167 kVA Kushin Dutsen Mai Canjawa-24 * 12 / 0.24 kV|Jamaica 2024

167 kVA Kushin Dutsen Mai Canjawa-24 * 12 / 0.24 kV|Jamaica 2024

Kasar: Jamaica 2024
Yawan aiki: 167kVA
Wutar lantarki: 24/13.8-0.24kV
Siffar: Dual{0}}maɓallin zaɓin wutar lantarki
Aika Aikace-aikacen

 

 

167 kva pad mount transformer

Ƙirƙirar fasaha tare da ingantaccen inganci{0}}yana bayyana sabon zamanin hanyoyin magance wutar lantarki.

 

01 Gabaɗaya

1.1 Fagen Aikin

SCOTECHya yi farin cikin samar da mafi ingancin 167 kva pad mount don sabis na Jama'a na Jamaica. Nasarar isar da wannan rukuni na babban{3}}ararrawa Single Phase Pad Mounted transformers alama ce ta ci gaban da kamfanin ya samu zuwa kasuwar Transformer ta duniya kuma yana nuna kyawunsa a cikin ƙirƙira da sarrafa inganci. Za a yi amfani da tasfoman da aka isar da su sosai a wasu ayyukan samar da ababen more rayuwa, da suka hada da inganta wutar lantarki a birane, inganta wutar lantarki a yankunan karkara, da tallafin wutar lantarki a wuraren kasuwanci. Abokin ciniki ya yi magana sosai game da isarwa, yana yaba ƙwararrun SCOTECH da ingancinsa.

Nau'in wutar lantarki guda ɗaya - yana da ƙarfin 167kVA, babban ƙarfin lantarki shine 24GrdY/13.8kV da 12GrdY/6.9kV kuma ƙaramin ƙarfin lantarki shine 0.12/0.24kV, wanda zai iya biyan buƙatun wutar lantarki cikin sauƙi. Transformer yana ɗaukar ƙirar wutar lantarki guda biyu kuma yana buƙatar amfani da na'ura mai jujjuya wutar lantarki guda biyu don sauyawar wutar lantarki. Wannan ƙira yana tabbatar da cewa mai canzawa zai iya daidaitawa da buƙatun wutar lantarki daban-daban, ta haka yana haɓaka aiki da daidaitawa. Thekushin saka taransifomaisar da wannan lokacin ana amfani da su sosai a cikin hanyoyin rarraba wutar lantarki na birni da ƙauye tare da inganci mai inganci da inganci. An ƙirƙira wannan jerin na'urorin taswira tare da daidaita yanayin muhalli da kwanciyar hankali na dogon lokaci a zuciya, da tabbatar da ingantaccen aiki koda a cikin matsanancin yanayi. SCOTECH za ta ci gaba da mai da hankali kan kirkire-kirkire na fasaha, inganta ingancin kayayyaki da fadada kason kasuwancinta na kasa da kasa. Kamfanin ya ce ba zai yi kasa a gwiwa ba wajen inganta ci gaban fasaha na masana'antun samar da wutar lantarki da kuma taimakawa dauwamammen ci gaban makamashi a duniya.

 

 

1.2 Ƙayyadaddun Fasaha

167 kva kushin Dutsen transformer takamaiman nau'in da takardar bayanai

Isarwa zuwa
Jamaica
Shekara
2024
Nau'in
Tashin wutar lantarki
Daidaitawa
IEEE
Ƙarfin Ƙarfi
167 kVA
Ciyarwa
Madauki
Gaba
Matattu
Iska
Copper
Polarity
Ragewa
Yawanci
50HZ
Mataki
1
Nau'in Sanyi
ONAN
Babban Voltage
24GrdY/13.8-12GrdY/6.9kV
Biyu Primary Voltage
Ee
Na biyu Voltage
0.24 / 0.12 kV
Abubuwan Iska
Copper
Ƙungiyar Vector
Ii0
Impedance
4%
Matsa Canji
Farashin NLTC
Liquid Insulant
Ma'adinan Mai
Taɓa Range
±2*2.5%
Babu Asara Load
0.332 kW
Akan Rasa Load
1.115 kW
Hakuri
10% NLL, 6% Jimlar Asara
Na'urorin haɗi
Daidaitaccen Kanfigareshan

 

1.3 Zane

167 kva kushin Dutsen Taswira zane da girman zane.

167 kva pad mount transformer drawing 167 kva pad mount transformer nameplate

 

 

02 Masana'antu

2.1 Kori

An karɓi babban ingantaccen aiki da ƙirar ƙirar ƙirar coil core. An raunata ƙirar ƙirar coil ɗin tare da ingantacciyar jagorancin maganadisu na madaidaiciyar takardar silicon karfe, wanda ke ba da cikakkiyar wasa ga kyakkyawan aikin takardar siliki mai daidaitacce. Juyawar da'irar maganadisu karami ne, don haka babu -asara da babu{3}} load current sun fi na laminated iron core (na laminated iron core zai sami murdiya na maganadisu saboda lamintin haɗin gwiwa). Domin ana ci gaba da jujjuya tushen coil ɗin ta kayan ƙarfe na siliki, idan aka kwatanta da ƙwanƙolin shear, a ƙarƙashin yanayi ɗaya, babu{5}}asara na coil core ana iya ragewa da kashi 30%; Amo yana daidai da ƙasa. Dangane da samarwa, core winding na iya amfani da sirara mai girma -permeability Magnetic sanyi- mirgina madaidaiciyar takardar silicon karfe don samar da ƙananan asarar matsi mai canzawa, core winding ba ya yanke sharar gida, amma kuma ana iya aiki da injina, don haka ingancin samarwa yana da girma. Gabaɗaya, jigon raunin yana da fa'idodi na haɓakawa mai girma, ƙarancin asara, ƙaramar amo, gajeriyar juriya mai ƙarfi da daidaito mai kyau.

167 kva pad mount transformer silicon steel iron core

 

2.2 Guda

167 kva pad mount transformer copper winding

Zane-zanen wayoyi na gidan wuta na Amurka guda ɗaya - yana rage tsawon ƙarancin layin rarraba wutar lantarki, yana rage asarar layi kuma yana haɓaka ingancin samar da wutar lantarki; Rage ƙananan radius - ƙarfin lantarki, na iya rage asarar layin fiye da 60%. Ana yin jujjuyawar iska mai ƙarfi da ƙarancin ƙarfi da jan ƙarfe.

 

2.3 Tanko

An yanke tankin mai, an buge shi kuma an lanƙwasa ta hanyar kayan sarrafa lambobi don tabbatar da daidaiton aiki. Surface electrostatic spray magani, 30 shekaru ba cire fenti. Majalisar ministocin ta ɗauki ƙirar ƙira, wanda ke sauƙaƙe haɗin igiyoyi da abubuwan lantarki. Har ila yau, majalisar ministocin tana da ƙira iri-iri don saduwa da na'urar kariya da sauya tsarin. Mai canzawa yana ɗaukar cikakken tsarin da aka rufe, ƙarfin yin nauyi mai ƙarfi, babban abin dogaro a cikin ci gaba da aiki da sauƙi mai sauƙi.

167 kva pad mount transformer oil tank with clamshell design

 

2.4 Taron Karshe

167 kva pad mount transformer active part
inside of 167 kva pad mount transformer

 

 

03 Gwaji

A'a.

Gwajin Abun

Naúrar

Dabi'un Karɓa

Ƙimar Ma'auni

Kammalawa

1

Ma'aunin Juriya

/

/

/

Wuce

2

Gwajin Rabo

/

Bambancin rabon ƙarfin lantarki akan babban tapping: ƙasa da ko daidai da 0.5%

Alamar haɗi: Ii0

A:0.00

B:0.00

Wuce

3

Gwajin polarity

/

Ragewa

Ragewa

Wuce

4

A'a -asara da tashin hankali na halin yanzu

%

kW

I0 : bayar da ma'auni darajar

P0: ba da ƙima mai ƙima

juriyar rashin hasara shine +10%

0.17

0.235

Wuce

5

Hasara mai ɗaukar nauyi, wutar lantarki mai ƙarfi, jimillar asara da inganci

/

kW

kW

t:85 ku

Z%: ƙimar da aka auna

Pk: ƙimar ƙima

Pt: ƙima mai ƙima

haƙuri ga impedance shine ± 10%

juriyar jimlar asarar kaya shine +6%

3.74

1.146

1.381

99.41

Wuce

6

Gwajin Karfin Wutar Lantarki

/

LV: 10kV 60s

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

7

Jarrabawar Juriya da Wutar Lantarki

/

Wutar lantarki mai aiki (kV): 40

Duration(s): 40

Mitar (HZ): 150

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

8

Ma'aunin Resistance Insulation

GΩ

LV -HV zuwa Ground

18.9

/

9

Gwajin Leaka

/

matsa lamba: 20kPA

Tsawon lokaci: 12h

Babu yabo kuma babu

Lalacewa

Wuce

10

Gwajin Dielectric Oil

kV

Yafi ko daidai da 45

56.11

Wuce

 

167 kva pad mount transformer testing
Leakage Test of 167 kva pad mount transformer

 

 

04 Shiryawa da jigilar kaya

167 kva pad mount transformer wood packing

167 kva pad mount transformer shipping

 

05 Yanar Gizo da Takaitawa

Theguda -saitaccen pad{1}}wanda aka ɗora wutar lantarki, tare da babban abin dogaronsa, makamashi{0}fasalan adanawa, da ƙira iri-iri wanda ya dace da mahalli daban-daban, shine mafi kyawun zaɓi don tsarin rarraba wutar lantarki. Ko a cikin ci gaban birane, tashoshin wutar lantarki na karkara, ko aikace-aikacen kasuwanci da masana'antu, yana ba da ingantaccen tallafi na wutar lantarki. Zaɓin guda ɗaya{3}}saitin kushin- wanda aka ɗora tasfoma ba kawai mahimmin mataki ba ne don inganta ingantaccen samar da wutar lantarki amma kuma zaɓi mai hikima don gina amintaccen, eco{5}, da tsarin wutar lantarki mai dorewa!

167 kva single pad mount transformer supplier

 

Hot Tags: 167 kva kushin Dutsen Transformer, Manufacturer, maroki, farashin, farashi