25 KVA Mai Canjin Wuta na Wuta-7.2 / 0.12 * 0.24 KV|Kanada 2025

25 KVA Mai Canjin Wuta na Wuta-7.2 / 0.12 * 0.24 KV|Kanada 2025

Ƙasar Bayarwa: Kanada 2025
Yawan aiki: 25kVA
Wutar lantarki: 7.2-0.12/0.24kV
Fasalin: Dual Voltage & Kariyar IFD
Aika Aikace-aikacen

Jiangshan Scotech Electric Co., Ltd yana ɗaya daga cikin amintattun masana'anta da masu samar da taswirar sandar wutan lantarki 25 kva -7.2/0.12*0.24 kv|kanada 2025 in China. Da fatan za a ji kyauta don siyan kayayyaki masu inganci don siyarwa anan kuma ku sami zane-zane daga masana'anta. Tuntube mu don ƙarin bayani.

 

25 kVA electricity pole transformer

25 kVA wutan lantarki taswirar sandar wuta - amintaccen wutar karkara tare da 9kV mai kama HV don kariya mai ƙarfi da aminci na tsawon lokaci-

 

 

01 Gabaɗaya

1.1 Bayanin Aikin

Wani ƙaramin gari na bakin teku a Atlantic Canada ya dogara da layin rarraba sama da ƙasa. Masu ciyar da abinci suna yin nisa mai nisa a cikin buɗaɗɗen filayen da bakin teku. Yankin yakan fuskanci tsawa a lokacin rani da iska mai karfi ko kankara a lokacin hunturu. Gidaje da ƙananan 'yan kasuwa suna karɓar wutar lantarki guda ɗaya{3} 120/240 V daga na'urorin wuta da aka sanya tare da masu ciyarwa.

An tsara taswirar 25 kVA don wannan yanayin. Yana da ƙarfin lantarki na farko na 12,470 GRDY / 7,200 V da na sakandare 120/240 V, yana aiki a 60 Hz, kuma yana da fasalin aluminum windings, laminated karfe core, ONAN sanyaya, da kuma NLTC tare da ± 2 × 2.5% famfo kewayon. Yana da inganci sosai (Mafi girma ko daidai da 98.87%), yana da illa na 1.9% ± 10%, kuma ya haɗa da mai kama 9 kV HV don kariyar karuwa. Ana amfani da shi don wadata ƴan gidaje ko ƙananan kasuwanci cikin aminci da dogaro.

Samar da gidaje 3-6 ko ƙananan kasuwancin gefen hanya.

A ɗora kan sandunan katako tare da daidaitaccen kayan aiki.

Yi aiki a wuraren da ke da haɗarin faɗakarwar walƙiya da jujjuyawa.

Me yasa 9kV mai kama HV ke da mahimmanci? Mai kamun kV 9 yana kiyaye na'urar taswira ta hanyar saurin karkatar da fitilun wutar lantarki kwatsam, kamar walƙiya ko juyawa, zuwa ƙasa kafin rufin ya lalace.

Wannan yana da mahimmanci musamman a hanyoyin sadarwa na karkara da bakin teku, inda wani ƙarfi mai ƙarfi guda ɗaya zai iya huda rufin, cutar da iska, ko kuma lalata man transfoma, wanda zai haifar da gazawa da katsewa. An zaɓi ƙimar 9kV a hankali don dacewa da ƙarfin lantarki na tsarin, yana tabbatar da kama mai kunnawa kafin a matsar da taswirar kanta.

 

 

 

1.2 Ƙayyadaddun Fasaha

25kVA lantarki iyakacin duniya gidan wuta ƙayyadaddun bayanai da takardar shaidar

Isarwa zuwa
Kanada
Shekara
2025
Nau'in
Pole mounted transformer
Daidaitawa
CSA C2.2-06/C802.1-23
Ƙarfin Ƙarfi
25 KWA
Yawanci
60HZ
Mataki
Single
Nau'in Sanyi
ONAN
Liquid insulant
Ma'adinan Mai
Babban Voltage
12470GRDY/7200
Na biyu Voltage
120/240 V
Polarity
Ƙara
Ƙungiyar Vector
Ii6
Abubuwan Iska
Aluminum
Impedance
1,9%(±10%)
inganci
Yafi ko daidai 98.87%
Matsa Canji
Farashin NLTC
Taɓa Range
±2*2.5%
Babu Asara Load
85 W
Load da Asara a Ƙarfin Wutar Lantarki
254 W
Na'urorin haɗi
9kV HV mai kama

 

1.3 Zane

25kVA wutan lantarki sandar wuta zane zane da sunan farantin

25kVA electricity pole transformer drawing 25kVA electricity pole transformer nameplate

 

 

02 Masana'antu

2.1 Kori

25kVA electricity pole transformer iron core

Transformer yana da ɗigon rauni wanda aka yi da siraran ƙarfe. Yana taimakawa makamashin maganadisu don motsawa cikin sauƙi tsakanin iska na farko da na biyu, yana rage asarar makamashi. Jigon yana da ƙarfi kuma ƙarami, yana kiyaye ƙarfin lantarki, yana rage zafi da hayaniya, kuma yana sa na'urar ta canza launin abin dogaro a kowace rana.

 

2.2 Guda

An ƙera shi don tsayin daka, wannan taswira ya haɗa nau'i-nau'i na LV tare da HV na waya. Copper yana ɗaukar halin yanzu, aluminum yana rage nauyi. Suna aiki tare. Ana sarrafa tsayawar zafi. Asarar ta kasance ƙasa kaɗan. lodi yana canzawa, yanayin yanayi, amma yana ci gaba da gudana. Sauƙaƙan, mai tasiri, ma'aikaci mai shiru a cikin sandar sandar sandar - da aka ɗora rarrabawa.

25kVA electricity pole transformer coils

 

2.3 9kV mai kama HV

25kVA electricity pole transformer HV arrester

Mai kamun sa na 9kV HV, wanda aka haɗa daga daji na HV zuwa ƙasa, yana ba da kariya ga taswirar ta hanyar saurin karkatar da walƙiya ko jujjuyawar motsi kafin rufi ko iska ya lalace. Tare da ci gaba da ƙarfin aiki na 7.65 kV da ragowar ƙarfin lantarki da ke ƙasa da 30 kV, ya dace da ƙarfin tsarin yayin sarrafa igiyoyi har zuwa 100 kA. Ƙananan fitarwa (<10 pC) and 308 mm creepage distance ensure safe, reliable operation in wet or coastal conditions.

 

2.4 Taron Karshe

Bayan mun sanya cibiya da coils a cikin tankin karfe da aka hatimce, gabaɗayan naúrar tana tafiya ta hanyar walda a hankali da ingantaccen maganin lalata{0} don ta iya ɗaukar shekaru na waje, yanayin bakin teku. Kafin da kuma bayan cika shi da man ma'adinai, muna gudanar da cikakken tsari{2}} bushewa don fitar da duk wani danshi ko iskar da ta kama{3}wannan matakin yana ƙarfafa rufin da gaske kuma yana rage fitar da wani sashi. Tare da cika tanki da tsarin sanyaya ONAN ɗin sa, injin ɗin ya fito daga taron ƙarshe da aka gina don dogon sandar sandar da aka ɗora-.

electricity pole transformer active part

 

 

03 Gwaji

25 kVA electricity pole transformer testing-1
25 kVA electricity pole transformer testing-2

 

 

04 Shiryawa da sufuri

4.1 Shiryawa

25 kVA electricity pole transformer packing-1
25 kVA electricity pole transformer packing-2

 

4.2 Shipping

25 kVA electricity pole transformer shipping-1
25 kVA electricity pole transformer shipping-2

 

 

05 Wutar Lantarki Pole Transformer: Yadda Suke Aiki

Electricity Pole Transformer

Wutar lantarki da aka ɗora{0}tasfoma tana amfani da induction electromagnetic don sauka ƙasa mai girma{1} wutar lantarki zuwa matakin da ya dace da gidaje da ƙananan kasuwanci. A ciki, tana da iska guda biyu -na farko da na sakandare{4}}wanda aka nannade a kusa da babban abin maganadisu:
• Babban iskar iska yana haɗi zuwa babban hanyar sadarwar rarraba wutar lantarki{0}.
• Layin na biyu ya haɗa zuwa ƙananan layin sabis na wutar lantarki wanda ke isar da 120 V ko 240 V zuwa gine-gine.
Ana rage ƙarfin wutar lantarki bisa ga jujjuyawar juyi tsakanin iska na farko da na sakandare, yana ba da aminci, wutar lantarki mai amfani ga na'urorin yau da kullun.

 

 

Hot Tags: wutar lantarki igiyar wuta transformer, manufacturer, maroki, farashin, tsada