Layin Wutar Lantarki na 50 kVA-13.8 / 0.12 * 0.24 kV|Guyana 2024

Layin Wutar Lantarki na 50 kVA-13.8 / 0.12 * 0.24 kV|Guyana 2024

Ƙasar Bayarwa: Guyana 2024
Yawan aiki: 50kVA
Ƙarfin wutar lantarki: 13.8 / 0.12 * 0.24 kVA
Aika Aikace-aikacen

 

 

transformer power line

SCOTECH Single Phase Pole Dutsen Masu Canji: Dogaran ƙarfi daga 10kVA zuwa 500kVA don kowane Buƙatar Grid

 

 

01 Gabaɗaya

1.1 Bayanin Aikin

Oda daga abokin cinikinmu a Guyana 2024, kamfanin sabis na injiniyan lantarki, ya haɗa da tasfoma masu ƙarfin 25kVA, 50kVA, 75kVA, 100kVA, da 167kVA. 50kVA Ideal don matsakaita{7}} wuraren zama ko ƙananan kasuwanci.

Transformer ya yi daidai da ka'idodin IEEE & ANSI C57.12.00. Yana aiki a farkon ƙarfin lantarki na 13,800V, yana saukowa zuwa 120/240V a gefen sakandare, tare da mitar 60Hz da tagulla. Matsala shine 2%, yana rage raguwar ƙarfin lantarki a ƙarƙashin kaya.

An sanye shi da tsarin sanyaya ONAN da NLTC (Babu Canjin Maɓallin Load), yana ba da kewayon bugun 10% (± 2.5% a kowace famfo), yana daidaita ƙarfin lantarki na biyu har ma da haɓakar farko. A'a -asarar kaya shine 160W, kuma akan{5}} asarar kaya shine 512W, inganta amfani da makamashi. Taswirar tana fasalta polarity mai ratsewa da rukunin vector na Ii0, yana ayyana dangantakar sa.

A matsayin babban masana'antar taransifoma, muna bayar da cikakkemafita na transformerdon buƙatun rarraba wutar lantarki.

1.2 Ƙayyadaddun Fasaha

50kVA Single lokaci iyakacin duniya saka tasfo bayani dalla-dalla da bayanai takardar

Isarwa zuwa
Guyana
Shekara
2024
Nau'in
Juzu'i guda sandar sandar da aka saka taransifoma
Daidaitawa
IEEE & ANSI C57.12.00
Ƙarfin Ƙarfi
50 kVA
Yawanci
60HZ
Polarity
Ragewa
Ƙungiyar Vector
Ii0
Babban Voltage
13800 V
Na biyu Voltage
120/240 V
Abubuwan Iska
KWANA
Impedance
2%
Hanyar sanyaya
ONAN
Matsa Canji
Farashin NLTC
Taɓa Range
± 2X2.5% (Jimlar kewayon =10%)
Babu Asara Load
160 W
Akan Rasa Load
512 W
Na'urorin haɗi
Daidaitaccen Kanfigareshan

 

 

1.3 Zane

50kVA Single lokaci iyakacin duniya saka taswira girma da nauyi cikakken bayani

image003 image005

 

 

02 Masana'antu

2.1 Kori

Fa'idar tsarin jigon raunin shine yana ba da damar kayan aikin ferromagnetic don yin cikakken amfani da mafi girman kaddarorin sa na lantarki, yana rage ma'aunin asarar ainihin. Babban kafa da giciyen karkiya - sashe na guda ɗaya -tsawon raunin lokaci duka biyu ne masu rectangular kuma suna ci gaba da rauni tare da ɗigon ƙarfe na maganadisu, suna rage rashin hasarar kaya, babu{4}} lodin halin yanzu, da hayaniyar canji.

wound core

 

2.2 Guda

high-purity enameled round copper wire

Wuraren wutar lantarki na mu na amfani da tsafta mai tsayi da aka yi wa zagaye da waya ta tagulla, wanda ke da ingantacciyar wutar lantarki da ƙarami. Rufin enamel yana ba da kariya iri ɗaya da ƙarfin dielectric abin dogara. Ɗauki ingantaccen tsarin na'ura na iska mai ƙarfi don ƙananan na'urorin wutar lantarki da iska mai ƙarfi don manyan na'urorin lantarki, tabbatar da kyakkyawan kwanciyar hankali na aiki, aminci, da aikin zafi.

 

2.3 Tanko

Tankin karfe mai laushi tare da gyalen ɗagawa masu walda da maƙallan rataye don hawan igiya kai tsaye{0}}zuwa{1}. KVA rating akan bangon tanki. Ana amfani da suturar kariya ga tankuna don rage lalata. Don tabbatar da amintaccen aiki na waɗannan na'urorin wutar lantarki duk da fuskantar yanayin yanayi mai tsauri da wuraren da suke nesa, an gina aminci cikin ƙayyadaddun su.

transformer specifications

 

2.4 Taron Karshe

core coil drying

1. Tauraron Iska:Zamar da iskar HV/LV a kan madaidaicin laminated, yana tabbatar da daidaitaccen jeri da amincin rufi.

2. Haɗin Wutar Lantarki:Haɗa iska tana kaiwa zuwa mai canza famfo, bushings, da sauran abubuwan da aka gyara, sannan a kiyaye da kuma rufe mahaɗin.

3. Core -Bushewar Naɗi:Sanya sashin da aka haɗa (core + windings) a cikin tanda mai bushewa don dumama don cire danshi.

4. Shigar Tanki:Sanya busassun sashin aiki a cikin tanki, sanya shi amintacce, kuma tabbatar da ingantaccen rufin bangon tanki.

5. Na'ura mai hawa:Shigar da bushings, bawul ɗin taimako na matsa lamba da sauran na'urorin haɗi, sa'an nan kuma bincika ɗigogi.

6. Ciko Mai & Matsala:Cika da mai mai hana ruwa, gurɓataccen ruwa, da ba da izinin daidaitawa kafin auna matakan mai da ƙarfin wutar lantarki.

 

 

03 Gwaji

Gwajin yau da kullun

1. Ma'aunin Juriya

2. Gwajin Rabo

3. Gwajin Polarity

4. Babu Asara Load Kuma Babu Load A Yanzu

5. Load Loss da Impedance Voltage

6. Gwajin Karfin Wutar Lantarki

7. Gwajin Juriya da Ƙarfin Wutar Lantarki

8. Ma'aunin Juriya na Insulation

9. Gwajin Leak tare da Matsi don Masu Canjin Ruwa na Immersed

10. Gwajin Dielectric Oil

transformer power line test

Sakamakon Gwaji

A'a.

Gwajin Abun

Naúrar

Dabi'un Karɓa

Ƙimar Ma'auni

Kammalawa

1

Ma'aunin Juriya

/

/

/

Wuce

2

Gwajin Rabo

/

Bambancin rabon ƙarfin lantarki akan babban tapping: ƙasa da ko daidai da 0.5%

Alamar haɗi: Ii0

-0.04

Wuce

3

Gwajin polarity

/

Ragewa

Ragewa

Wuce

4

A'a -asara da tashin hankali na halin yanzu

%

kW

I0 :: bayar da ma'auni darajar

P0: ba da ƙima mai ƙima

juriyar rashin hasara shine +10%

0.95

0.130

Wuce

5

Load asarar, impedance ƙarfin lantarki, jimlar asarar da kuma yadda ya dace

/

kW

kW

t:85 ku

Z%: ƙimar da aka auna

Pk: ƙimar ƙima

Pt: ƙima mai ƙima

haƙuri ga impedance shine ± 10%

juriyar jimlar asarar kaya shine +6%

2.08

0.518

0.648

99.02

Wuce

6

Gwajin Karfin Wutar Lantarki

/

HV: 34KV 60s

LV: 10kV 60s

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

7

Jarrabawar Juriya da Wutar Lantarki

/

Wutar lantarki mai aiki (KV):

2 Ur

Duration(s): 48

Mitar (HZ): 150

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

8

Ma'aunin Resistance Insulation

HV{0}LV zuwa Ground

LV -HV zuwa Ground

HV&LV zuwa Ground

83.6

76.9

75.3

/

9

Gwajin Leaka

/

matsa lamba: 20kPA

Tsawon lokaci: 12h

Babu yabo kuma babu

Lalacewa

Wuce

10

Gwajin Dielectric Oil

kV

Yafi ko daidai da 45

51.41

Wuce

 

04 Shiryawa da jigilar kaya

transformer power line packing transformer power line shipping
 

05 Yanar Gizo da Takaitawa

Mu50kVA guda ɗaya -ƙaran sandar zamani{2}}wanda aka ɗora tafsiridon Guyana yana tabbatar da ingantaccen, kwanciyar hankali, da amintaccen rarraba wutar lantarki.

Injiniya tare da ingancin iskar tagulla mai inganci, ƙananan raunin raunin rauni, da kuma tanki mai ɗorewa na waje{2}} yana ba da aminci na dogon lokaci har ma a cikin mahalli masu buƙata.

50 kVA transformer power line

 

 

Hot Tags: Layin wutar lantarki, mai kera, mai kaya, farashi, farashi