150 kVA Pmt Mai Canjawa-19.92 / 0.24 * 0.12 kV|Kanada 2024
Yawan aiki: 150 kVA
Wutar lantarki: 19.92/0.24 kV
Feature:tare da tallafin kama

Makamashi{0}} ingantaccen aiki kuma mai girma{1}, yana tsara makoma mai dorewa! Zaɓi sandal ɗin lokaci ɗaya{2}}{3} wanda aka ɗora tasfoma don tallafawa ayyukan ku na kore.
01 Gabaɗaya
1.1 Fagen Aikin
150 kVA single fase pole mounted transformer an isar da ita zuwa Kanada a cikin 2024. Ƙarfin da aka ƙididdigewa na na'urar shine 150 kVA tare da sanyaya ONAN. Babban ƙarfin lantarki shine 19.92 kV tare da ± 2 * 2.5% tapping range (NLTC), ƙarfin lantarki na biyu shine 0.12 / 0.24 kV, sun kafa ƙungiyar vector na Ii0.
Guda ɗaya -iyali mai ɗorawa na wuta, nau'in transfoma ne da aka saba amfani da shi a tsarin rarrabawa, da farko an sanya shi akan sandunan kayan aiki. Babban aikinsa shine canza babban ƙarfin lantarki zuwa ƙananan ƙarfin lantarki don aminci da ingantaccen amfani ta masu amfani. Ana amfani da wannan taransfoma sosai a hanyoyin sadarwa na yankunan karkara da birane, musamman a wuraren da ake da karancin wutar lantarki, kamar wuraren zama, noma, da kananan masana'antu. Tunda an shigar da na'urorin wutan lantarki{4} akan sandunan kayan aiki, suna adana sararin ƙasa yadda ya kamata kuma suna rage farashin ababen more rayuwa da ke da alaƙa da shimfiɗar kebul. An sanye su da na'urori masu kariya, waɗannan na'urorin lantarki na iya hana gajeriyar kewayawa, yin lodi, da sauran kurakurai, haɓaka aminci da amincin aiki.
1.2 Ƙayyadaddun Fasaha
150 kVA guda lokaci iyakacin duniya saka tasfo bayani dalla-dalla da bayanai takardar
|
Isarwa zuwa
Kanada
|
|
Shekara
2024
|
|
Nau'in
Juzu'i guda sandar sandar da aka saka taransifoma
|
|
Daidaitawa
IEEE C57.12.00
|
|
Ƙarfin Ƙarfi
150 kVA
|
|
Yawanci
60HZ
|
|
Mataki
Single
|
|
Nau'in Sanyi
ONAN
|
|
Babban Voltage
19.92 kV
|
|
Na biyu Voltage
0.24 / 0.12 kV
|
|
Abubuwan Iska
Aluminum
|
|
Polarity
Ragewa
|
|
Impedance
Yafi ko daidai 1.5%
|
|
Matsa Canji
Farashin NLTC
|
|
Taɓa Range
±2*2.5%
|
|
Babu Asara Load
0.32KW
|
|
Akan Rasa Load
3.3KW
|
|
Na'urorin haɗi
Daidaitaccen Kanfigareshan
|
|
Jawabi
N/A
|
1.3 Zane
150 kVA igiyar lokaci guda ɗaya wanda aka ɗora ma'aunin wuta da cikakkun bayanai masu nauyi
![]() |
![]() |
02 Masana'antu
2.1 Polarity
Polarity zai zama ƙari ga duk masu tasforan lokaci ɗaya- masu girma dabam 200 kVA kuma ƙarami suna da babban -voltagewindings 8660 V da ƙasa, Polarity zai zama mai ragi ga duk sauran tasfofi guda ɗaya{4}}.

2.2 Guda

Coil na farko yana karɓar ƙarfin shigarwa, yayin da na'ura na biyu ke fitar da wutar lantarki da aka canza. Ya danganta da juzu'in jujjuyawar coils ɗin, mai sauya fasalin zai iya hawa sama ko ya sauko da ƙarfin lantarki. Coils ba kawai suna canza ƙarfin lantarki ba har ma suna watsa halin yanzu. Girman na yanzu a cikin coils na farko da na sakandare ya yi daidai da adadin jujjuyawar su, yana sauƙaƙe sauyin halin yanzu. Zane na coils ya kamata yayi la'akari da madaidaicin impedance tare da kaya don tabbatar da iyakar wutar lantarki da ingantaccen aikin aiki.
2.3 Tushen tanki
Ƙarƙashin tanadin ƙasan wutar lantarki mai ƙanƙan - zai ƙunshi kushin ƙarfe tare da rami mai 1/2-in-13-NC, zurfin 11 mm (0.44 in). The zaren za a kiyaye ta wani lalata-resistant flanged kofin shigar a cikin threaded bude na kasa kushin da ba a amfani da.The transformer cover za a electrically bonded externally zuwa tanki, The wurin da bond ba zai tsoma baki tare da dagawa lugs.

2.4 walƙiya arrester hawa tanadi

Shiri: Tsaftace da duba duk abubuwan da aka gyara, gami da gidajen wuta, core, windings, kayan rufewa, da mai sanyaya.
Core Installation: Haɗa da kuma kiyaye ainihin zuwa kasan gidaje, tabbatar da kwanciyar hankali.
Shigar da iska: Shigar da babban -ƙarfin wutar lantarki da ƙananan{1}}ƙarar iskar wutar lantarki a kan ainihin ƙayyadaddun ƙira, yana tabbatar da insulation mai kyau tsakanin iskar.
Cikon Mai Insulation: Zuba man hana ruwa a cikin gidaje, tabbatar da cewa ya nutsar da iska gaba ɗaya kuma yana kawar da duk wani iska.
Rufe Gidaje: Shigarwa da kuma rufe ɓangaren sama na gidaje, tabbatar da cewa an kare kayan ciki daga danshi da gurɓatawa.
03 Gwaji
Wurin da za a gwada zai zama sabon naúrar, cikakke tare da ainihinsa da coil, bushings, da dai sauransu. Za a gudanar da gwajin a yanayin zafi tare da matsa lamba na farko daga 42 kPa zuwa 48 kPa (ma'auni) (6 psigto 7 psig). Tasfomar da ake gwadawa za ta kasance amintacciya ta goyan bayan saƙon goyan bayanta kuma a dora ta daga ƙasa. Bukatun gwaji na leEEE Std C37.40 da leEEE Std C37.41 za a bi. Gwajin gwajin yanzu zai kasance daidai. Za a yi amfani da sabon shinge don kowane aikin gwaji, Aikin gwaji zai ƙunshi gwaji biyu. Gwajin na biyu za a cim ma ta ta hanyar sake amfani da shi, “kamar yadda masana’anta suka ayyana,” duk abubuwan da ke cikin yadi. Za a yi tanadi don fitar da iska cikin aminci duk wani matsin lamba na ciki da ya rage bayan kowace gwaji.


04 Wasu
4.1 na'urar taimakon matsa lamba
na'urar agajin matsa lamba yawanci tana ƙunshe da diaphragm mai sassauƙa ko matsa lamba{0}}aƙƙarfan murfin huɗa da aka sanya akan tankin wuta. A yayin da wani mummunan lahani na lantarki na ciki, saurin samar da iskar gas yana haifar da tashin hankali kwatsam a cikin tanki. An ƙera PRD don fashe ko buɗewa a wani ƙayyadadden matsa lamba, ta haka nan take kuma cikin aminci tana fitar da iskar gas mai ƙarfi da samfuran bazuwar yanayi zuwa sararin samaniya. Wannan sakin da aka sarrafa yana hana mummunan fashewar babban tanki, yana rage yiwuwar haɗarin wuta, kuma yana taimakawa wajen kare kayan aiki kusa. Na'urar galibi tana haɗa tuta ko mai nuna alama da ke tafiya a bayyane yayin aiki don siginar cewa wani abin damuwa ya faru.

4.2 bugu

Bushing ɗin da aka ɗora akan kushin ({0}}waɗanda aka ɗora tafsirin wutan lantarki abu ne mai mahimmancin abin rufe fuska wanda ke aiki a matsayin madaidaicin madaurin wutar lantarki na ciki don fita daga tankin ƙarfe na ƙasa. An gina shi daga maɗaukakin ƙarfi, mai kyalli, yana samar da ingantacciyar ƙarfin wutar lantarki don keɓance madugu mai kuzari daga gidajen tafofi mai ƙasa, koda ƙarƙashin rigar da gurɓataccen yanayi. Halayensa elongated, ribbed ko siket zane yana ƙara girman nisa, yana hana walƙiya. An rufe taron bushing da ƙarfi a cikin tanki don kiyaye mutuncin mai na ciki kuma galibi yana fasalta haɗin tasha (kamar kushin da aka kulle ko na'urorin haɗi na kebul) don haɗawa zuwa tsarin rarraba ƙasa ko sama.
05 Yanar Gizo da Takaitawa
Mun gode don sha'awar ku ga ma'aunin mu guda ɗaya -ƙara{1}} masu hawa tafsiri. A matsayin amintaccen bayani don rarraba wutar lantarki, suna taka muhimmiyar rawa a duka hanyoyin wutar lantarki na birane da na karkara. Samfuran mu suna fuskantar tsauraran kulawar inganci da gwaji don tabbatar da ingantaccen aiki da tsawon rai a cikin yanayi daban-daban na muhalli. Ko don aikace-aikacen masana'antu, noma, ko na zama, an ƙera tafsirin mu guda ɗaya{5}}ƙara{6} don biyan buƙatun ku da samar da amintaccen wutar lantarki. Da fatan za a ji daɗin tuntuɓar mu don ƙarin bayanin samfur ko mafita na musamman. Muna fatan yin aiki tare da ku don ƙirƙirar makoma mai haske!