500 kVA Mai Canja Wuta-4.16 / 0.6 kV|Kanada 2024

500 kVA Mai Canja Wuta-4.16 / 0.6 kV|Kanada 2024

Kasar: Kanada 2024
Yawan aiki: 500kVA
Wutar lantarki: 4.16/0.6kV
Feature: tare da IFD
Aika Aikace-aikacen

 

 

500 kVA pole transformer

Zabin abin dogaro, ƙarfin da ba ya katsewa – Guda ɗaya{0}}ƙaran sandar lokaci{1}wanda aka ɗora tafsiri yana ƙarfafa kowane layi.

 

01 Gabaɗaya

1.1 Fagen Aikin

Wannan 500 kVAWurin Wuta Mai Wuta Mai Wuta Mai Wutaan kai kasar Canada ne a shekarar 2024. Nau’in na’ura mai suna Platform Transformer, wanda kasansa yana da dandali don tallafa masa, Babban karfin wutar lantarki na farko shine 4.16GrdY/2.4kV sannan kuma na biyu shine 0.6kV. Ƙarfin ya fi girma fiye da na al'ada. An tsara shi bisa ga daidaitattun CSA C2.1. Wannan na'ura mai ɗaukar hoto guda 500 kVA mai nauyin kilogiram 2150 an sanya shi akan dandamali. Mun tsara shi tare da fasaharmu ta ci gaba da kayan aikin iska mai inganci don cimma asarar nauyi 3 kW. Matsala shine 4% tare da hanyar sanyaya ONAN.

Pole Transformer wani muhimmin kayan aiki ne da ake amfani da shi a tsarin wutar lantarki, wanda galibi ana amfani dashi don canza ƙarfin wutar lantarki mai ƙarfi{0}ƙarashin wutar lantarki zuwa ƙananan ƙarfin lantarki don biyan buƙatun matakan ƙarfin lantarki daban-daban. Yawancin lokaci ana shigar da shi akan sandunan watsa wutar lantarki da grid rarraba, don haka sunan. Za a iya taƙaita ƙa'idodin aiki na injin wutan lantarki da aka ɗora shi azaman shigar da wutar lantarki. Lokacin da babban ƙarfin wutan lantarki ke gudana ta cikin babban ƙarfin wutan lantarki, filin maganadisu yana haifar da juzu'in maganadisu a cikin tsakiyar ƙarfe. Wannan motsi na maganadisu zai ƙara haifar da ƙarfin lantarki a cikin ƙaramar na'ura mai ƙarfi -, don haka yana mai da babban{7}} ƙarfin wutar lantarki zuwa ƙananan ƙarfin lantarki- ƙarfin lantarki.

Pole mounted transformersana amfani da su sosai a tsarin watsa wutar lantarki da rarrabawa. Yawancin lokaci ana shigar da su akan sandunan watsa wutar lantarki da grid ɗin rarrabawa kuma ana amfani da su don canza ƙarfin wutar lantarki mai ƙarfi{1} zuwa ƙaramin ƙarfin lantarki mai ƙarfi da ya dace da amfanin gida, masana'antu da kasuwanci. Hakanan za'a iya amfani da tasfotoci masu ɗorawa a cikin tashoshin wutar lantarki, masana'antu da ma'adinai, gine-ginen birane da sauran fannoni. Silinda mai canzawa yana da ƙananan girman, haske a nauyi kuma mai sauƙi don shigarwa da kulawa. Ƙananan farashi, dacewa da ƙanana da matsakaici{6}} girman watsa wutar lantarki da tsarin rarrabawa. Ingantacciyar jujjuyawar injin da aka ɗora da wuta yana da girma kuma ana iya rage asarar makamashi yadda ya kamata.

Mu 500 kVA na'urar wutan lantarki an ƙera shi tare da fasaha na ci gaba kuma yana ɗaukar kayan inganci da kayan haɗin gwiwa wanda ke haifar da ingantaccen inganci da tsawon lokacin aiki.

 

 

1.2 Ƙayyadaddun Fasaha

500 kVA na'ura mai ba da hanya tsakanin hanyoyin sadarwa da takaddun bayanai

Isarwa zuwa
Kudancin Amurka
Shekara
2024
Nau'in
Pole mounted transformer
Daidaitawa
Bayanan Bayani na CSA2.1
Ƙarfin Ƙarfi
500kVA
Yawanci
60HZ
Mataki
1
Nau'in Sanyi
ONAN
Babban Voltage
4.16GrdY/2.4kV
Na biyu Voltage
0.6 kV
Abubuwan Iska
Aluminum
Matsala ta kusurwa
YNyn0
Impedance
3%
Matsa Canji
Farashin NLTC
Taɓa Range
±2*2.5%
Babu Asara Load
0.08KW
Akan Rasa Load
1.27KW
Na'urorin haɗi
Daidaitaccen Kanfigareshan

 

1.3 Zane

500 kVA igiyar wutar lantarki zane da girman zane.

500 kVA pole transformer diagram 500 kVA pole transformer nameplate

 

 

02 Masana'antu

2.1 Kori

Kayayyakin da ake amfani da su don abin da aka yi birgima ultra -sanyi sanyi{1}} silicon karfe sheet ɗin birgima tare da ɗorewa mai ƙarfi da tsiri mai taushi kamar permalloy. A kauri na silicon karfe takardar ne 0.18 ~ 0.30; The kauri daga cikin Permalloy tsiri ne 0.03 ~ 0.10mm. Ɗaukar ƙanana da matsakaita{8}} na'urar taswira a matsayin misali, yin amfani da abin da aka yi birgima yana da fa'idodi masu zuwa:

1) A ƙarƙashin sharuɗɗa iri ɗaya, babu - ɗora asarar ainihin abin da aka yi birgima yana raguwa da kashi 7% zuwa 10% idan aka kwatanta da tushen da aka tara; Babu - za'a iya rage yawan lodawa da kashi 50%~75%.

2) The rolled core ana iya yin shi da sirara mai girman gaske -ciwon sanyi - mirgine silikon karfe zanen gado, wanda zai iya samar da tasfoma tare da ƙananan asara.

3) Babban abin da aka yi birgima yana da kyakkyawan aiki, babu sharar fage, kuma ƙimar amfani kusan kusan 100%. Hakanan yana iya ɗaukar aikin injina, yana kawar da tsarin tarawa, kuma ingancin samarwa ya ninka sau 5 zuwa 10 sama da na abin da ake tarawa.

4) Ƙaƙwalwar na'ura mai jujjuyawa kanta cikakke ne, baya buƙatar gyarawa ta hanyar ƙulla sassa na tallafi, kuma ba shi da haɗin gwiwa, don haka a ƙarƙashin yanayi guda ɗaya kamar yadda aka ɗora, za'a iya rage sautin wutar lantarki ta 5 ~ 10dB.

5) Ƙididdigar tsarin na'ura mai jujjuyawa guda ɗaya -aramin wutan lantarki yana kusan 1.1; Uku{3}}asa da 1.15; Don stacking baƙin ƙarfe coefficients, da tsari coefficient na kananan iya aiki ne game da 1.45, da kuma tsari coefficient na babban iya aiki ne game da 1.15. Don haka, abin da aka yi nadi ya dace musamman don ƙanana da matsakaita{7}} na'urorin wutar lantarki.

pole transformer ultra-thin cold-rolled silicon steel sheet core

 

2.2 Guda

pole transformer electrical coils

Siffar lebur na ƙananan iska mai ƙarfi - yana ƙara sararin saman iskar kuma yana taimakawa wajen haɓaka haɓakar zafi. Sabili da haka, a ƙarƙashin babban nauyin kaya, mai canzawa yana aiki a ƙananan zafin jiki, yana ƙara tsawon rayuwar kayan aiki. Babban ɓangaren ƙaramar iska mai ƙarfi - na iya rage asarar da ake yi a yanzu (asara I²R) da rage hasarar da ake samu a halin yanzu a cikin iskar, inganta ƙarfin ƙarfin gaba ɗaya da haɓaka aikin taswira. Saboda tsarinsa na tsari, ƙaramin -ƙarar iska yana da mafi girman gajeriyar juriya a halin yanzu kuma yana iya jure juriya nan take ba tare da zafi ko lalacewa ba, don haka inganta aminci da kwanciyar hankali na taswirar. Zane na tsare iska na iya yadda ya kamata kashe amo a lokacin aiki, musamman a cikin halin yanzu high halin yanzu, da amo kula da aikin ne mafi bayyananne, dace da aikace-aikace tare da amo bukatun. Haɗin ƙira na ƙananan juzu'i na ƙananan ƙarfin ƙarfin lantarki da iska mai ƙarfi - yana sanya rarrabawar filin maganadisu ya zama iri ɗaya, yana rage yanayin ɗigon maganadisu, yana haɓaka ƙarfin lantarki na na'ura mai canzawa, kuma yana rage tsangwama ga kayan lantarki da ke kewaye.

 

2.3 Tanko

Tankin cylindrical yana amfani da ma'auni mai ma'ana don tarwatsa matsa lamba na ciki da na waje yadda ya kamata, haɓaka ƙarfin tsarin tanki, da rage haɗarin nakasawa da lalacewa ta hanyar canjin zafin jiki ko haɓakar kaya. Tsarin Silinda ya sa man ya zama mafi daidaituwa kuma yana iya rage yawan zafi a cikin mai yadda ya kamata. Ta wannan hanyar, za ta iya tabbatar da cewa ana ci gaba da yaɗuwar mai na taransfoma, ta yadda za a fi rarraba zafi da ɓarkewa, wanda ke taimakawa wajen inganta amincin na'urar. Tankin mai cylindrical yana da mafi kyawun aikin girgizar ƙasa. Ƙarƙashin aikin girgizar ƙasa ko wasu dakarun waje, tsarin madauwari yana da ingantacciyar kwanciyar hankali a cikin aikin injiniya, wanda zai iya kare abubuwan da ke cikin ciki da kuma rage haɗarin lalacewar na'ura. Tsarin tanki na silinda yawanci yana da ingantacciyar hanyar rufewa, wanda zai iya hana kwararar mai da kyau yadda ya kamata. Haka kuma, tana iya hana shigowar gurbatacciyar iska kamar iska da danshi, da kuma kiyaye inganci da rayuwar da ake amfani da shi na insulating mai.

cylindrical tank of single pole transformer

 

2.4 Taron Karshe

500 kVA pole transformer active part
500 kVA pole transformer finall assembly

 

 

03 Gwaji

A'a.

Gwajin Abun

Naúrar

Karba

Darajoji

Ƙimar Ma'auni

Kammalawa

1

Ma'aunin Juriya

/

/

/

Wuce

2

Gwajin Rabo

/

Bambancin rabon ƙarfin lantarki akan babban tapping: ƙasa da ko daidai da 0.5%

Alamar haɗi: ii6

0.00

Wuce

3

Gwajin polarity

/

Ƙara

Ƙara

Wuce

4

A'a -asara da tashin hankali na halin yanzu

%

I0 :: bayar da ma'auni darajar

0.22

Wuce

kW

P0: ba da ƙima mai ƙima

0.836

/

Haƙuri don asarar nauyi shine ± 15%

/

5

Load asarar, impedance ƙarfin lantarki, jimlar asarar da kuma yadda ya dace

/

t:85 ku

haƙuri ga impedance shine ± 7.5%

Haƙuri don asarar nauyi shine ± 8%

/

Wuce

%

Z%: ƙimar da aka auna

4.05

kW

Pk: ƙimar ƙima

2.887

kW

Pt: ƙima mai ƙima

3.723

%

Ingancin ba kasa da 99.26%

99.41

6

Gwajin Karfin Wutar Lantarki

/

LV: 10kV 60s

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

7

Jarrabawar Juriya da Wutar Lantarki

/

Wutar lantarki mai aiki (kV): 4.8

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

Duration(s): 60

Mitar (HZ): 120

8

Ma'aunin Resistance Insulation

LV -HV zuwa Ground:

2.65

Wuce

9

Gwajin Leaka

/

matsa lamba: 20kPA

Babu yabo kuma babu

Lalacewa

Wuce

Tsawon lokaci: 12h

10

Gwajin Mai

kV

Ƙarfin Dielectric

56.4

Wuce

mg/kg

Abubuwan Danshi

9.5

%

Factor Dissipation

0.00206

mg/kg

Furan Analysis

0.03

/

Gas Chromatography Analysis

/

 

500 kVA pole transformer testing
500 kVA pole transformer FAT

 

 

04 Shiryawa da jigilar kaya

500 kVA pole transformer packing

500 kVA pole mounted transformer shipping

 

05 Yanar Gizo da Takaitawa

Na gode don sha'awar ku da goyan bayan ku a cikin mu guda ɗaya{0}}Phase pole transformer! Tare da kyakkyawan aiki, aiki mai tsayi, da ingantaccen inganci, samfurinmu ya zama zaɓi mai kyau a cikin watsa wutar lantarki da filin rarraba. Za mu ci gaba da kiyaye ƙa'idodin ƙirƙira fasaha da ingantaccen inganci don samar muku da amintattun hanyoyin samar da wutar lantarki. Muna fatan yin aiki tare da ku don ƙirƙirar makoma mai haske tare! Idan kuna da wata tambaya ko buƙatu,don Allah a ji daɗin tuntuɓar mu.

500 kVA pole transformer manufacturer

 

Hot Tags: pole transformer, manufacturer, maroki, farashin, farashi