Akwatin wutar lantarki 500 kVA - 12.47 * 4.16 / 0.208 kV|Kanada 2024

Akwatin wutar lantarki 500 kVA - 12.47 * 4.16 / 0.208 kV|Kanada 2024

Ƙasar Bayarwa: Kanada 2024
Yawan aiki: 500kVA
Wutar lantarki: 12.47Grdy/7.2 X 4.16Grdy/2.4-0.208y/0.12 kV
Feature: Tare da IFD
Aika Aikace-aikacen

 

500 kva electric transformer box-internal-compartment

Dogaro da ingantaccen ƙarfi don hanyoyin sadarwar Kanada tare da kushin kVA ɗin mu 500 -samar da na'urorin wutar lantarki, an gina su don dorewa da aiki mai ƙarfi biyu{2}}

 

 

01 Gabaɗaya

1.1 Bayanin Aikin

A cikin 2024, abokin ciniki na Kanada ya karɓi kVA 500akwatin wutan lantarki, ƙira da ƙera su daidai da CSA Standard C227.4:21. Naúrar an yi niyya ne don kushin waje{2}} hawa kan tubalin tushe kuma ya dace da amfani da shi a cikin madauki{3}}asashen tsarin rarraba ƙasa yadda ya kamata.

Wannan akwatin wutan lantarki yana fasalta mataccen ƙira ta gaba don aminci da sauƙin aiki. Yana amfani da sanyaya ONAN tare da rufin mai na ma'adinai, da iska na aluminium don ingantaccen ma'auni na inganci, nauyi, da farashi. An ƙididdige taswirar 500 kVA, 60 Hz, tare da manyan ma'auni masu girma biyu{5}} 12.47/4.16 kV da ƙarfin lantarki na biyu na 0.208 kV, wanda aka saita azaman YNyn0.

Mahimmin fasalin ƙirar wannan rukunin shine ginin gininsa na ƙafa biyar-, wanda ke samar da ingantaccen ƙarfin maganadisu, yana rage asara, da haɓaka aiki ƙarƙashin GrdY–GrdY ko manyan tsare-tsaren haɗin wutar lantarki guda biyu{{1}. Transformer ba shi da mai sauya matsa lamba (NLTC). Yana ba da kewayon tapping ± 2 × 2.5%. Wannan yana ba da damar daidaita wutar lantarki cikin sauƙi a ƙarƙashin yanayi daban-daban.

Ƙungiyar ta kai 99.05% inganci. Babu -asarar lodi bai yi ƙasa da ko daidai da 1090 W. Asarar lodi ba ta kai ko daidai da 5800 W. An gina shi don amfani da waje kuma yana da dorewa sosai. Akwatin wutar lantarki ya zo tare da daidaitattun na'urorin haɗi na CSA{8}. Amintaccen bayani ne ga hanyoyin sadarwar rarraba Kanada kuma yana goyan bayan manyan haɗin wutar lantarki guda biyu{10}.

 

 

 

1.2 Ƙayyadaddun Fasaha

500kVA lantarki taswirar akwatin ƙayyadaddun bayanai da takardar bayanai

Isarwa zuwa
Kanada
Shekara
2024
Nau'in
Daidaitawa
CSA C227.4:21
Ƙarfin Ƙarfi
500KVA
Yawanci
60HZ
Ciyarwa
Madauki
Gaba
Matattu
Mataki
uku
Adadin ainihin kafa
5
Nau'in Sanyi
ONAN
Liquid insulant
Ma'adinan Mai
Babban Voltage
12.47 (4.16) kV
Na biyu Voltage
0.208 kV
Ƙungiyar Vector
YNyn0
Abubuwan Iska
Aluminum
Impedance
5%
inganci
99.05%
Matsa Canji
Farashin NLTC
Taɓa Range
±2*2.5%
Babu Asara Load
Kasa da ko daidai da 1090 W
Akan Rasa Load
Kasa da ko daidai da 5800 W
Na'urorin haɗi
Daidaitaccen Kanfigareshan

 

1.3 Zane

500kVA akwatin wutan lantarki zane da farantin suna

500kVA pad mounted electrical transformers drawing 500 kVA pad mounted electrical transformers nameplate

 

 

02 Masana'antu

2.1 Kori

Karfe na siliki yana da babban ƙarfin maganadisu da kunkuntar madauki na hysteresis. Wannan yana sa magnetizing sauƙi kuma yana rage zafi a cikin ainihin. Daidaitaccen siffar kafa guda biyar - shima yana taimakawa rage asara{3}}. Transformer yana aiki da kyau kuma ya kasance mai sanyi ƙarƙashin amfani na yau da kullun.

 

2.2 Guda

ƙwararrun ƙwararrun ma'aikata suna raunata dukkan murɗa a hankali ta hanyar amfani da foil na aluminum da waya, suna tabbatar da ingantaccen gini da sanyaya mai inganci don rage asara. Kwarewar masu iskar gas tana ba da tabbacin iska iri ɗaya, ƙarfin injina mai ƙarfi, da kuma abin dogaro. Tare da ingantaccen impedance da ingantaccen aiki, kowane taswira yana ba da daidaitaccen aiki kuma yana shirye don ɗorawa - sakawa.

500 kva electric transformer box-transformer-coil

 

2.3 Tanko

pad mounted electrical transformers oil tank

Kowace rukunin za ta haɗa da tanki mai laushi mai laushi{0}} tare da rufaffiyar murfi, mai iya jurewa ma'aunin ma'aunin kPa 50 ba tare da yatsa ko murdiya fiye da 0.25% na tsayin diagonal ba. Za a kiyaye shingen tare da abin rufe fuska- kuma a kiyaye shi ta hanyar amfani da ƙusoshin pentahead, yana tabbatar da juriya da yanayi{6}mai juriya kamar yadda CSA C227.4 ke faɗi.

 

2.4 Taron Karshe

Ta hanyar aiwatar da daidaitattun umarnin aiki wanda ke rufe dukkan tsari, muna tabbatar da daidaito da gano ayyukan taro. Bugu da ƙari, ana gudanar da taro na ƙarshe a cikin ɗaki mai tsabta tare da yawan zafin jiki da zafi. Masu sa ido masu inganci suna gudanar da cikakken binciken tsari da gudanar da bincike na musamman na mahimman matakai, suna tabbatar da dogaro da yanayin samarwa da ingancin tsari. Wannan zurfin haɗe-haɗe na daidaitawa da tsarin dogaro da kai shine mabuɗin ikon samfuranmu na ci gaba da cika ma'auni.

 

 

03 Gwaji

Matsayin Gwaji da Gwajin Na yau da kullun

Saukewa: CSA227.4-21

Uku -, pad - an ɗora tafsirin rarrabawa tare da keɓaɓɓen keɓaɓɓen

manyan masu haɗa wutar lantarki{{0}

CSA{0}C802.1-13 (R2022)

Ƙimar Ƙarfin Ƙarfi don Liquid{0}}Cikakken Masu Canza Rarraba

1. Ma'aunin Juriya
2. Gwajin Rabo
3. Gwajin Dangantakar Mataki
4. Babu Asara Load Kuma Babu Load A Yanzu
5. Load asarar Impedance ƙarfin lantarki da inganci
6. Gwajin Karfin Wutar Lantarki
7. Gwajin Juriya da Ƙarfin Wutar Lantarki
8. Gwajin Leak tare da Matsi don Masu Canjin Ruwa na Immersed
9. Ma'aunin Juriya na Insulation
10. Gwajin Dielectric Oil
 

pad mounted electrical transformers FAT
pad mounted electrical transformers test

 

Sakamakon Gwaji

A'a.

Gwajin Abun

Naúrar

Karba

Darajoji

Ƙimar Ma'auni

Kammalawa

1

Ma'aunin Juriya

%

Matsakaicin juriya rashin daidaituwa

4.57

Wuce

2

Gwajin Rabo

%

Bambancin rabon ƙarfin lantarki akan babban tapping: ƙasa da ko daidai da 0.5%

-0.04-0.10

Wuce

3

zango{0}}gwajin dangantaka

/

YNyn0

YNyn0

Wuce

4

A'a -asara da tashin hankali na halin yanzu

/

I0 :: bayar da ma'auni darajar

0.48%

Wuce

P0: ba da ƙima mai ƙima

0.8246 kW

juriyar rashin hasara shine +10%

/

5

Load hasarar impedance ƙarfin lantarki da inganci

/

t:85 ku

haƙuri ga impedance shine ± 7.5%

juriyar jimlar asarar kaya shine +6%

/

Wuce

Z%: ƙimar da aka auna

5.36%

Pk: ƙimar ƙima

4.889 kW

Pt: ƙima mai ƙima

5.750 kW

Ingancin ba kasa da 99.05%

99.22%

6

Gwajin Karfin Wutar Lantarki

kV

LV: 10kV 60s

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

7

Jarrabawar Juriya da Wutar Lantarki

kV

Wutar lantarki mai aiki (KV):

2 Ur

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

Duration(s):30

Mitar (HZ): 240

8

Gwajin Leaka

kPa

matsa lamba: 20kPA

Tsawon lokaci: 12h

Babu yabo kuma babu

Lalacewa

Wuce

9

Ma'aunin Resistance Insulation

LV -HV zuwa Ground

9.7

/

HV&LV zuwa Ground

12.2

10

Gwajin Mai

/

Ƙarfin Dielectric

53.5 kv

Wuce

Abubuwan Danshi

10.5 mg/kg

Factor Dissipation

0.00332%

Furan Analysis

Kasa da ko daidai da 0.1

Gas Chromatography Analysis

/

 

 

04 Shiryawa da jigilar kaya

pad mounted electrical transformers packing
pad mounted electrical transformers shipping
 
 

05 Yanar Gizo da Takaitawa

500 kva electric transformer box-back-view

500 kVA uku -kushin lokaci - da aka ɗora tafsiri yana ba da ingantaccen ƙarfi da ingantaccen ƙarfi ga cibiyoyin rarraba Kanada. Ya dace da ma'aunin CSA C227.4:21. Akwatin taswira na lantarki yana da ƙaƙƙarfan silikon karfe core biyar{7}. Aluminum windings an yi daidai don sanyaya mai kyau da ƙarancin asara. Tankin yana da juriya kuma yana jurewa. ƙwararrun ma'aikata suna haɗa kowace ƙungiya a hankali. Madaidaitan matakai da cikakkun abubuwan dubawa suna tabbatar da dogon aiki mai dorewa.

 