuta-13.8 / 0.24 kV|Guyan...
50 kVA Mai Canjawa Akan Ƙarfin Wuta-7.97 / 0.12 / 0....
50 kVA Mai Canjawa A kan Layin Wuta-7.97 / 0.277 kV|...
Aika Aikace-aikacen