25 kVA Mai Canjin Wuta na Wuta-13.8 / 0.12 * 0.24 kV|Guyana 2024

25 kVA Mai Canjin Wuta na Wuta-13.8 / 0.12 * 0.24 kV|Guyana 2024

Kasar: Guyana 2024
Yawan aiki: 25kVA
Wutar lantarki: 13.8/0.24kV
Feature: tare da jan karfe
Aika Aikace-aikacen

 

 

electric pole transformer

Guda ɗaya{0}}iyakin zamani{1} masu ɗaure tafsiri: ginshiƙan kyakkyawan rabon wutar lantarki na zamani.

 

01 Gabaɗaya

1.1 Fagen Aikin

An isar da wutar lantarki mai nauyin 25 KVA zuwa Guyana a cikin 2024. Ƙididdigar ƙarfin wutar lantarki da aka ɗora shi ne 25 KVA tare da sanyaya ONAN, ƙarfin farko shine 13.8 kV tare da ± 2 * 2.5% tapping range (NLTC), ƙarfin lantarki na biyu shine 0.12/0.24 kV, sun kafa ƙungiyar lipid. -ana amfani da na'urar taswira guda ɗaya a cikin tsarin rarraba wutar lantarki don rage wutar lantarki don biyan bukatun gidaje da ƙananan masu amfani da kasuwanci. Yawancin lokaci ana sanya shi a kan sandar watsa wutar lantarki da rarraba wutar lantarki, don haka ana kiranta "Pole transformer".

Irin wannan na'urar tana canza babban wutar lantarki zuwa ƙaramin ƙarfin aiki ta hanyar samar da wutar lantarki guda ɗaya -, yana tabbatar da ƙarancin wutar lantarki yayin watsawa. Ya ƙunshi juzu'i na farko, iska na biyu da kuma baƙin ƙarfe. Taransfoma na sanda suna da ƙarfi kuma suna da sauƙin shigarwa, wanda ya sa su dace don rarraba wutar lantarki a birane da karkara.

Bugu da kari, masu taswirar sandar sandar lokaci guda - suna da sau}i wajen aiki da kiyayewa, kuma suna iya aiki kark'ashin yanayin muhalli daban-daban. An tsara ƙirar kariyar sa sau da yawa don tsayayya da yanayi mai tsanani da kuma tasirin waje, yana tabbatar da amincin wutar lantarki. A taƙaice, irin waɗannan na'urorin wutan lantarki wani abu ne da ba makawa kuma muhimmin sashe ne na hanyoyin sadarwar wutar lantarki na zamani.

 

 

1.2 Ƙayyadaddun Fasaha

25 KVA dalla-dalla dalla-dalla da takaddun bayanai

Isarwa zuwa
Guyana
Shekara
2024
Nau'in
Pole mounted transformer
Daidaitawa
IEEE C57.12.00
Ƙarfin Ƙarfi
25 KWA
Yawanci
60HZ
Mataki
3
Nau'in Sanyi
ONAN
Babban Voltage
13.8KV
Na biyu Voltage
0.12/0.24 KV
Abubuwan Iska
Aluminum
Matsala ta kusurwa
li0
Impedance
2.2%
Matsa Canji
Farashin NLTC
Taɓa Range
±2*2.5%
Babu Asara Load
0.098KW
Akan Rasa Load
0.289KW
Na'urorin haɗi
Daidaitaccen Kanfigareshan

 

1.3 Zane

25 KVA sandar sandar da aka ɗora zane da girma.

electric pole transformer diagram

electric pole transformer nameplate

 

 

02 Masana'antu

2.1 Kori

An raunata core coil da yawa yadudduka na banded silicon karfe zanen gado don samar da madauwari ko murabba'ai rufaffiyar da'irar maganadiso. Hanyar iska ba wai kawai inganta maganadisu ba ne ta hanyar rage girman hatsi na kayan, amma har ma ƙara yawan ciko na baƙin ƙarfe. Domin rage eddy halin yanzu asara, da silicon karfe zanen gado an shirya a hankali a high matsa lamba a lokacin winding, da kuma wasu siffofi ne "tsaye" ko "matsa lamba", dangane da zane da bukatun na transformer. Kowane Layer na siliki karfe takardar da ke cikin ainihin yawanci ana lullube shi da abin rufe fuska don hana igiyoyin ruwa tsakanin yadudduka. Rufaffen da'irar maganadisu wanda ya ƙunshi birgima na ƙarfe na ƙarfe yana haɓaka ƙarfin maganadisu kuma yana sa ya fi dacewa a shigar da wutar lantarki. Ta haɓaka zaɓin kayan abu da ƙirar tsari, coil core na iya rage asarar kuzari yadda yakamata (kamar asarar hysteresis da asarar halin yanzu) waɗanda aka haifar yayin aikin taswira. Zane-zanen ƙarfe na ƙarfe ya ƙunshi juzu'in juzu'i na iska na farko da na biyu don tabbatar da cewa juzu'in jujjuyawar wutar lantarki na gidan wuta ya cika buƙatu. Saboda tsarin yana da ɗan rufewa, ƙarar da ke haifar da coil core yayin aiki ya ragu.

eddy current loss

 

2.2 Guda

Automatic foil winding machine

Ƙarfin matsi mai jujjuyawa
Na'ura mai jujjuyawa ta atomatik, TIG argon arc waldi, madaidaiciyar madaidaiciyar hanya, tsarin sarrafa PLC, tsarin gyare-gyaren hoto ta atomatik, saurin sauri da daidaitaccen iska. Mitar jujjuyawar ƙa'idar saurin stepless, shigar da wutar lantarki ta atomatik gyara. Da zarar an gama iska, ana ɗaure saman saman ciki da na waje na coil. Ƙarshen iskar foil ɗin yana da kyau kuma ɗigon ƙarshensa bai yi ƙasa ba, wanda ke sa gajeriyar ƙarfin kewayawa ba zato ba tsammani kuma an haɓaka ƙarfin kewayawa. Wutar lantarki tsakanin yadudduka na murɗa mai ƙarfi daidai yake da ƙarfin lantarki tsakanin juyi, kuma ƙarfin lantarki tsakanin yadudduka yana da ƙasa. Don samfuran waya{8}, saboda wutar lantarki ba ta da girma, yana da sauƙin ƙira da ƙira.

 

2.3 Tanko

An yi tankin da ƙarfe mai inganci{0} don tabbatar da cewa tankin yana da ƙarfin injina mai kyau da juriyar lalata. Bisa ga zanen zane, ana amfani da shears don yanke farantin karfe zuwa girman da ake so. Ta hanyar yin hatimi ko lankwasawa, an sanya farantin karfe da aka yanke zuwa sassa daban-daban na tanki (kamar farantin ƙasa, farantin gefe, farantin saman, da sauransu). Abubuwan da aka haɗa ana haɗa su cikin tanki ta amfani da walda mai karewa (MIG waldi) ko waldawar baka. Lokacin waldawa, tabbatar da ƙarfi da ƙarfi na walda. Ana goge walda bayan walda don kawar da burrs da rashin daidaituwa.

stainless steel transformer tank

 

2.4 Taron Karshe

transformer final assembly
single phase transformer assembly

 

 

03 Gwaji

A'a.

Gwajin Abun

Naúrar

Karba

Darajoji

Ƙimar Ma'auni

Kammalawa

1

Ma'aunin Juriya

/

/

/

Wuce

2

Gwajin Rabo

/

Bambancin rabon ƙarfin lantarki akan babban tapping: ƙasa da ko daidai da 0.5%

Alamar haɗi: Ii0

-0.03

Wuce

3

Gwajin polarity

/

Ragewa

Ragewa

Wuce

4

A'a -asara da tashin hankali na halin yanzu

%

kW

I0 : bayar da ma'auni darajar

P0: ba da ƙima mai ƙima

juriyar rashin hasara shine +10%

1.44

0.084

Wuce

5

Load asarar, impedance ƙarfin lantarki, jimlar asarar da kuma yadda ya dace

/

kW

kW

t:85 ku

Z%: ƙimar da aka auna

Pk: ƙimar ƙima

Pt: ƙima mai ƙima

haƙuri ga impedance shine ± 10%

juriyar jimlar asarar kaya shine +6%

2.41

0.296

0.380

98.80

Wuce

6

Gwajin Karfin Wutar Lantarki

/

HV: 34KV 60s

LV: 10kV 60s

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

7

Jarrabawar Juriya da Wutar Lantarki

/

Wutar lantarki mai aiki (KV): 2 Ur

Duration(s): 48

Mitar (HZ): 150

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

8

Ma'aunin Resistance Insulation

GΩ

HV{0}LV zuwa Ground

LV -HV zuwa Ground

HV&LV zuwa Ground

79.6

78.3

78.1

/

9

Gwajin Leaka

/

matsa lamba: 20kPA

Tsawon lokaci: 12h

Babu yabo kuma Babu Lalacewa

Wuce

10

Gwajin Dielectric Oil

kV

Yafi ko daidai da 45

52.18

Wuce

 

No-load losses test
transformer Polarity tests

 

 

04 Shiryawa da jigilar kaya

seal the tin foil bag load transformer onto transport vehicle
 

 

05 Yanar Gizo da Takaitawa

Na gode don sha'awar ku da goyan bayan ku a cikin tiransifoma mai hawa guda ɗaya -lokacin lokaci{1}}! Tare da aikin sa na musamman, aiki mai ƙarfi, da ingantaccen fasali, wannan samfurin yana biyan buƙatun wuta a cikin aikace-aikace daban-daban, yana ba da ingantaccen tallafi ga tsarin wutar lantarki. Za mu ci gaba da ƙirƙira kuma mu himmatu wajen isar da samfurori da ayyuka masu inganci-. Muna fatan yin aiki tare da ku don ƙirƙirar kyakkyawar makoma ga masana'antar wutar lantarki tare!

high-quality pole mounted transformer

 

Hot Tags: lantarki iyakacin duniya transformer, manufacturer, maroki, farashin, farashi