500 KVA Utility Transformer Pad-34.5/0.48 KV|Amurka 2025

500 KVA Utility Transformer Pad-34.5/0.48 KV|Amurka 2025

Kasar: Amurka 2025
Yawan aiki: 500kVA
Wutar lantarki: 34.5GrdY/19.92-0.48 kV
Siffar: tare da mai FR3
Aika Aikace-aikacen

Jiangshan Scotech Electric Co., Ltd yana ɗaya daga cikin amintattun masana'anta kuma masu samar da kushin wutar lantarki 500 kva{6}}34.5/0.48 kv|Amurka 2025 in China. Da fatan za a ji kyauta don siyan kayayyaki masu inganci don siyarwa anan kuma ku sami zane-zane daga masana'anta. Tuntube mu don ƙarin bayani.

 

utility transformer pad

Sauƙaƙe grid ɗinku, ƙara girman sararin ku - na'ura mai ɗaukar wuta, ingantaccen tushe na ƙarfi.

 

 

01 Gabaɗaya

1.1 Bayanin Aikin

500 kVAuku fase kushin saka transformerAn isar da shi zuwa Amurka a cikin 2025. Ƙarfin wutar lantarki na wutar lantarki shine 500 kVA tare da sanyaya KNAN. Babban ƙarfin lantarki shine 34.5GrdY / 19.92 kV tare da ± 2 * 2.5% tapping range (NLTC), ƙananan ƙarfin lantarki shine 0.48 kV, sun kafa ƙungiyar vector na YNd1.

Wannan 500kVA guda uku -saitin kushin{2}} wanda aka ɗora shi an kera shi musamman don aikace-aikacen rarrabawa a waje a Arewacin Amurka da sauran kasuwanni masu buƙata. Yana ba da ƙaƙƙarfan sawun ƙafa da amintaccen matsakaicin-ƙarfin wutar lantarki zuwa canjin wutar lantarki mai ƙarancin ƙarfi, yana mai da shi kyakkyawan zaɓi don rukunin kasuwanci, wuraren shakatawa na masana'antu, rukunin gidaje, da hanyoyin sadarwar jama'a.

Babban ƙirar lantarki tare da ƙungiyar vector YNd1.
Kushin wutar lantarki mai amfani yana ɗaukar ƙungiyar vector YNd1, tare da haɗe-haɗe da tauraro mai girman ƙarfin lantarki da kuma keɓaɓɓen da aka fito da shi (H0). Wannan saitin yana ba da zaɓuɓɓukan tsarin ƙasa masu sassauƙa. Haɗin low-voltage delta yana haifar da rufaffiyar hanya don magudanar ruwa-jeri-sifili, yadda ya kamata yana murkushe masu jituwa tare da haɓaka ƙarfin injin na'ura don ɗaukar kaya marasa daidaituwa. An haɗa fis ɗin Cooper masu inganci a gefe na farko, suna ba da ingantaccen kariyar wuce gona da iri ta hanyar ware kurakurai cikin sauri.

Tsarin insulating da sanyaya mai dacewa da muhalli (KNAN / FR3).
Hanyar sanyaya shine KNAN (convection na halitta ta amfani da ruwa mara ƙonewa). Na'urar taswira tana cike da ruwan ester na halitta na FR3 - mai sabuntawa, dielectric mai lalacewa da aka samu daga mai. FR3 yana da madaidaicin walƙiya sama da digiri 300, yana haɓaka amincin wuta sosai idan aka kwatanta da mai na ma'adinai na al'ada. Matsayinsa mai kyau na danshi (425 ppm jikewa a -20 digiri vs. kawai ~ 8 ppm don man ma'adinai) yana rage haɗarin rashin lalacewa. Bugu da ƙari, FR3 yana ba da damar yin aiki mai girma har zuwa 20% mafi girma ba tare da sadaukar da rayuwa ko aminci ba. An tabbatar da mafi girman ƙarfinsa na dielectric da juriyar tsufa a cikin miliyoyin na'urorin rarrabawa a duniya.

Yarda da ƙa'idodin ingancin DOE.
Na'urar taswira ta cika daidai da sabbin buƙatun ingancin Ma'aikatar Makamashi ta Amurka (DOE). Ana sarrafa asarar da ke ƙarƙashin ƙayyadaddun yanayin kaya zuwa matakin jagorancin masana'antu, yana taimaka wa abokan ciniki cimma tanadin makamashi da rage fitar da iskar carbon.

Tare da ƙirar wutar lantarki ta ci gaba, eco-friendly da wuta mai aminci FR3 ruwa, fuses Cooper mai inganci, da tsananin yarda da ƙa'idodin ingancin DOE, wannan mai ɗaukar kushin 500kVA shine amintaccen bayani don ayyukan rarraba wutar lantarki da yawa.

 

 

 

1.2 Ƙayyadaddun Fasaha

500 kVA nau'in nau'in kushin mai amfani da kayan aiki da takaddun bayanai

Isarwa zuwa
Amurka
Shekara
2025
Nau'in
Tashin wutar lantarki
Daidaitawa
IEEE Std C57.12.34-2022 DOE 2016
Ƙarfin Ƙarfi
500 kVA
Yawanci
60HZ
Mataki
3
Ciyarwa
Madauki
Gaba
Matattu
Nau'in Sanyi
KNAN
Babban Voltage
34.5GrdY/19.92 kV
Na biyu Voltage
0.48 kV
Abubuwan Iska
Aluminum
Ƙungiyar Vector
YNd1
Impedance
5.75%
inganci
99.35%
Matsa Canji
Farashin NLTC
Taɓa Range
±2*2.5%
Babu Asara Load
0.73 kW
Akan Rasa Load
4 kW

 

1.3 Zane

500 kVA mai amfani mai canza canji zane da girman zane.

utility transformer pad diagram utility transformer pad nameplate

 

 

02 Masana'antu

2.1 Kori

utility transformer pad core

Kushin mai amfani da wutar lantarki yana ɗaukar ginshiƙi guda uku - da aka gina daga ƙarfe mai ƙarfi{2}madaidaicin siliki, wanda yayi daidai da ƙarfin 500kVA kuma an tsara shi daidai da IEEE C57.12.34-2022. Aunawa babu-nauyi asarar shine kawai 701W (tabbacin 730W) kuma halin yanzu mai ban sha'awa shine 0.38%, duka biyun sun fi daidaitattun buƙatu, suna tabbatar da ingantaccen yanayin da'ira da ƙarancin hasara. A lokacin masana'antu, ana amfani da matakan madaidaicin madaidaicin ma'auni tare da tsauraran matakan haɗin gwiwa da matsa lamba; Ana tabbatar da kowace cibiya ta gwajin babu-nauyi kafin taro, yana tabbatar da daidaiton aiki da aminci a duk raka'a.

 

2.2 Guda

Ana yin iska da aluminium mai inganci tare da ƙungiyar vector YNd1, kuma bushing H0 a gefen babban ƙarfin lantarki an fito da shi daban don sauƙaƙe ƙasa mai tsaka tsaki ko saka idanu, daidaitaccen buƙatun tsarin. Ana kashe maɓalli (NLTC) tare da matakan ± 2 × 2.5%, wanda ya dace da IEEE C57.12.34-2022. Ma'auni ma'auni kewayo daga -0.04% zuwa 0.00% (mafi kyau fiye da ± 0.5% haƙuri), matsakaicin juriya rashin daidaituwa akan ƙaramin ƙarfin lantarki shine 2.21% (da kyau a cikin ƙarancin ƙarancin ko daidai da 4%), kuma gwajin alaƙa na lokaci yana tabbatar da haɗin YNd1 daidai. Ana amfani da injunan iska mai sarrafa kansa tare da sarrafa tashin hankali na ainihin lokaci, sannan bushewa da kyau kafin taro, yana tabbatar da jujjuyawar juzu'i da ƙarfin injina.

utility transformer pad winding

 

2.3 Tanko

utility transformer pad tank with KNAN cooling

An rufe tanki cikakke, yana amfani da sanyaya KNAN (zazzagewar mai na yanayi, sanyaya iska), kuma yana cike da babban wuta-maki FR3 na ester ruwa na halitta - abokantaka na muhalli da wuta, mai dacewa da shigarwa na waje da ka'idojin IEEE. Gwajin zubewa tare da matsa lamba 20kPa na tsawon awanni 24 ya nuna babu yabo ko nakasar dindindin. Ƙirar haɓakar zafin jiki ya haɗu da matsakaita hawan iska Kasa da ko daidai da digiri 65 da hawan mai ƙasa da ko daidai da digiri 65. Dukkanin waldar tanki ana dubawa 100% ta hanyar mai shigar da ruwa ko X-ray, kuma kowane tanki ana gwada shi kafin taro na ƙarshe. Ana samar da na'urar taimakon matsa lamba na nau'in zobe don ƙarin aminci.

 

2.4 Taron Karshe

Cikakken taron ya haɗa da ɓangarorin farko na matattu, ma'aunin matsa lamba, bawul ɗin taimako na matsa lamba, bawul ɗin magudanar mai tare da bawul ɗin samfur, da filogi mai cike da sama, duk an ajiye su a cikin majalisar kulawar tamper ta NEMA 3R. Kariyar mai mahimmanci tana amfani da fuses Cooper masu inganci. Majalisar ta wuce gwajin ƙarfin lantarki da aka yi amfani da shi (10kV akan gefen LV na tsawon daƙiƙa 60, babu raguwa), ƙarfin jurewar gwajin da aka haifar (69kV akan gefen HV a 150Hz don 48 seconds, babu raguwa), da ma'aunin juriya (HV‑LV zuwa ƙasa: 2.58GΩ, HV&LV zuwa ƙasa: 1.76GΩ: 1.76GΩ) Kowane tafsirin da aka haɗe yana yin cikakken gwajin yau da kullun (ragi, polarity, asara, dielectric, da sauransu) kafin jigilar kaya.

utility transformer pad active part

 

 

03 Gwaji

Dukkan gwaje-gwaje ana yin su daidai gwargwadon IEEE C57.12.90-2021, tare da rahoton gwaji No{1}} kwanan wata 2026-04-20. Mahimman ƙididdiga masu mahimmanci: asarar nauyi 701W (garanti 730W), asarar kaya a 85 digiri 3,529W (tabbacin 4,000W), gajeren lokaci impedance 5.49% (haƙuri ± 7.5% na 5.75%), ko dacewa 99. 99.35%). Matsakaicin rabo tsakanin -0.04% da 0.00%; matsakaicin juriya rashin daidaituwa shine 2.21%; dangantakar lokaci daidai YNd1. Gwajin wutar lantarki da aka yi amfani da shi (10kV/60s), gwajin ƙarfin lantarki da aka jawo (69kV/150Hz/48s), da gwajin yatsa na tsawon awanni 24 (20kPa) duk an wuce su ba tare da wata matsala ba. Ƙimar juriya na rufi sun fi 1.7GΩ. Gwaje-gwaje na yau da kullun da nau'in zaɓi (juriya, hawan zafin jiki, motsa jiki, da sauransu) suna nuna cikakken cewa wannan taswira yana da ingantaccen dogaro da gefe, cikakke mai yarda da grid ta Arewacin Amurka da buƙatun ingancin makamashi na DOE.

 

 

04 Shiryawa da jigilar kaya

4.1 Shiryawa

Shiryawa ya ƙunshi tushe na skid na katako, tarpaulin mai hana ruwa, da ɗaurin ƙarfe, wanda ya dace da jigilar ruwa da na ƙasa, biyan buƙatun fitarwa don danshi da kariyar girgiza (daidai da IP23). Dukkan tashoshi da aka fallasa ana bi da su tare da murfin anti-tsatsa, kuma na'urorin haɗi an cika su daban-daban tare da cikakken lissafin tattarawa. Ana yin duban gani na ƙarshe da takaddun hoto kafin shiryawa don tabbatar da rashin tsatsa ko lalacewa akan karɓar abokin ciniki.

 

4.2 Shipping

Ana iya jigilar na'urar ta hanyar mota ko a cikin kwantena, tare da shirin ɗaukar akwati mai tsayi 40ft akan buƙata. Abubuwan da aka fi so na tashi sune Ningbo ko Shanghai. Cikakken fakitin takaddun ya haɗa da rahoton gwaji, takardar shedar daidaito, jagorar shigarwa, zane-zane, da hotunan farantin suna. Ana samun kulawar lodi na ɓangare na uku idan an buƙata. Ana iya gano duk bayanan dabaru, kuma ana ba da tallafin kwastam na fitarwa don rage haɗarin isarwa.

 

 

05 Taƙaitaccen

Wannan 500kVA na'ura mai ɗaukar hoto mai hawa uku ya cika ko wuce ƙa'idodin IEEE da buƙatun ingancin DOE a ƙira, masana'anta, da gwaji. Haɗin YNd1 tare da keɓaɓɓen da aka kawo H0 bushing yana ɗaukar hanyoyi daban-daban na tsarin ƙasa; KNAN sanyaya tare daRuwan ester na halitta FR3yana ba da abokantaka na muhalli da amincin wuta; da Cooper fuses tabbatar da abin dogara kariya. Ƙimar da aka auna na 99.40%, tare da hasara mara nauyi, asarar nauyi, da rashin ƙarfi duk mafi kyau fiye da ƙimar da aka tabbatar, yana tabbatar da kyakkyawan aiki. Kowane mataki daga tushe da iska zuwa taro, gwaji, tattarawa, da jigilar kaya yana ƙarƙashin ingantattun kulawar inganci. Wannan taswirar ta dace da aikace-aikacen waje a Arewacin Amurka da na duniya 34.5kV cibiyoyin rarrabawa, wuraren shakatawa na masana'antu, cibiyoyin kasuwanci, da tashoshin caji na EV - yana ba da aminci, inganci, kuma amintaccen aiki na dogon lokaci.

utility transformer pad with IEEE standards

 

Hot Tags: kushin wutar lantarki mai amfani, masana'anta, mai kaya, farashi, farashi

Aika Aikace-aikacen