50 kVA Mai Canja wurin Wutar Lantarki-13.8 / 0.347 kV|Kanada 2025

50 kVA Mai Canja wurin Wutar Lantarki-13.8 / 0.347 kV|Kanada 2025

Ƙasar Bayarwa: Kanada 2025
Yawan aiki: 50kVA
Wutar lantarki: 13.8/0.347kV
Feature: High ƙarfin lantarki biyu bushing
Aika Aikace-aikacen

 

 

CSA-compliant

Dogara mai ƙarfi ga hanyoyin sadarwar kan layi - CSA{1}}mai yarda da waje{2}} shirye

 

01 Gabaɗaya

1.1 Fagen Aikin

Don biyan buƙatun rarraba kayan aiki na gida a Kanada, an isar da raka'a uku na 50 kVA, 13.8 kV guda -ƙaran sandar lokaci{3}} da aka ɗora tafsiri. An ƙera shi da ginawa cikin yarda da ka'idodin CSA C2.1 da C802.1, waɗannan masu canji suna tabbatar da ingantaccen aiki da cikakken bin buƙatun lantarki na Kanada.

Kowane taswira yana da babban ƙarfin lantarki na 13.8 kV Delta da ƙarfin lantarki na biyu na 347 V, tare da ƙimar BIL na 95 kV/30 kV, impedance na 2.3% ± 15%, matsakaita zafin iska na 65 digiri, da ƙari polarity. An ƙera shi don sanyaya ONAN na waje, rukunin sun haɗa da 5{11}}mai canza matsa lamba (±2×2.5%) kuma an sanye su da murfi{12}}mai hawa mai tsayi{13}}ƙarar wuta da gefe{14}}mai hawa ƙasa{15}}ƙarar wutar lantarki don daidaitaccen shigarwa na saman sandar sanda.

A matsayin mafitacin sandar wutar lantarki na yau da kullun, waɗannan raka'a an ƙera su don rarraba wutar lantarki a cikin mahalli na waje kuma sun dace don:

• Wuraren zama a yankunan karkara ko yankunan karkara

• Kayan kasuwanci mai sauƙi tare da wadatar lokaci ɗaya{0}

• Fadada hanyar sadarwa ko ƙarfafa ciyarwa a 13.8 kV

 

1.2 Ƙayyadaddun Fasaha

50kVA guda lokaci igiyar wutar lantarki da aka ɗora ƙayyadaddun taswira da takaddar bayanai

Isarwa zuwa
Kanada
Shekara
2025
Nau'in
Pole mounted transformer
Daidaitawa
Bayanan Bayani na CSA2.1
Ƙarfin Ƙarfi
50 kVA
Yawanci
60HZ
Polarity
Ragewa
Ƙungiyar Vector
Ii0
Babban Voltage
13800 V
Na biyu Voltage
347 V
Abubuwan Iska
KWANA
Impedance
2.3%
Hanyar sanyaya
ONAN
Matsa Canji
Farashin NLTC
Taɓa Range
±2X2.5%
inganci
98.84 %
Babu Asara Load
135 W
Akan Rasa Load
705 W
Na'urorin haɗi
Daidaitaccen Kanfigareshan

 

1.3 Zane

50kVA lokaci guda igiyar wutar lantarki da aka ɗora ma'auni da cikakkun bayanai masu nauyi

transformer electric pole diagram transformer electric pole nameplate

 

 

02 Masana'antu

2.1 Kori

Wannan 50kVA wutan lantarki da aka ɗora tafsiri yana da ƙayyadaddun ƙayyadaddun sanyi{2} silicon karfe core kafa ta hanyar iska. Karamin tsarinsa da da'irar maganadisu iri ɗaya daidai yana rage asarar nauyi zuwa 160W. An ƙera shi don saduwa da ƙa'idodin CSA C2.1, yana da kyau{8}} ya dace da aikace-aikacen rarraba 13.8/0.347kV.

CSA C2.1

 

2.2 Guda

Wutar wutar lantarki tana amfani da kayan jan ƙarfe, tare da ƙaramin -ƙarar ƙarfin wutar lantarki da aka samar ta hanyar iskar waya da babban iskar wutar lantarki da aka yi daga iska mai ƙarfi. Wannan haɗin gwiwar yana tabbatar da kyakkyawan ingancin wutar lantarki da ingantaccen zafi mai zafi. ƙwararrun ƙwararrun ƙwararrun ƙwararrun ƙwararrun ƙwararrun ƙwararrun ƙwararrun ƙwararrun ƙwararrun ƙwararrun ƙwararrun ƙwararrun ƙwararrun ƙwararrun ƙwararrun ƙwararrun ƙwararrun ƙwararrun ƙwararrun ƙwararrun ƙwararrun ƙwararrun ƙwararrun ƙwararrun ƙwararrun ƙwararrun ƙwararrun ƙwararrun injiniya ne ke ƙera su don haɓaka aiki da aminci, saduwa da ƙaƙƙarfan ƙa'idodin masana'anta.

 

2.3 Tanko

sealed structure transformer tank

An yi tankin mai canza fasalin da ƙarfe mai ɗorewa kuma an lulluɓe shi da fenti mai launin toka mai haske don haɓaka juriya na lalata. An ƙera shi azaman tsarin da aka rufe, yana hana haɓakar mai da kutsawa cikin ruwa yadda ya kamata. Kowace naúrar tana fuskantar ƙaƙƙarfan gwajin iska{2}} don tabbatar da kyakkyawan aikin hatimi, yana ba da ingantaccen kariya ga abubuwan ciki a cikin matsanancin yanayi na waje.

 

2.4 Taron Karshe

A yayin taro, ana ɗora bushings na HV a saman tanki, tare da tashar H1 ta amfani da matsi mai 4- da H2 da aka haɗa ta ciki ta ƙusoshi. Ana shigar da tashoshi na LV spade a gefen tanki don sauƙin wayoyi. An shigar da ƙwalƙwalwar ƙasa, tanki, da madauri na ƙasa, tare da bakin karfe mai ramin rami ɗaya na ƙasa wanda ke tabbatar da aiki mai aminci da aminci.

transformer electric pole winding

 

 

03 Gwaji

Gwajin yau da kullun

1. Ma'aunin Juriya

2. Gwajin Rabo

3. Gwajin Polarity

4. Babu Asara Load Kuma Babu Load A Yanzu

5. Load Loss da Impedance Voltage

6. Gwajin Karfin Wutar Lantarki

7. Gwajin Juriya da Ƙarfin Wutar Lantarki

8. Ma'aunin Juriya na Insulation

9. Gwajin Leak tare da Matsi don Masu Canjin Ruwa na Immersed

10. Gwajin mai

transformer electric pole test

Sakamakon gwaji

 

A'a.

Gwajin Abun

Naúrar

Karba

Darajoji

Ƙimar Ma'auni

Kammalawa

1

Ma'aunin Juriya

/

/

/

Wuce

2

Gwajin Rabo

/

Bambancin rabon wutar lantarki akan babban tapping: ƙasa da ko daidai da ± 0.5%

Alamar haɗi: ii6

0.05~0.08

Wuce

3

Gwajin polarity

/

Ƙara

Ƙara

Wuce

4

A'a -asara da tashin hankali na halin yanzu

%

I0 :: bayar da ƙima (100%)

0.24

Wuce

kW

P0: bayar da ƙima (100%)

0.1089

%

I0 :: bayar da ƙima (105%)

0.27

kW

P0: bayar da ƙima (105%)

0.123

/

juriyar rashin hasara shine +15%

/

5

Load asarar, impedance ƙarfin lantarki, jimlar asarar da kuma yadda ya dace

/

t:85 ku

haƙuri ga impedance shine ± 15%

juriyar jimlar asarar kaya shine +8%

/

Wuce

%

Z%: ƙimar da aka auna

2.27

kW

Pk: ƙimar ƙima

0.636

kW

Pt: ƙima mai ƙima

0.7449

%

Ingancin ba kasa da 98.84%

99.00

6

Gwajin Karfin Wutar Lantarki

/

LV: 10kV 60s

HV: 34kV 60s

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

7

Jarrabawar Juriya da Wutar Lantarki

/

Wutar lantarki mai aiki (KV): 0.694

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

Duration(s):40

Mitar (HZ): 180

8

Ma'aunin Resistance Insulation

HV -LV·to·Ground

26.3

Wuce

LV -HV zuwa Ground

32.2

HV&LV zuwa Ground

28.7

9

Gwajin Leaka

/

Aiwatar da matsa lamba: 20kPA

Babu yabo kuma babu

Lalacewa

Wuce

Tsawon lokaci: 12h

10

Gwajin Mai

kV

Ƙarfin Dielectric

60.9

Wuce

mg/kg

Abubuwan Danshi

10.5

%

Factor Dissipation

0.138

mg/kg

Furan Analysis

Kasa da ko daidai da 0.1

/

Gas Chromatography Analysis

/

 

04 Shiryawa da jigilar kaya

Wooden crate packaging
 
transformer electric pole shipping
 

05 Yanar Gizo da Takaitawa

Wannan na'ura mai ɗaukar hoto don aikace-aikacen sandar wutan lantarki shine 50 kVA guda ɗaya -ƙaran sandar zamani{2}}wanda aka ɗora musamman don tsarin rarraba gida a Kanada, wanda ya cika manyan ka'idojin wutar lantarki na Arewacin Amurka. Yana da manufa don yanayin samar da wutar lantarki a waje a 13.8kV, musamman dacewa da wuraren zama na kewayen birni, ƙananan wuraren kasuwanci, da ayyukan faɗaɗa grid waɗanda ke buƙatar aminci, abin dogaro, da ƙananan kayan aikin wutar lantarki.

Tare da ingantaccen tsarin tsari da ingantaccen aiki, an gina na'urar ta atomatik don jure matsanancin yanayi da yanayin muhalli. Yana fasalta ingantattun damar rufewa da sanyaya, tare da babban - inganci, kuzari{2}} ƙira mai adanawa don saduwa da ƙaƙƙarfan buƙatun Kanada don adana makamashi da dogaro. Mai amfani da - shigarwa na abokantaka da dogon lokaci{5} ɗorewa sun sa ya zama mafi kyawun zaɓi ga kamfanoni masu amfani da ayyukan ci gaban ababen more rayuwa da suka haɗa da sandar wutan lantarki{6}}masu tafsiri.

transformer electric pole

 