167 KVA Single Matsayin Ƙaƙwalwar Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙaƙwalwa-2.4 / 0.347 KV|Kanada 2025
Yawan aiki: 167 kVA
Wutar lantarki: 2.4/0.347 kV
Siffar: tare da IFD da anti{0}} bin diddigi

An Gina Don Abubuwan Abubuwan, Amintacce don Aiwatarwa: Maɗaukakin Maɗaukakin Lokaci Guda Daya.
01 Gabaɗaya
1.1 Bayanin Aikin
167 kVA single fase pole mounted transformer an isar da ita zuwa Kanada a shekarar 2025. Ƙarfin wutar lantarkin shine 167 kVA tare da sanyaya ONAN. Babban ƙarfin lantarki shine 2.4 kV, ƙananan ƙarfin lantarki shine 0.347 kV, sun kafa ƙungiyar vector na II6.
Na zamani guda ɗaya -ƙara - mai ɗaure tafsiri, haɗa Mai Gano Laifin Ciki (IFD) da Anti{2}Tsarin saɓo, an ƙera shi don ingantaccen dogaro a aikace-aikace masu mahimmanci kamar rarraba wutar lantarki, wutar lantarki na karkara, da layukan ciyar da masana'antu. IFD tana sa ido sosai kan laifuffukan ciki don ba da damar kiyaye tsinkaya da hana gazawa, yayin da Anti{4}}Tsarin bin diddigin yana da ƙarfi yana ƙin bin sawun saman da hazo gishirin bakin teku ya haifar, gurɓacewar masana'antu, ko muhalli mai ɗanɗano. Wannan haɗin gwiwar bincike da dorewa yana tabbatar da ingantaccen aminci kuma yana rage katsewar sabis ga abokan cinikin kayan aiki.
1.2 Ƙayyadaddun Fasaha
167 kVA iyakacin duniya saka na'ura mai ba da hanya tsakanin hanyoyin sadarwa da takardar bayanai
|
Isarwa zuwa
Kanada
|
|
Shekara
2025
|
|
Nau'in
Pole mounted transformer
|
|
Daidaitawa
CSA C2.2-06
|
|
Ƙarfin Ƙarfi
167 kVA
|
|
Yawanci
60HZ
|
|
Mataki
1
|
|
Polarity
Ƙara
|
|
Nau'in Sanyi
ONAN
|
|
Babban Voltage
2.4 kv
|
|
Na biyu Voltage
0.347 kV
|
|
Abubuwan Iska
aluminum
|
|
Ƙungiyar Vector
Ii6
|
|
Impedance
2.3%(±10%)
|
|
Matsa Canji
N/A
|
|
Babu Asara Load
0.096 kW
|
|
Akan Rasa Load
1.85 kW
|
1.3 Zane
167 kVA sandar sandar da aka ɗora zane da girman hoto.
![]() |
![]() |
02 Masana'antu
2.1 Kori

An gina ainihin sa ta amfani da ci gaba da ƙira mai rauni daga ƙarfe na silicon mai girma{0}. Wannan sabon tsarin yana haifar da ingantacciyar hanyar maganadisu tare da ƙaramin giɓi, yana haifar da ingantaccen ƙarfin kuzari da nutsuwa, ingantaccen aiki.
2.2 Guda
Yana amfani da foil na aluminium{0}}rauni don ƙananan{1}} gefen wutar lantarki don samar da ingantaccen gajeriyar ƙarfi{2}}ƙarfin kewayawa da wariyar aluminium mai shimfiɗaɗɗa{3}}ƙirar rauni don babban gefen wutar lantarki{4}} don mafi kyawun rarraba wutar lantarki. Wannan tsarin haɗakar iska, ta amfani da aluminium, yana samun ma'auni mafi kyau na dogaro, farashi{6} inganci, da aikin zafi.

2.3 Tanko

An gina tankin daga babban bakin karfe{0}maki, yana ba da juriya na musamman da kuma kawar da buƙatar fenti. Ƙirar sa ta hatimi, haɗe tare da ƙuƙumma, yana tabbatar da ƙaƙƙarfan kariya daga ƙaƙƙarfan mahalli da ingantaccen, kulawa{2}}ƙasasshen zafi kyauta a tsawon rayuwar sabis.
2.4 Taron Karshe
Haɗin ƙarshe yana wakiltar daidaitattun haɗin kai na duk manyan abubuwan haɗin gwiwa. Babban-An rufe taro mai iska a cikin tankin bakin karfe mai juriya, wanda babu ruwa{3}}cike da ruwan dielectric don tabbatar da mafi girman ƙarfin kuzari da sanyaya. Haɗe-haɗe na manyan injina na lantarki, na'urorin haɗi, da ƙaƙƙarfan gwaji na ƙarshe suna tabbatar da cikakken aiki, wanda ke haifar da ɗorewa da kiyayewa{6} ingantacciyar na'ura mai ɗaukar nauyi da aka inganta don rarraba sama.

03 Gwaji
Ƙaƙwalwar -ƙara -wanda aka ɗora wutar lantarki (samfurin: 167kVA-2.4/0.347kV) ta SCOTECH ya bi CSA C2.2{24}}06(R2022) da CSA C802.1-02. Gwaje-gwaje na yau da kullun sun haɗa da ma'aunin juriya na iska (HV: 0.09067Ω, LV: 1.919mΩ a digiri 32 da 60% zafi), gwajin rabo (saɓawa: 0.04% Kasa da ko daidai da 0.5%, ƙungiyar vector: Ii6), gwajin polarity (Ƙari, buƙatun gwaji}) 9: {asara 9} haƙuri, halin yanzu: 0.36%), gwajin gwaji (asarar a digiri na 85: 1165W, asarar duka: 1261W, rashin ƙarfi na ɗan gajeren lokaci: 2.17% a cikin ± 10% haƙuri, inganci: 99.57% Mafi girma ko daidai da 98.63%) V: rushewar wutar lantarki a cikin 0k, 0k, 6. Gwajin jurewar wutar lantarki (0.694kV, 150Hz don 48s, babu rushewar wutar lantarki), ma'aunin juriya na juriya (LV-HV zuwa ƙasa: 29.1GΩ), 20kPa gwajin leak ɗin matsa lamba (24h, babu ɓarna ko lalacewa), da gwajin mai (ƙarfin dielectric: 58.4kV, abun ciki na danshi: 9.5mg).
|
A'a. |
Gwajin Abun |
Naúrar |
Karba Darajoji |
Ƙimar Ma'auni |
Kammalawa |
|
1 |
Ma'aunin Juriya |
/ |
/ |
/ |
Wuce |
|
2 |
Gwajin Rabo |
/ |
Bambancin rabon ƙarfin lantarki akan babban tapping: ƙasa da ko daidai da 0.5% Alamar haɗi: ii6 |
0.04 |
Wuce |
|
3 |
Gwajin polarity |
/ |
Ƙara |
Ƙara |
Wuce |
|
4 |
A'a -asara da tashin hankali na halin yanzu |
% |
I0 :: bayar da ma'auni darajar |
0.36 |
Wuce |
|
kW |
P0: ba da ƙima mai ƙima |
0.095 |
|||
|
/ |
juriyar rashin hasara shine +15% |
/ |
|||
|
5 |
Load asarar, impedance ƙarfin lantarki, jimlar asarar da kuma yadda ya dace |
/ |
t:85 ku haƙuri ga impedance shine ± 10% juriyar jimlar asarar kaya shine +8% |
/ |
Wuce |
|
% |
Z%: ƙimar da aka auna |
2.17 |
|||
|
kW |
Pk: ƙimar ƙima |
1.165 |
|||
|
kW |
Pt: ƙima mai ƙima |
1.261 |
|||
|
% |
Ingancin ba kasa da 98.63% |
99.57 |
|||
|
6 |
Gwajin Karfin Wutar Lantarki |
/ |
LV: 10kV 60s |
Babu rushewar ƙarfin gwajin da ke faruwa |
Wuce |
|
7 |
Jarrabawar Juriya da Wutar Lantarki |
/ |
Wutar lantarki mai aiki (KV): 0.694 |
Babu rushewar ƙarfin gwajin da ke faruwa |
Wuce |
|
Duration(s):48 |
|||||
|
Mitar (HZ): 150 |
|||||
|
8 |
Ma'aunin Resistance Insulation |
GΩ |
LV -HV zuwa Ground |
29.1 |
Wuce |
|
9 |
Gwajin Leaka |
/ |
matsa lamba: 20kPA |
Babu yabo kuma babu Lalacewa |
Wuce |
|
Tsawon lokaci: 12h |
|||||
|
10 |
Gwajin Mai |
kV |
Ƙarfin Dielectric |
58.4 |
Wuce |
|
mg/kg |
Abubuwan Danshi |
9.5 |
|||
|
% |
Factor Dissipation |
0.00194 |
|||
|
mg/kg |
Furan Analysis |
0.03 |
|||
|
/ |
Gas Chromatography Analysis |
/ |


04 Shiryawa da jigilar kaya
4.1 Shiryawa

Don marufi, igiya ɗaya na - na zamani - wanda aka ɗora tasfoma yana cikin amintaccen akwatin katako mai ɗorewa. Kafin a sanya shi a cikin akwatin, an rufe tafsirin da fim ɗin filastik don kariya daga zafi da gurɓatawa. Akwatin katako yana sanye da kayan ƙarfafa gefen ƙarfe don ingantacciyar dorewa, kuma mahimman umarnin kulawa da alamun gargaɗi ana buga su a fili a saman sa. Bugu da ƙari, an saita shi a kan pallet, yana sauƙaƙe ayyukan dabaru da kuma tabbatar da cewa taswirar ta kasance cikin yanayi mai kyau yayin jigilar kaya da ajiya.
4.2 Shipping
Ƙarƙashin sharuɗɗan CIF na Montreal, - sandar sandar zamani - da aka ɗora tasfofi ana jigilar su ta jigilar kaya na teku. Mai siyarwar ya tsara da kuma biyan kuɗin jigilar ruwa zuwa tashar jiragen ruwa na Montreal, yana samar da inshorar jigilar kayayyaki na ruwa don kiyaye haɗarin haɗari, kuma yana tabbatar da sarrafa na'urorin lantarki da kyau kuma an loda su a kan jirgin don isar da lafiya zuwa tashar jirgin ruwa.

05 Yanar Gizo da Takaitawa
Tun daga ƙaƙƙarfan ginin bakin ƙarfensa zuwa ƙaƙƙarfan ƙwaƙƙwaran rauni da iska, kowane fanni na wannan -ƙara mai tsayi{1}} wanda aka ɗora shi an yi shi don manufa ɗaya: amincin da bai dace ba a filin. Yana da wayo, zaɓi mai dorewa don abubuwan amfani waɗanda ke neman haɓaka juriyar grid, rage farashin aiki, da samar da sabis na musamman ga abokan cinikinsu. Shin kuna shirye don yin iko da gaba tare da amincewa? Tuntuɓe mu a yau don gano yadda za'a iya haɗa wannan taransifoma zuwa cibiyar sadarwar ku.

Hot Tags: single phase sandar sandar da aka ɗora tafsiri, masana'anta, mai siyarwa, farashi, farashi
You Might Also Like
167 kVA Canjin Wuta na Wuta-13.8 / 0.347 kV|Kanada 2025
75 kVA Mai Canjawa Mai Amfani-24.94 / 0.12 kV|Kanada...
Layin Wutar Lantarki na 50 kVA-13.8 / 0.12 * 0.24 kV...
75 kVA Pole Mounted Transformer-7.97/0.12/0.24 kV|Ka...
37.5 kVA Transformers A kan sandar waya-34.5 / 0.12 ...
25 kVA Mai Canja Wuta Mai Wuta-14.4 / 0.12 kV|Kanada...
Aika Aikace-aikacen