500 KVA Menene Mai Canjawa Mai Sauƙi-12.47 / 0.6 KV|Kanada 2024
Yawan aiki: 500kVA
Wutar lantarki: 12.47Grdy/7.2 X 4.16Grdy/2.4-0.6y/0.347 kV
Feature: Tare da IFD

Dogaro, inganci, kuma amintaccen ƙarfi tare da kushin kVA ɗin mu 500 -samar da wutar lantarki, yana isar da tsayayyen wutar lantarki na lokaci uku{2} don kasuwanci, wurin zama, da amfanin masana'antu
01 Gabaɗaya
1.1 Bayanin Aikin
A cikin 2024, SCOTECH ya kawo 500 kVA guda uku -kushin lokaci{3}} wanda aka ɗora shi zuwa Kanada. An yi shi bisa ga CSA C227.4:21 kuma an gina shi don ingantaccen amfani da wutar lantarki a gine-ginen kasuwanci, gidaje, da ƙananan masana'antu.
Kushin da aka ɗora{0}Transfoma nau'in na'ura ce ta rarrabawa da aka girka a matakin ƙasa akan siminti. An rufe shi sosai kuma yawanci yana da mataccen ƙira ta gaba. Wannan yana adana manyan sassan wutar lantarki{4} a cikin ma'ajiya ta kulle. Yana kare jama'a da ma'aikatan amfani. Hakanan yana ba da damar sauƙi don kiyayewa. Naúrar tana da ƙulli da aka ɗora - ƙira kuma an sanya shi a kan siminti don amintaccen amfani a waje. Yana canza matsakaicin ƙarfin lantarki (12.47 / 4.16 kV) zuwa ƙananan ƙarfin lantarki (0.6 kV) kuma yana ba da ƙarfi da ingantaccen ƙarfi ga masu amfani.
Yana da tsarin kwantar da hankali na ONAN tare da rufin mai mai ma'adinai, yana ba da kyakkyawan yanayin zafi da kuma tsawon rayuwar sabis. Transformer yana aiki a 12.47 / 4.16 kV a gefen farko da 0.6 kV a gefen sakandare. Yana amfani da ƙungiyar vector YNyn0 don kiyaye daidaiton ƙarfin lokaci uku{6}. Yana da aluminium windings, 5% impedance, da kuma 99.5% inganci. Yana aiki tare da ƙananan asara kuma yana riƙe ƙarfin lantarki a tsaye ƙarƙashin cikakken kaya.
1.2 Ƙayyadaddun Fasaha
500kVA uku lokaci kushin saka gidan wuta ƙayyadaddun bayanai da takardar bayanai
|
Isarwa zuwa
Kanada
|
|
Shekara
2024
|
|
Nau'in
Uku fanni kushin Dutsen transformer
|
|
Daidaitawa
CSA C227.4:21
|
|
Ƙarfin Ƙarfi
500KVA
|
|
Yawanci
60HZ
|
|
Ciyarwa
Madauki
|
|
Gaba
Matattu
|
|
Mataki
uku
|
|
Nau'in Sanyi
ONAN
|
|
Liquid insulant
Ma'adinan Mai
|
|
Babban Voltage
12.47 (4.16) kV
|
|
Na biyu Voltage
0.6 kV
|
|
Ƙungiyar Vector
YNyn0
|
|
Abubuwan Iska
Aluminum
|
|
Impedance
5%
|
|
inganci
99.5%
|
|
Matsa Canji
Farashin NLTC
|
|
Taɓa Range
±2*2.5%
|
|
Babu Asara Load
Kasa da ko daidai da 1090 W
|
|
Akan Rasa Load
Kasa da ko daidai da 5800 W
|
|
Na'urorin haɗi
Daidaitaccen Kanfigareshan
|
1.3 Zane
500kVA uku lokaci kushin saka tasfofi zane da sunan farantin
![]() |
![]() |
02 Masana'antu
2.1 Kori
Ƙirar kafa guda biyar - tana ba da babban goyan baya da ma'auni. Yana taimakawa rage zubewar ruwa da gajeriyar damuwa ta kewayawa. Wannan tsarin yana sa na'ura mai taswira lafiya, karko, kuma mai ɗorewa, koda lokacin yana aiki cikin nauyi mai nauyi ko yanayin waje.
2.2 Guda
Musamman don daidaitawar YNyn0, ma'aikata suna ba da kulawa ta musamman ga ma'aunin tsaka-tsaki da ma'aunin lokaci yayin iska don tabbatar da ma'auni guda uku{1} da gajeriyar juriyar kewayawa. Ƙaƙƙarfan ƙira mai jujjuyawa yana rage hasara yayin da yake riƙe mafi kyawun zafin jiki.
2.3 Tanko

An rufe tankin mai canzawa da murfin da aka kulle kuma an yi shi da ƙarfe mai laushi. Yana iya ɗaukar matsa lamba na ciki na 50 kPa ba tare da wani yatsa ba ko nakasar dindindin fiye da 0.25% na diagonal na saman. An tsara majalisar don zama mai juriya da juriya. Ana amfani da ƙwanƙwasa ƙwanƙwasa pentahead daidai da buƙatun CSA C227.4.
2.4 Taron Karshe
Muna bin daidaitattun hanyoyin aiki, muna ba da cikakken jagora ga kowane mataki na haɗuwa da transfoma da rage rashin tabbas na aikin hannu. Haɗe tare da ƙwararrun tsarin haɓaka ƙungiyar, ta hanyar horo na tsari da ƙwararrun ƙwararru, muna tabbatar da cewa kowane ma'aikaci yana da ikon aiwatar da babban aiki mai girma{2}. Wannan cikakkiyar haɗin tsari da mutane sune tushen tushen ingancin samfuran mu mafi tsayi.
03 Gwaji
Matsayin Gwaji da Gwajin Na yau da kullun
|
Saukewa: CSA227.4-21 |
Uku -, pad - ɗora tasfoma masu rarrabawa tare da keɓance manyan haɗe-haɗe masu ƙarfi{2} |
|
CSA{0}C802.1-13 (R2022) |
Ƙimar Ƙarfin Ƙarfi don Liquid{0}}Cikakken Masu Canza Rarraba |
1. Ma'aunin Juriya
2. Gwajin Rabo
3. Gwajin Dangantakar Mataki
4. Babu Asara Load Kuma Babu Load A Yanzu
5. Load asarar Impedance ƙarfin lantarki da inganci
6. Gwajin Karfin Wutar Lantarki
7. Gwajin Juriya da Ƙarfin Wutar Lantarki
8. Gwajin Leak tare da Matsi don Masu Canjin Ruwa na Immersed
9. Ma'aunin Juriya na Insulation
10. Gwajin Dielectric Oil
Sakamakon Gwaji


|
|
Gwajin Abun |
Naúrar |
Karba Darajoji |
Ƙimar Ma'auni |
Kammalawa |
|
1 |
Ma'aunin Juriya |
% |
Matsakaicin juriya rashin daidaituwa |
1.27 |
Wuce |
|
2 |
Gwajin Rabo |
% |
Bambancin rabon ƙarfin lantarki akan babban tapping: ƙasa da ko daidai da 0.5% |
-0.04-0.10 |
Wuce |
|
3 |
zango{0}}gwajin dangantaka |
/ |
YNyn0 |
YNyn0 |
Wuce |
|
4 |
A'a -asara da tashin hankali na halin yanzu |
/ |
I0 :: bayar da ma'auni darajar |
0.37% |
Wuce |
|
P0: ba da ƙima mai ƙima |
0.7317 kW |
||||
|
juriyar rashin hasara shine +10% |
/ |
||||
|
5 |
Load asarar impedance ƙarfin lantarki da inganci |
/ |
t:85 ku haƙuri ga impedance shine ± 7.5% juriyar jimlar asarar kaya shine +6% |
/ |
Wuce |
|
Z%: ƙimar da aka auna |
5.35% |
||||
|
Pk: ƙimar ƙima |
4.483 kW |
||||
|
Pt: ƙima mai ƙima |
5.247 kW |
||||
|
Ingancin ba kasa da 99.05% |
99.29% |
||||
|
6 |
Gwajin Karfin Wutar Lantarki |
kV |
HV: 34kV 60s LV: 10kV 60s |
Babu rushewar ƙarfin gwajin da ke faruwa |
Wuce |
|
7 |
Jarrabawar Juriya da Wutar Lantarki |
kV |
Wutar lantarki mai aiki (KV): 2 Ur |
Babu rushewar ƙarfin gwajin da ke faruwa |
Wuce |
|
Duration(s):30 |
|||||
|
Mitar (HZ): 240 |
|||||
|
8 |
Gwajin Leaka |
kPa |
matsa lamba: 20kPA Tsawon lokaci: 12h |
Babu yabo kuma babu Lalacewa |
Wuce |
|
9 |
Ma'aunin Resistance Insulation |
GΩ |
LV -HV zuwa Ground |
7.8 |
/ |
|
HV&LV zuwa Ground |
8.0 |
||||
|
10 |
Gwajin Mai |
/ |
Ƙarfin Dielectric; |
51,8 kv |
Wuce |
|
Abubuwan Danshi |
11.5 mg/kg |
||||
|
Factor Dissipation |
0.00298% |
||||
|
Furan Analysis |
Kasa da ko daidai da 0.1 |
||||
|
Gas Chromatography Analysis |
/ |
04 Shiryawa da jigilar kaya



05 Yanar Gizo da Takaitawa

500 kVA uku -kushin lokaci - da aka ɗora tafsiri yana ba da ingantaccen ƙarfi da ingantaccen ƙarfi ga cibiyoyin rarraba Kanada. Ya dace da ma'aunin CSA C227.4:21. Transformer yana da ƙaƙƙarfan cibiya mai ƙarfi guda biyar{7} da madaidaicin iskar aluminum. Tankin an rufe shi kuma yana hana yanayi. ƙwararrun ma'aikata suna haɗa kowace ƙungiya a hankali. Na'urar taswira tana kiyaye daidaiton ƙarfin lokaci uku{11} kuma yana gudana tare da ƙarancin asara. Yana amfani da sanyaya ONAN kuma yana ba da ingantaccen ƙarfin lantarki ƙarƙashin cikakken kaya.
Hot Tags: menene pad mounted transformer, manufacturer, maroki, farashi, farashi
You Might Also Like
75 kVA Pad Dutsen-23 / 0.208 kV|Amurka 2025
1000 kVA Matsakaicin Kushin Gida Mai Canzawa-22.86 /...
300 kVA Mai Cika Mai Sauƙi-13.2 / 0.48 kV|Guyana 2024
2000 kVA Kushin Dutsen Mai Canjawa-25 / 0.6 kV|Kanad...
300 KVA Kushin Haɓaka Gidan Wuta-12.47*4.16/0.208 KV...
500 KVA Radial Feed Transformer-12.47*4.16/0.6 KV|Ka...
Aika Aikace-aikacen