500 kVA Kushin Haɓaka Mai Canjin Lantarki-34.5 / 0.48 kV|Panama 2024
Yawan aiki: 500kVA
Wutar lantarki: 34.5/0.48kV
Feature: tare da bayoneti fuse

Fasaha mai wayo, garantin aminci{0}}Cikakken sabis don buƙatun ku!
01 Gabaɗaya
1.1 Kalubalen Aiki a Panama
Asarar Makamashi:Canjin grid yana ɓata makamashi, haɓaka farashi.
Rashin kwanciyar hankali:Kayan aiki masu hankali suna haɗarin rashin aiki yayin jujjuyawar wutar lantarki.
Kalubalen Kulawa:Wurare masu nisa da matsanancin yanayi suna wahalar da sabis.
Lokacin aiki:Rashin kayan aiki na iya dakatar da samarwa ko rushe wutar lantarki.
1.2 Fagen Aikin
An isar da tafsiri mai nauyin kVA 500 zuwa Panama a cikin 2024. Ƙarfin wutar lantarkin shine 500 kVA tare da sanyaya ONAN. Babban ƙarfin lantarki shine 34.5kV tare da kewayon tapping ± 2 * 2.5% (NLTC), ƙarfin lantarki na biyu shine 0.48y / 0.277kV, sun kafa ƙungiyar vector na Dyn1, kuma shine madaidaicin ciyarwa da matattu na gaba.
Ƙirar 500 kVA da aka ɗora ƙirar wutar lantarki ya dace da ANSI C57.12.28 Standard kuma ya ƙunshi tanki mai girma da ƙananan ƙarfin lantarki, rabu da shinge na karfe ko wani abu mai mahimmanci. Maɗaukaki masu girma da ƙananan ƙarfin lantarki suna gefe ɗaya na ɗayan, suna a gefen akwatin taransifofi. Daga gaba, ƙananan ƙarfin lantarki yana kan dama. Dakin ya haɗa da ƙofar shiga. Wannan kofa nau'in lilo ce. Ƙofar ƙofa ta dogara da tsarin kofa, wanda aka cika tare da sashe na 6.1.2 na ANSI C57.12.25 Standard. Za a iya samun damar daki daga ciki kawai. Transformer ya haɗa da alamar matakin mai, wanda ke kan ƙaramin ɗakin wutar lantarki{11}. Har ila yau, ya haɗa da bawul ɗin mai guda biyu, ɗaya don sake cikawa ɗayan kuma don dalilai na magudanar ruwa. Bugu da ƙari, an shigar da bawul ɗin overpressure a kan matsakaicin ƙarfin lantarki. Tsarin yana tabbatar da cewa za'a iya dakatar da na'urar, motsawa, da/ko zamewa akan tushe ba tare da haifar da lahani ga manyan abubuwan wuta da ƙananan ƙarfin lantarki ba. Tsarin na'ura mai canzawa yana ba da damar motsi ta hanyoyi biyu: a layi daya da kuma a kusurwa 90-digiri zuwa gefensa. Transformer ya haɗa da na'urar dakatarwa ta dindindin (ƙugiya) don ba da damar dakatar da naúrar a kwance ta hanyar inji. Waɗannan abubuwan ba dole ba ne su lalace. Duk wani ɓangare na na'urar kuma yana ba da damar dakatar da na'urar ba tare da haifar da gajiya ga kayan ba.
1.3 Ƙimar Fasaha
500 kVA nau'in ƙayyadaddun bayanai da takaddun bayanai
|
Isarwa zuwa
Panama
|
|
Shekara
2024
|
|
Nau'in
Tashin wutar lantarki
|
|
Daidaitawa
IEEE C57.12.00
|
|
Ƙarfin Ƙarfi
500kVA
|
|
Yawanci
60HZ
|
|
Mataki
3
|
|
Nau'in Sanyi
ONAN
|
|
Ciyarwa
Madauki
|
|
Gaba
Matattu
|
|
Babban Voltage
34.5 kV
|
|
Na biyu Voltage
0.48y/0.277 kV
|
|
Abubuwan Iska
Aluminum
|
|
Matsala ta kusurwa
Dyn1
|
|
Impedance
5%
|
|
Matsa Canji
Farashin NLTC
|
|
Taɓa Range
±2*2.5%
|
|
Babu Asara Load
0.08KW
|
|
Akan Rasa Load
1.27KW
|
|
Na'urorin haɗi
Daidaitaccen Kanfigareshan
|
1.4 Zane
500 kVA kushin da aka ɗora zane da girman hoto.
![]() |
![]() |
02 Maganganun Hanyoyi

Babban - Zane mai inganci:Ƙananan -asashen asali da ingantattun iska suna rage babu{1}}asara da lodi; inganci ~ 99.7%, ƙetare ka'idodin DOE.
Abin dogaro:Matattu{0}} gini na gaba da madauki{1}} saitin ciyarwa yana haɓaka aminci kuma yana ba da damar kiyaye sashe ba tare da cikakken rufewa ba.
Karfin Wutar Lantarki:NLTC ± 5% yana kula da ƙarfin lantarki na biyu; Ƙungiyar Dyn1 tana tabbatar da ma'auni kuma yana rage girman jituwa.
Sauƙin Shigarwa & Kulawa:Gilashin aluminium da na'urorin haɗi na yau da kullun suna sauƙaƙe jigilar kaya, shigarwa, da kuma kan ayyukan rukunin yanar gizo-.
Muhalli & Dogon Aiki -:ONAN sanyaya yana rage hayaniya da kulawa; babban inganci yana rage amfani da makamashi da tasirin muhalli.
03 Masana'antu
3.1 Kori
Don shawo kan ƙalubalen hasarar makamashi mai yawa da rashin daidaituwar maganadisu a cikin tasfofi na zamani guda uku{0}, dabarun ƙirar mu na amfani da madaidaicin ginshiƙi guda uku{1} tare da hadedde yokes. Wannan daidaitaccen da'irar maganadisu yana tabbatar da daidaiton juzu'i, yana rage yawan wanzuwa, kuma yana rage yawan baƙin ƙarfe da asara na yanzu, yana haifar da ingantaccen ƙarfin kuzari da kwanciyar hankali na aiki.

3.2 Guda

Don magance ƙalubale masu mahimmanci na jure manyan gajerun igiyoyin kewayawa, da rage asarar makamashi, da inganta yanayin sarrafa zafi, dabarun iskan mu na haɗaɗɗen ƙanƙara na ciki -ƙarar iska mai ƙarfi tare da babban iska mai ƙarfi{2}}waya. Wannan ƙira yana tabbatar da ingantaccen ƙarfin injina da gajeriyar juriyar kewayawa, yayin da lokaci guda yana rage juriya na DC da hasara na yanzu don ingantaccen inganci. Hakanan tsarin yana ba da damar ingantattun tashoshi masu sanyaya, yana haifar da ƙarancin yanayin aiki da haɓaka aikin gabaɗaya.
3.3 Tanko
Don saduwa da ƙalubalen damuwa na injina, lalata muhalli, da amincin aiki a aikace-aikace iri-iri, an ƙera tankin mu na canjin yanayi tare da dabarun kariya da yawa{0}. An gina shi daga ƙaƙƙarfan ƙarfe mai inganci tare da walda na mutum-mutumi, yana tabbatar da daidaiton tsari da ɗigogi{3}}hujja aiki, yayin da ci-gaba na rigakafin{4}}lalacewa yana ba da tsayin tsayin tsayin yanayi. Ana inganta tsaro da kiyayewa ta hanyar haɗaɗɗun fasalulluka waɗanda suka haɗa da bawul ɗin taimako na matsa lamba, bawul ɗin mai na musamman, da tagogin dubawa, tare da ƙira ta ƙara daidaitawa zuwa takamaiman iya aiki da buƙatun wutar lantarki.

3.4 Taron Karshe

Shigar da mahimman abubuwan haɗin gwiwa: Gyara jikin mai canza wuta, babban ƙarfin lantarki da ƙarancin wutar lantarki a cikin ɗakunan su.
Haɗin ciki: Haɗa igiyoyi ko sandunan bas tsakanin taswira da maɓalli kuma tabbatar da ingantaccen ƙasa.
Shigar da kayan aikin taimako: shigar da na'urorin kariya kamar fis, bawul ɗin taimako na matsa lamba, matakan man fetur da ƙananan abubuwan rarraba wutar lantarki-.
Hadarin akwatin: Dukkanin abubuwan da aka gyara ana gyara su a cikin akwatin bakin karfe, ƙara hana ruwa, mai hana ƙura, ƙirar lalata, da tabbatar da samun iska mai kyau.
04 Gwaji


05 Kiɗa da jigilar kaya
5.1 Shiryawa
Fuskokin mu guda uku -{1} da aka ɗora tasfoma an tattara su cikin amintaccen akwati{2}}ingin katako, wanda aka ƙera don iyakar kariya yayin tafiya da ajiya. An ƙarfafa firam ɗin katako mai ƙarfi a ciki tare da toshewa da takalmin gyaran kafa don hana naúrar, yayin da madaurin ƙarfe na waje suna ba da ƙarin daidaiton tsari. Wannan ingantaccen bayani na marufi yana tabbatar da cewa taswirar ku ta isa wurin a cikin kyakkyawan yanayi, a shirye don shigarwa nan take.

5.2 Shipping

An ƙirƙira shi don amintaccen jigilar kaya na teku, na'urorin mu na zamani guda uku{0}}{1} masu ɗaure su an cika su a cikin akwatunan katako masu hana yanayi tare da ƙarfafan takalmin gyaran kafa na ciki don jure yanayin ruwa. Kowane rukunin yana fasalta daidaitattun wuraren ɗagawa da share alamun tari don tabbatar da amintaccen lodin kwantena, ingantaccen tanadin jirgin ruwa, da lalacewa- bayarwa kyauta zuwa wuraren aikin duniya.
06 Yanar Gizo da Takaitawa
A cikin tsarin wutar lantarki na zamani, na'ura mai ɗaukar wutan lantarki na zamani guda uku ya fito waje a matsayin ingantacciyar mafita don buƙatun lantarki daban-daban, yana ba da aiki na musamman da amintaccen aminci. Ko don ababen more rayuwa na birane, gine-ginen kasuwanci, ko aikace-aikacen masana'antu, zai iya ba da ingantaccen goyan bayan wutar lantarki, yana taimaka wa masu amfani haɓaka ingantaccen aiki. Mun himmatu wajen isar da ingantattun samfura masu inganci da ƙwararrun sabis na abokin ciniki, tare da tabbatar da cewa kuna da mafi kyawun gogewa yayin zabar kushin mu mai ɗorewa. Zaɓi samfurin mu, kuma bari mu yi aiki tare don ƙirƙirar kore mai ɗorewa kuma mai dorewa nan gaba!

Hot Tags: kushin saka wutar lantarki, masana'anta, mai kaya, farashi, farashi
You Might Also Like
225 kVA Kushin Dutsen Mai Canjawa-34.5 / 0.208 kV|Am...
750 kVA Kushin Waje Mai Sauƙi Mai Sauƙi-34.5 / 0.48 ...
2500 kVA Kushin Haɗa Mai Canjawa-13.2 / 0.48 kV|Kana...
1250 kVA Kushin Haɗa Mai Canjawa-12.47 / 0.6 kV|Amur...
300 kVA Green Akwatin Mai Canjawa-12 / 0.12 * 0.24 k...
300 kVA Mai Cika Mai Sauƙi-13.2 / 0.48 kV|Guyana 2024
Aika Aikace-aikacen