50 kVA Single Phase Pad Hawan Rarraba Masu Canjin Rarraba-24*12/0.24 kV|Jamaica 2024
Yawan aiki: 50kVA
Wutar lantarki: 24*12-0.24/0.12kV
Feature: tare da dual primary ƙarfin lantarki

Single -Pad Pad{1}Mounted Transformer – Compact & Silent, Cikakkar Garuruwan Birane!
01 Gabaɗaya
1.1 Bayanin Aikin
50 kVA single fase pad mounted transformers rarrabawa da aka kawo zuwa Jamaica a 2025. Ƙimar ikon na'urar shine 50 kVA tare da sanyaya ONAN. Babban ƙarfin lantarki shine 24GrdY / 13.8 * 12GrdY / 6.9 kV tare da kewayon tapping ± 2 * 2.5% (NLTC), ƙarfin lantarki na biyu shine 0.24 / 0.12 kV, sun kafa ƙungiyar vector na YNyn0.
Wannan 50 kVA guda 50- kushin kushin{2} da aka ɗora tasfoma an ƙirƙira shi don ingantaccen aiki mai inganci a cikin tsarukan rarraba wutar lantarki mai girma biyu{3}}, mai nuna 24GrdY/13.8 kV da 12GrdY/6.9 kV na farko tare da 0.24/0.12 kV. Tsare-tsaren kariyar sa mai ƙarfi ya haɗa da fis ɗin bayoneti da na yanzu{11}}iyakance fis don ingantaccen katsewar kuskure, tare da masu kamawa don kiyayewa daga masu wucewar wutar lantarki. Mai Gano Laifin Cikin Gida (IFD) yana ba da kulawa na gaske{13}}lokaci, yayin da mai zaɓin zaɓin wutar lantarki biyu{14} yana ba da damar canzawa tsakanin manyan ƙarfin lantarki na farko. Don sassauƙan aiki, kashewa{16}}mai canza maɓallan kewayawa yana ba da damar daidaitaccen daidaitawar wutar lantarki, kuma jujjuyawar ɗaukar nauyi tana tabbatar da keɓewar aminci yayin kulawa.
Ƙarin fasalulluka na aminci sun haɗa da na'urar taimako na matsa lamba don rage haɗarin wuce gona da iri na ciki da ma'aunin matakin mai don sa ido kan ruwan dielectric. An gina shi don dorewa da sauƙi na kulawa, wannan mai canzawa yana da kyau don amfani, kasuwanci, da aikace-aikacen masana'antu da ke buƙatar maganin rarraba wutar lantarki mai ƙarfi da daidaitawa.
1.2 Ƙayyadaddun Fasaha
50 kVA kushin da aka ɗora nau'in ƙayyadaddun bayanai da takaddun bayanai
|
Isarwa zuwa
Jamaica
|
|
Shekara
2024
|
|
Nau'in
Tashin wutar lantarki
|
|
Daidaitawa
IEEE StdC57.12.34-2022
|
|
Ƙarfin Ƙarfi
50 kVA
|
|
Yawanci
50HZ
|
|
Mataki
1
|
|
Ciyarwa
Madauki
|
|
Gaba
Matattu
|
|
Nau'in Sanyi
ONAN
|
|
Babban Voltage
24GrdY/13.8*12GrdY/6.9kV
|
|
Na biyu Voltage
0.24/0.12kV
|
|
Abubuwan Iska
Copper
|
|
Matsala ta kusurwa
Ii0
|
|
Impedance
4%
|
|
Matsa Canji
Farashin NLTC
|
|
Taɓa Range
±2*2.5%
|
|
Babu Asara Load
0.116 kW
|
|
Akan Rasa Load
0.445 kW
|
|
Na'urorin haɗi
Daidaitaccen Kanfigareshan
|
1.3 Zane
50kVA kushin da aka ɗora zane da girman hoto.
![]() |
![]() |
02 Masana'antu
2.1 Kori
Transformer yana fasalta ƙirar ci-gaban ƙwayar cuta ta toroidal, wanda aka gina daga ci gaba da rauni, mai girma -warewa, ƙaramin -asarar hatsi{2}}madaidaitan silin karfe tube don samar da rufaffiyar madauki{3}}tsarin madauki. Cibin raunin yana da cikakken amfani da halayen daidaitawar hatsi na karfen siliki, yana daidaita alkiblar maganadisu tare da alkiblar juyi, yayin da rufin da ke kan saman yana rage yawan asarar da ake yi a halin yanzu. Yana ba da fa'idodi masu mahimmanci, gami da ƙarancin ƙarancin nauyi - (raguwa 20-30% idan aka kwatanta da lamintattun abubuwan da aka gyara na gargajiya), aiki mai natsuwa, ingantaccen aiki (nau'in cika abin da ya wuce 95%), da ingantaccen ƙarfin injina.

2.2 Guda

Wannan taswira yana fasalta ƙirar iska mai haɗaɗɗiyar haɗa ƙananan foil{0}ƙarfin ƙarfin lantarki da babban ginin waya{1} don ingantaccen aiki. Ƙarƙashin 0.24/0.12kV -ƙarar ƙarfin wutar lantarki yana amfani da lebur ɗin tagulla wanda aka jera tare da takarda mai rufewa, yana ba da kyakkyawan gajeriyar ƙarfin kewayawa, ingantaccen watsar zafi, da ƙaƙƙarfan ƙira. Babban 24kV/12kV -madaidaicin wutar lantarki yana amfani da waya ta jan karfe zagaye/rectangular tare da rufaffiyar tsaka-tsaki, yana tabbatar da ingantaccen rarraba wutar lantarki, sassauƙan daidaitawa biyu{11}, da juriya na fitarwa. Wannan haɗin haɗin foil na jan karfe (LV) da waya ta jan ƙarfe (HV) yana ba da ingantaccen aiki tare da ƙarancin asarar eddy na yanzu, kwanciyar hankali mai ƙarfi don jure yanayin zafi da gajeriyar yanayi, da sarari{14}} ingantaccen fakitin da ya dace don kushin{15}} ɗora kayan aikin rarrabawa.
2.3 Tanko
Tankin na'ura mai canzawa yana da cikakken tsarin walda wanda aka gina daga 4{1}} 6mm high- faranti masu ƙanƙara masu inganci, waɗanda aka sarrafa ta hanyar fashewar yashi (Sa2.5 grade), yankan CNC (±0.5mm haƙuri), da waldar MAG mai sarrafa kansa. Yana ƙetare gwajin matsa lamba na 20kPa/30min, tare da hatimi biyu (rubber gasket + sealant) da bakin karfe don tabbatar da aikin hujja. Ana kula da saman da zafi mai zafi ({12}} tsoma tutiya mai zafi (Mafi girma ko daidai da 80μm) da fenti mai hana lalata Layer dual{13}. Tare da juriya na matsa lamba 100kPa da ƙimar lalata C5-M (ISO9001 bokan), ya cika duk buƙatun aikin hermetic na waje.

2.4 Taron Karshe

1. Tauraron Iska:Daidai hawa iskar HV/LV a kan jigon rauni, yana tabbatar da daidaitawar rufin da ta dace.
2. Haɗin Wutar Lantarki:Solder ko jujjuyawar kusoshi yana kaiwa ga masu canza famfo, bushings, da sauran madugu, sannan tabbatar da juriyar lamba.
3. Core -Bushewar Naɗi:Sanya sashin da aka haɗa a cikin tanda mai bushewa, yin amfani da injin motsa jiki da zafi don cire danshi har sai juriya na rufi ya dace da ma'auni.
4. Shigar Tanki:Yi amfani da kayan ɗagawa don saukar da busasshen sashin aiki a hankali cikin tanki, kiyaye shi don guje wa karo.
5. Shigar Na'ura:Shigar da bushings, bawul ɗin taimako na matsa lamba, IFD, mai kamewa, da dai sauransu, amfani da sealant zuwa saman gasket don zubewa{1}} hujja.
6. Ciko Mai & Tsayuwa:Cika da mai a ƙarƙashin vacuum zuwa ƙayyadadden matakin, gurɓataccen ruwa, kuma bari ya tsaya na awanni 24+ kafin gwaje-gwajen dielectric na ƙarshe da DGA.
03 Gwaji
|
A'a. |
Gwajin Abun |
Naúrar |
Dabi'un Karɓa |
Ƙimar Ma'auni |
Kammalawa |
|
1 |
Ma'aunin Juriya |
/ |
/ |
/ |
Wuce |
|
2 |
Gwajin Rabo |
/ |
Bambancin rabon ƙarfin lantarki akan babban tapping: ƙasa da ko daidai da 0.5% Alamar haɗi: Ii0 |
A:-0.03 B:-0.05 |
Wuce |
|
3 |
Gwajin polarity |
/ |
Ragewa |
Ragewa |
Wuce |
|
4 |
A'a -asara da tashin hankali na halin yanzu |
% kW |
I0 :: bayar da ma'auni darajar P0: ba da ƙima mai ƙima juriyar rashin hasara shine +10% |
0.35 0.095 |
Wuce |
|
5 |
Hasara mai ɗaukar nauyi, wutar lantarki mai ƙarfi, jimillar asara da inganci |
/ kW kW |
t:85 ku Z%: ƙimar da aka auna Pk: ƙimar ƙima Pt: ƙima mai ƙima haƙuri ga impedance shine ± 7.5% juriyar jimlar asarar kaya shine +6% |
4.28 0.432 0.527 99.23 |
Wuce |
|
6 |
Gwajin Karfin Wutar Lantarki |
/ |
LV: 10kV 60s |
Babu rushewar ƙarfin gwajin da ke faruwa |
Wuce |
|
7 |
Jarrabawar Juriya da Wutar Lantarki |
/ |
Wutar lantarki mai aiki (KV): 40 Duration(s): 40 Mitar (HZ): 150 |
Babu rushewar ƙarfin gwajin da ke faruwa |
Wuce |
|
8 |
Ma'aunin Resistance Insulation |
GΩ |
LV -HV zuwa Ground |
28.2 |
/ |
|
9 |
Gwajin Leaka |
/ |
Aiwatar da matsa lamba: 20kPA Tsawon lokaci: 12h |
Babu yabo kuma babu Lalacewa |
Wuce |
|
10 |
Gwajin Dielectric Oil |
kV |
Yafi ko daidai da 45 |
59.40 |
Wuce |


04 Shiryawa da jigilar kaya
4.1 Shiryawa
Tsarin marufi don kushin lokaci ɗaya{0}{1}} wanda aka ɗora tasfoma ya haɗa da tsaftacewa, kariya ta ciki, ƙarfafa waje, da lakabi. Na farko, ana tsaftace tafsirin da kyau, tare da duba matakan mai da hatimi; don sufuri, ana iya zubar da mai kuma a maye gurbin shi da busasshiyar nitrogen (0.02-0.03 MPa) don hana shigar da danshi, ko kuma a ajiye shi tare da rufe duk buɗe ido. A waje, ana amfani da ma'aunin girgiza (mantuna ko ƙwanƙwasa tushe) yayin da aka kiyaye mahimman abubuwan (bushings, IFD, da dai sauransu) tare da tasiri{8}}rufin juriya, kuma ana kula da saman ƙarfe da maganin tsatsa. Sa'an nan kuma an nannade naúrar a cikin fim ɗin filastik mai hana ruwa tare da hatimi (an inganta don jigilar ruwa). An cika kayan a cikin akwati na katako (tare da firgita{12}}kayan sha a ciki) daidai da bukatun sufuri. Ana haɗe alamar haske (nauyi, wuraren ɗagawa, haɗari) da takaddun (jerin tattarawa, rahotannin gwaji) an haɗa su, suna tabbatar da yarda da danshi{14}}hujja, abin girgiza, da ƙa'idodin IP56 don jigilar ruwa.

4.2 Shipping

Ana jigilar tasfofi guda ɗaya{0}}saidai{1} wanda aka ɗora ta hanyar jigilar ruwa a cikin kwantena a cikin jirgin ruwa ZIM SAMMY OFER (Voyage 8E) ƙarƙashin Bill of Lading 177PNBNBNL8580A, yana tashi daga Ningbo Chuanshan Port zuwa Jamaica. An adana shi a cikin akwati na 40'HC tare da ƙarfe{7}} itace anti- tushe mai rawar jiki da kumfa{9}}abubuwa masu mahimmanci, rukunin yana cike da busasshen nitrogen 0.02{11}}0.03MPa don rigakafin danshi kuma an lulluɓe shi da man tsatsa. Siffofin jigilar kayayyaki sun rufe{14}} sarrafa kwantena, sa ido na ainihin lokacin GPS, da saka idanu akan matsa lamba na nitrogen (Mafi girma ko daidai da 0.01MPa). Bayan isowa, dubawa sun haɗa da tabbatar da hatimin hatimi, gwajin gani, da gwaje-gwajen rufewa, tare da ƙaddamar da B/L da tattara hotuna don tabbatar da bin ƙa'idodin ruwa na ƙasa da ƙasa don kariyar danshi da girgiza.
05 Yanar Gizo da Takaitawa
A matsayin ginshiƙi na hanyoyin rarraba wutar lantarki, wannan -saitaccen pad{1} da aka ɗora tasfoma yana haɗa sabbin ƙira tare da ƙwararrun ƙwararrun ƙwararrun don sadar da amincin da bai dace da yanayin samar da wutar lantarki daban-daban ba. Tare da ƙaƙƙarfan tsarin sa, ingantaccen ƙarfin kuzari, da fasalin sa ido mai wayo na zaɓi, yana cika daidai buƙatun grids na zamani don aminci, tattalin arziki, da dorewar muhalli. Daga al'ummomin birane zuwa yankuna masu nisa, daga rarraba na al'ada zuwa haɗin gwiwar makamashi mai sabuntawa, mun himmatu wajen samar da mafi sauƙi, mafi aminci, da ƙarin dorewar hanyoyin lantarki ta wannan samfurin da aka ƙera. Zaɓin na'urar tamu yana nufin saka hannun jari a nan gaba mai dogaro da makamashi.

Hot Tags: guda fanti kushin saka rarraba rarrabawa, manufacturer, maroki, farashin, farashi
You Might Also Like
50 kVA Kushin Haɗa Mai Canjawa-24.94 / 0.24 * 0.12 k...
100 kVA Kushin Dutsen Mai Canjawa-24 / 0.24 kV|Jamai...
167 kVA Kushin Dutsen Mai Canjawa-24 * 12 / 0.24 kV|...
400 kVA Padmount Transformer-23 / 0.4 kV|Chile 2024
2500 kVA Kushin Haɗa Mai Canjawa-13.2 / 0.48 kV|Kana...
630 kVA Nau'in Busassun Nau'in Rubutun Mataki na Uku...
Aika Aikace-aikacen