167 kVA Canjin Wuta na Wuta-13.8 / 0.347 kV|Kanada 2025
Yawan aiki: 167 kVA
Wutar lantarki: 13.8/0.347kV
Feature: tare da surge arrester

Tsayayyen Makamashi, Ruwa ko Haske - Amintattun Motoci Masu Haɗawa!
01 Gabaɗaya
1.1 Bayanin Aikin
A cikin 2025, an isar da sandar taswirar kVA 167 - zuwa Kanada. Yana aiki a matsayin yanki na masana'antu da kasuwanci na kewayen birni, yana samar da wuraren samar da haske, ofisoshi, da gungu na zama. Ƙarfin yana zuwa ta hanyar ciyarwar 13.8kV, yana sauka zuwa 0.347 kV don amfanin yau da kullum. Kololuwar dumama lokacin sanyi da guguwa na lokaci-lokaci suna yin abin dogaro, tsayayye mai ƙarfi dole ne.
An gina taswirar tare da sanyaya ONAN, ± 2 × 2.5% NLTC, da rukunin vector na Ii6. Tare da ƙari polarity, yana haɗawa da sauƙi cikin daidaitattun tsarin lantarki. Na'urar agajin matsin lamba tana karewa daga wuce gona da iri na ciki, yayin da haɗe-haɗe mai kama shugaba ke gadin walƙiya da ƙarfin wutar lantarki. A kashe -Mai canjin kewayawa yana ba da damar daidaita wutar lantarki ta hannu{6}}babu katsewar sabis da ake buƙata.
Karami mai ƙarfi amma mai ɗorewa, wannan transfomer yana da sauƙin shigarwa. Yana aiki da kyau a cikin hanyoyin sadarwar mai amfani, wuraren kasuwanci, wuraren masana'antu, da haɗin gwiwar makamashi mai sabuntawa. An ƙera shi don ɗaukar yanayi mai tsauri, yana ba da ingantaccen lokacin wutar lantarki{2} zagaye kuma yana tallafawa ayyukan rarraba birane da ƙauyuka.
1.2 Ƙayyadaddun Fasaha
167 kVA iyakacin duniya saka na'ura mai ba da hanya tsakanin hanyoyin sadarwa da takardar bayanai
|
Isarwa zuwa
Kanada
|
|
Shekara
2025
|
|
Nau'in
igiya saka taransifoma
|
|
Daidaitawa
CSA C2.2-06
|
|
Ƙarfin Ƙarfi
167 kVA
|
|
Yawanci
60HZ
|
|
Mataki
3
|
|
Polarity
Ƙara
|
|
Nau'in Sanyi
ONAN
|
|
Babban Voltage
13.8 kV
|
|
Na biyu Voltage
0.347 kV
|
|
Abubuwan Iska
Aluminum
|
|
Matsala ta kusurwa
Ii6
|
|
Impedance
3%
|
|
Matsa Canji
Farashin NLTC
|
|
Taɓa Range
±2*2.5%
|
|
Babu Asara Load
0.295 kW
|
|
Akan Rasa Load
2.255 kW
|
|
Na'urorin haɗi
Daidaitaccen Kanfigareshan
|
1.3 Zane
167 kVA sandar sandar da aka ɗora zane da girman hoto.
![]() |
![]() |
02 Masana'antu
2.1 Insulation & Core Technology
Matsakaicin 167 kVA da aka ɗora wutar lantarki yana ɗauke da a125 kV BIL, wanda -musamman a cikin guguwa -yankuna masu saurin kamuwa da shi{2}} yana ba ta dakin numfashin da yake bukata daga tashin hankali. Da kumaamorphous karfe core, shiru da inganci, ba a gyara asarar - ta hanyar da za ta zama sananne a tsawon shekaru na aiki.

2.2 Daidaituwar Lantarki

Ƙarin polarity, ƙungiyar Ii6 vector, windings na aluminum{1}}ba wani sabon abu ga grid na Arewacin Amurka. Waɗannan cikakkun bayanai suna sa sandar hasken wutar lantarki ta ɗora, da kyau{3}}ya dace da masu ciyarwa, da sauƙin shiga cikin ayyukan sauyawa na yanzu.
2.3 Sanyaya & Tsarin Injini
Sanyaya ya dogara ne akan zagayawa na ONAN, amma tare da karkatarwa: filayen radiyo akan bangon tanki, yana ƙara zafin mai - yanki na tarwatsewa; sassa masu sauƙi, babu hanyoyin motsi, duk da haka tasirin yana da tsayi kuma abin dogara. Zane yana gudana bisa ga dabi'a, har ma a cikin dogon lodin hunturu lokacin da na'urar ta atomatik ke samun hutu.

2.4 Babban Mai kama

Theshugaba mai kameyana ɗaukar haske anan{0} saita kai tsaye akan bangon tanki, mai siffa don hawa da sauri, kuma a sanya shi ta yadda hanyar ƙasa ta zama gajere da tsabta. Masu sakawa suna son irin wannan daki-daki; yana adana 'yan mintoci kaɗan yayin shigarwa kuma yana guje wa tuƙi na kebul mara kyau akan sandar. Babu wani abu da ke rataye a kusa da shi, babu alamun da ba dole ba{3}}kawai mai amfani ne kawai, ginannen -a cikin keɓancewa wanda ke taimaka wa igiya da aka ɗora taswira don sarrafa walƙiya da jujjuyawar daɗaɗɗa tare da ƙarin kwarin gwiwa.
2.5 Muhimman Abubuwan Tsaro
Na'urar taimako na matsa lamba tana kiyaye kariya daga matsanancin matsatsi na ciki da ba zato ba tsammani{0}} iskar gas, faɗaɗa zafi, kuna suna. Tankin da kansa, cikakken yanayi -, yana sarrafa ruwan sama mai daskarewa, feshin gishiri, ko shekara mai sauƙi{3}} zagaye na UV ba tare da ƙaranci ba.

05 Amfanin Ayyuka

Tushen da aka ɗora wutar lantarki yana kula da masu ciyar da abinci na birane da kewayen karkara ba tare da hayaniya ba. Yana dawwama ta hanyar hawan hunturu, canjin yanayi ba zato ba tsammani, ko guguwa{1}} bambance-bambancen wutar lantarki masu alaƙa- yanayi waɗanda galibi ke gwada kayan aikin rarrabawa a Kanada.
Ƙirar ƙarancin ƙiransa,{0}}arancin hasara, haɓaka ta hanyar amorphous core da CSA{1}}aiki masu dacewa, yana sa naúrar ta kasance mai sanyaya kuma tana da arziƙi cikin lokaci. Shigarwa ya kasance cikin sauri: ƙaramin tanki, sharewar da za a iya tsinkaya, filayen radiyo da aka sanya don hawan igiya mai sauƙi. Da zarar an sami kuzari, taranfomar ba ta cika neman kulawa ba; sanyaya na halitta tare da madaidaiciyar abubuwan gyara suna kiyaye a sarari da tsinkaya.
Yanki na masana'antu, gungu na zama, ko gauraye{0}}amfani da corridor{1} transfomer yayi daidai da kowane saiti ba tare da buƙatar kulawa ta musamman ba. M, tsayayye, kuma an gina shi don rayuwar waje, yana yin aikinsa kawai.
04 Gwaji


05 Kiɗa da jigilar kaya
5.1 Shiryawa
Sansanin da aka ɗora tasfoman{0} an cushe shi a cikin wani akwati mai ƙarfi na katako ko firam ɗin ƙarfe, an sanya shi a ciki tare da girgiza (misali, kumfa ko kumfa) kuma an naɗe shi da fim ɗin filastik mai hana ruwa don hana danshi da tasiri yayin tafiya. Ana tsare jikin na’urar taranfoma da madaurin karfe, yayin da sassa masu rauni kamar na’urar wutan lantarki ana kiyaye su da tsattsauran murfin filastik, kuma tankin mai yana rufewa don hana zubewa. An yi wa marufi a fili alamar "↑Wannan Side Up," "Rarraucewa," ƙayyadaddun samfur, nauyi, da wuraren ɗagawa, ta amfani da itacen ISPM15 mai dacewa. Ƙirar tana tabbatar da aminci, yarda da muhalli, da sauƙin sarrafawa don sufuri ɗaya ko na zamani.

5.2 Shipping

Ƙarƙashin sharuɗɗan CIF, za a aika da sandar taswirar - ta hanyar jigilar kaya zuwa tashar jiragen ruwa na Montreal, tare da mai siyar da alhakin ɗaukar kaya da farashin inshora. Za a ɗora kayan a cikin madaidaicin kwantena, tare da matakan tsaro masu ƙarfi don wucewa lafiya. Dole ne mai siyarwa ya samar da cikakkun takaddun jigilar kaya (gami da tsaftataccen B/L, daftarin kasuwanci, da takardar shaidar inshora) kuma tabbatar da bin ayyukan tashar jiragen ruwa na hunturu na Montreal. Mai siye ne ke da alhakin ba da izinin kwastam a lokacin isowa da kuma shirya sufurin cikin ƙasa.
06 Aikace-aikace

Wuraren zama



Scotech yana ba da -iyalin sandar lokaci{1}}ananan na'urorin rarraba wutar lantarki, wanda aka gina da farko don rarraba saman gida. Amma suna yin fiye da haka{3} suna kuma kula da hasken masana'antu, kaya masu sauƙi na kasuwanci, da sauran aikace-aikacen wutar lantarki. An ƙera kowace rukunin don biyan buƙatun tsarin rarraba kayan aiki na yau da kullun. Yarda da IEC, ANSI/IEEE, CSA, RUS, NEMA ma'auni yana tabbatar da aminci da aminci.
Hot Tags: Power Pole Transformer, Manufacturer, Supplier, Price, Cost
You Might Also Like
50 kVA Utility Pole Transformers-34.5 / 0.12 * 0.24 ...
75 kVA Utility Pole Transformer-34.5 / 0.12 * 0.24 k...
167 kVA Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙ...
167 kVA Cooper Kushin Haɗa Mai Canjawa-13.8 / 0.24 k...
15 kVA Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwaƙw...
75 kVA Mai Canjawa Mai Amfani-24.94 / 0.12 kV|Kanada...
Aika Aikace-aikacen