167 kVA Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwaƙwalwa-13.8 / 0.12 * 0.24 kV|Guyana 2024

167 kVA Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwararren Ƙwaƙwalwa-13.8 / 0.12 * 0.24 kV|Guyana 2024

Ƙasar Bayarwa: Guyana 2024
Yawan aiki: 167kVA
Ƙarfin wutar lantarki: 13.8 / 0.12 * 0.24 kVA
Aika Aikace-aikacen

 

 

167 kva pole mounted transformer

167 kVA Pole -Mounted Transformer - Tabbataccen Maganin Wutar Lantarki na Scotech don Girin Gid

 

 

01 Gabaɗaya

1.1 Bayanin Aikin

Wannan 167 kvaigiya saka taransifomaAn isar da shi zuwa Guyana a cikin 2024. Yi biyayya da ka'idodin IEEE & ANSI C57.12.00 bisa lamiri. Polarity yana raguwa, kuma ƙungiyar vector shine Ii0. Bayar da ƙimar ƙarfin lantarki guda ɗaya na 120/240V da ƙarfin 167 kVA, wannan na'urar ta atomatik yana tabbatar da ingantaccen jujjuyawar wutar lantarki. Yana amfani da hanyar sanyaya ONAN. Ana sanyaya cibiya da coils ta hanyar kewaye da mai. Copper windings don mafi ingancin conductivity

Tare da kewayon bugun ± 2.5% da jimlar kewayon 10%, yana ba da daidaitaccen fitowar wutar lantarki ta hanyar sarrafa kaya mai ƙarfi, haɓaka aiki a cikin buƙatu masu canzawa. Rashin isar da wutar lantarki - shine 379W kuma akan - asarar kaya shine 1360W, yana nuna ingantaccen kuzari. Matsakaicin 2.4% yana rage raguwar ƙarfin lantarki a ƙarƙashin kaya, yana tallafawa daidaitaccen isar da wutar lantarki.

Scotechyana ba da na'urorin taswira na al'ada{0}, waɗanda aka ƙera don dacewa da ƙa'idodin ƙasashen duniya kamar IEC, ANSI/IEEE, CSA, RUS, da NEMA. Kayan na'urorin namu sun haɗa da masu kama walƙiya, IFDs (Gano Laifin Ciki), ma'aunin zafi da sanyio da ƙari. Dangane da buƙatun ku, muna samar da na'urorin taswira na al'ada da kuma Cikakkiyar Kai{3}} Samfuran Kariya (CSP).

 

1.2 Ƙayyadaddun Fasaha

167 kVA iyakacin duniya saka taswirar ƙayyadaddun bayanai da takaddar bayanai

Isarwa zuwa
Guyana
Shekara
2024
Nau'in
Juzu'i guda sandar sandar da aka saka taransifoma
Daidaitawa
IEEE & ANSI C57.12.00
Ƙarfin Ƙarfi
167 kVA
Yawanci
60HZ
Polarity
Ragewa
Ƙungiyar Vector
Ii0
Babban Voltage
13800 V
Na biyu Voltage
120/240 V
Abubuwan Iska
KWANA
Impedance
2.4%
Hanyar sanyaya
ONAN
Matsa Canji
Farashin NLTC
Taɓa Range
± 2X2.5% (Jimlar kewayon =10%)
Babu Asara Load
379 W
Akan Rasa Load
1360 W
Na'urorin haɗi
Daidaitaccen Kanfigareshan

 

 

1.3 Zane

167 kVA iyakacin duniya saka ma'auni mai canzawa da cikakkun bayanai masu nauyi

167 kva pole mounted transformer outline drawing 167 kva pole mounted transformer nameplate

 

 

02 Masana'antu

2.1 Kori

167 kva pole mounted transformer wound core

Ƙarƙashin yanayi guda ɗaya, ƙananan raunin rauni suna rage rashin hasara mai nauyi da babu{1}}waɗanda aka yi amfani da su idan aka kwatanta da laminated cores. Rauni yana ba da fiye da kashi 7% ƙasa da -asara fiye da laminated. An yi amfani da shi sosai a cikin ƙaramin ƙarfin sandar sandar da aka ɗora wutar lantarki. Muna gudanar da gwajin ingancin ƙarshe na 100% don tabbatar da daidaiton girman da kuma tabbatar da cewa an cika iyakokin ƙimar maganadisu.

2.2 Guda

Masanan mu na iska, tare da gogewa sama da shekaru 10, suna tabbatar da daidaitawar coil da daidaitaccen sarrafa tashin hankali a cikin kowane Layer, rage jujjuyawar juyi da lalacewar rufi. Haɗe tare da ingancin tagulla mai inganci{2} da na'urar gyaran fuska na musamman, coils ɗin mu na iya jure maɗaukakiyar nauyi da dogayen zagayowar aiki.

167 kva pole mounted transformer copper winding

 

 

2.3 Tanko

steel plate oil tank of pole transformer

Tankin na'ura mai canzawa wani muhimmin bangare ne na na'urar taswirar wutar lantarki, wanda ke ƙunshe da asali, coils, da insulating mai don amintaccen aiki. A Scotech, muna kera tankuna na al'ada waɗanda aka gina don ƙayyadaddun ƙayyadaddun bayanai: duk girman kayan dole ne ya dace da zane-zane, tare da rarrabuwa a ƙarƙashin 1 mm. Dole ne faranti na ƙarfe ya dace da ma'auni na ƙasa, tare da filaye marasa nakasu, tsatsa mai nauyi, bawo, ko haƙora.

 

2.4 Taron Karshe

1. Tauraron Iska:Zamar da iskar HV/LV a kan madaidaicin laminated, yana tabbatar da daidaitaccen jeri da amincin rufi.

2. Haɗin Wutar Lantarki:Haɗa iska tana kaiwa zuwa mai canza famfo, bushings, da sauran abubuwan da aka gyara, sannan a kiyaye da kuma rufe mahaɗin.

3. Core -Bushewar Naɗi:Sanya sashin da aka haɗa (core + windings) a cikin tanda mai bushewa don dumama don cire danshi.

4. Shigar Tanki:Sanya busassun sashin aiki a cikin tanki, sanya shi amintacce, kuma tabbatar da ingantaccen rufin bangon tanki.

5. Na'ura mai hawa:Shigar da bushings, bawul ɗin taimako na matsa lamba da sauran na'urorin haɗi, sa'an nan kuma bincika ɗigogi.

6. Ciko Mai & Matsala:Cika da mai mai hana ruwa, gurɓataccen ruwa, da ba da izinin daidaitawa kafin auna matakan mai da ƙarfin wutar lantarki.

167 kva pole mounted transformer assembly

 

03 Gwaji

Gwajin yau da kullun

1. Ma'aunin Juriya

2. Gwajin Rabo

3. Gwajin Polarity

4. Babu Asara Load Kuma Babu Load A Yanzu

5. Load Loss da Impedance Voltage

6. Gwajin Karfin Wutar Lantarki

7. Gwajin Juriya da Ƙarfin Wutar Lantarki

8. Ma'aunin Juriya na Insulation

9. Gwajin Leak tare da Matsi don Masu Canjin Ruwa na Immersed

10. Gwajin Dielectric Oil

 

167 kva pole mounted transformer testing
167 kva pole mounted transformer fat

 

Sakamakon Gwaji

A'a.

Gwajin Abun

Naúrar

Dabi'un Karɓa

Ƙimar Ma'auni

Kammalawa

1

Ma'aunin Juriya

/

/

/

Wuce

2

Gwajin Rabo

/

Bambancin rabon ƙarfin lantarki akan babban tapping: ƙasa da ko daidai da 0.5%

Alamar haɗi: Ii0

-0.06

Wuce

3

Gwajin polarity

/

Ragewa

Ragewa

Wuce

4

A'a -asara da tashin hankali na halin yanzu

%

kW

I0 :: bayar da ma'auni darajar

P0: ba da ƙima mai ƙima

juriyar rashin hasara shine +10%

0.29

0.343

Wuce

5

Load asarar, impedance ƙarfin lantarki, jimlar asarar da kuma yadda ya dace

/

kW

kW

t:85 ku

Z%: ƙimar da aka auna

Pk: ƙimar ƙima

Pt: ƙima mai ƙima

haƙuri ga impedance shine ± 10%

juriyar jimlar asarar kaya shine +6%

2.16

1.178

1.521

99.27

Wuce

6

Gwajin Karfin Wutar Lantarki

/

HV: 34KV 60s

LV: 10kV 60s

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

7

Jarrabawar Juriya da Wutar Lantarki

/

Wutar lantarki mai aiki (KV):

2 Ur

Duration(s): 48

Mitar (HZ): 150

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

8

Ma'aunin Resistance Insulation

HV{0}LV zuwa Ground

LV -HV zuwa Ground

HV&LV zuwa Ground

54.6

52.7

50.3

/

9

Gwajin Leaka

/

matsa lamba: 20kPA

Tsawon lokaci: 12h

Babu yabo kuma babu

Lalacewa

Wuce

10

Gwajin Dielectric Oil

kV

Yafi ko daidai da 45

51.03

Wuce

 

 

04 Shiryawa da jigilar kaya

167 kva pole mounted transformer packaging
 

 

 

05 Yanar Gizo da Takaitawa

Scotech yana ba da ingantacciyar sandar sandar sandar hannu{0}saka tafsiri da aka gina don yin fice a cikin mahalli masu buƙata. Rukunin mu sun haɗu da ingantattun injiniyoyi tare da kayan ƙima don tabbatar da shekarun da suka gabata na sabis na dogaro don grid masu amfani, ayyukan wutar lantarki, da aikace-aikacen masana'antu.

Kowane transformer yana nuna sadaukarwar mu ga kyakkyawan aiki:

Injiniya don matsananciyar yanayi- Jurewa matsananciyar yanayi da maɗaukakiyar kaya

Ingantaccen inganci{0} Na ci gaba na ƙira yana rage asarar kuzari

Kula da inganci mai ƙarfi- Daga zaɓin abu zuwa gwaji na ƙarshe

Daidaitawar al'ada- An keɓance don biyan takamaiman buƙatun yanki

An goyi bayan shekarun da suka gabata na ƙwarewar masana'antar taswira, Scotech yana ba da ƙarfi ga al'ummomin yayin da rage buƙatun kulawa da raguwar lokaci. A duk inda ingantaccen wutar lantarki ya shafi, taranfoma na mu suna bayarwa.

167 kva pole mounted transformer-right-view

 

 

Hot Tags: 167 kva iyakacin duniya saka transformer, manufacturer, maroki, farashin, farashi