1000 KVA Transformer 3 Phase-24 / 0.416*0.24*0.12 KV|Jamaica 2026

1000 KVA Transformer 3 Phase-24 / 0.416*0.24*0.12 KV|Jamaica 2026

Ƙasa: Jamaica 2026
Yawan aiki: 1000 kVA
Wutar lantarki: 24GrdY/13.8-0.416Y/0.24*0.24DkV
Siffar: YNyn0/YNd11
Aika Aikace-aikacen

Jiangshan Scotech Electric Co., Ltd yana ɗaya daga cikin masana'antun da suka fi dacewa kuma masu samar da wutar lantarki 1000 kva 3 lokaci -24/0.416*0.24*0.12 kv|jamaica 2026 in China. Da fatan za a ji kyauta don siyan kayayyaki masu inganci don siyarwa anan kuma ku sami zane-zane daga masana'anta. Tuntube mu don ƙarin bayani.

 

image001

Ƙarfi a inda kuke buƙata, kyakkyawa inda kuka gan shi - wannan shine abin da aka saka tafsiri.

 

 

01 Gabaɗaya

1.1 Bayanin Aikin

1000 kVA three phase pad mounted transformer an isar da ita zuwa Amurka a shekarar 2026. Ƙarfin wutar lantarkin shine 1000 kVA tare da sanyaya KNAN. Babban ƙarfin lantarki shine 24GrdY / 13.8 kV tare da ± 2 * 2.5% tapping range (NLTC), ƙarancin ƙarfin lantarki shine 0.416Y / 0.24 * 0.24D kV, sun kafa ƙungiyoyin vector guda biyu na YNyn0/YNd11.

Dual Low- Kanfigarewar Rukunin Vector Voltage don Canjin Wutar Lantarki

Babban fasalin wannan aikin shine daidaitawar rukunin rukunin ƙananan ƙarancin wutar lantarki na na'ura mai canzawa, wanda aka tsara shi azaman YNyn0/YNd11. A cikin haɗin YNyn0, duka babban ƙarfin lantarki da ƙarancin wutar lantarki suna da alaƙa tauraro tare da abubuwan tsaka tsaki waɗanda aka fito da su, kuma ƙaramin ƙarfin lantarki ya kasance cikin lokaci tare da gefen babban ƙarfin lantarki. A cikin tsarin YNd11, ana haɗa ƙaramin iska mai ƙarfi a cikin delta, yana haifar da jagorar lokaci na digiri 30 (ko lag 330) dangane da babban ƙarfin wutar lantarki. Wannan ƙirar rukunin vector dual vector yana ba da damar canzawa mai sassauƙa tsakanin mabambantan ƙayyadaddun ƙarancin ƙarfin ƙarfin lantarki daban-daban, yana bawa abokin ciniki damar daidaita halayen wutar lantarki na biyu na gidan wuta don saduwa da buƙatun tsarin daban-daban. Ta hanyar haɗin da aka sake daidaitawa da kuma amfani da tsaka-tsakin tsaka-tsakin, mai canzawa zai iya isar da ba kawai daidaitattun 0.416 kV (layi zuwa layi) da 0.24 kV (layi zuwa tsaka tsaki / delta) abubuwan fitarwa, amma har ma da ƙarancin wutar lantarki na 0.12 kV, yana ba da zaɓi na uku don kaya na musamman ko buƙatun wadata. Wannan haɓakar haɓakawa yana sa waɗannan na'urori masu canzawa musamman dacewa don yanayin haɗin haɗin grid daban-daban da aikace-aikacen wutar lantarki da yawa.

Bukatar Nau'in Gwajin: DC Winding Resistance Measurement

Bayan daidaitattun gwaje-gwaje na yau da kullun da aka ƙayyade a cikin ƙa'idar fasaha, wannan aikin yana ɗauke da buƙatu ta musamman: an ayyana ma'aunin juriya na DC a matsayin gwajin nau'in dole. Wannan gwajin ya ƙunshi allurar halin yanzu na DC mai sarrafawa cikin kowane iska mai ɗaukar wuta da auna jujin ƙarfin lantarki don ƙididdige ƙimar juriya. Gwajin juriya na DC babban kayan aikin bincike ne da ake amfani da shi don gano katsewa, haɗin kai mara kyau, da buɗaɗɗen da'irori a cikin iska, da kuma tabbatar da amincin duk haɗin famfo. Ta hanyar yin wannan gwajin azaman gwaji na yau da kullun maimakon gwaji na yau da kullun, abokin ciniki yana samun ingantaccen matakin tabbaci game da ci gaba da jujjuyawar iska, ingancin haɗin kai, da daidaitattun masana'anta na waɗannan taswirar - wani muhimmin la'akari musamman da aka ba da ƙirar rukuni biyu{4}vector{5}} da kuma buƙatar ingantaccen aiki a ƙarƙashin saitunan haɗin gwiwa.

 

1.2 Ƙayyadaddun Fasaha

1000 kVA kushin da aka ɗora nau'in ƙayyadaddun bayanai da takaddun bayanai

Isarwa zuwa
Jamaica
Shekara
2026
Nau'in
Tashin wutar lantarki
Daidaitawa
IEEE Std C57.12.34-2022
Ƙarfin Ƙarfi
1000 kVA
Yawanci
50HZ
Mataki
3
Ciyarwa
Madauki
Gaba
Matattu
Nau'in Sanyi
ONAN
Babban Voltage
24GrdY/13.8kV
Na biyu Voltage
0.416Y/0.24*0.24kV
Abubuwan Iska
Copper
Ƙungiyar Vector
YNyn0/YNd11
Impedance
5.75%
inganci
99.06%
Matsa Canji
Farashin NLTC
Taɓa Range
±2*2.5%
Babu Asara Load
1.5 kW
Akan Rasa Load
14.32 kW

 

1.3 Zane

1000 kVA kushin da aka ɗora zane da girma.

image003

image005

image007

 

 

02 Masana'antu

2.1 Guda

image009

Ana kera iskar wutar lantarki tare da jan ƙarfe 100% electrolytic don tabbatar da kyakkyawan aiki, ƙarfin gajeriyar kewayawa, da kwanciyar hankali na dogon lokaci. Babban ƙirar ƙafar ƙafa 5 ce da aka gina daga babban juzu'i, birgima mai sanyi, ƙarfe madaidaiciyar silikon ƙarfe, daidai gwargwado don rage girman magnetizing na yanzu da asarar ɓacewa. Tsarin kafa na 5 yana da fa'ida musamman don daidaitawar rukunin vector dual (YNyn0/YNd11), yayin da yake daidaita rarraba juzu'i a ƙarƙashin duka haɗin taurari da delta, don haka rage ƙarancin nauyi da tashin hankali na halin yanzu.

 

2.2 LV Mai Gudanarwa Rod (takaice)

Ƙarƙashin ƙarfin wutar lantarki yana amfani da sandunan madugu na jan ƙarfe (basbars) waɗanda ke haɗa tashoshi masu jujjuyawa zuwa nau'in spade na LV bushings. Waɗannan sandunan suna da girma don ɗaukar cikakken ƙimar halin yanzu (kimanin{1}} A a 416 V) tare da isasshiyar tazara, kuma an ƙirƙira su don jure gajeriyar ƙarfin kewayawa da matsananciyar zafi ba tare da nakasu ba. Sandunan suna da kariya amintacciya kuma ana tallafawa a cikin tanki don tabbatar da ƙarancin juriya, haɗin kai kyauta a tsawon rayuwar na'urar.

image011

 

2.3 Maɓallin Loadbreak Sauyawa biyu

image013

Uku FYB 10 nau'in matsayi biyu na man da aka nutsar da masu ɗaukar nauyi an shigar da su a cikin sashin HV. An ƙididdige su 10 kV, 630 A, tare da juriya na thermal na 20 kA / 2s, juriya mai ƙarfi na 50 kA (kololuwa), da rayuwar injiniya na ayyukan 2000. An shirya maɓallan don aikace-aikacen ciyarwar madauki (biyu don madauki cikin/fita, ɗaya don kariyar taswira), tare da hannaye masu kullewa waɗanda ke samun dama daga sashin gaba.

 

2.4 H0 Bushing (HV Neutral)

Ana fitar da madaidaicin tsaka-tsakin wutar lantarki ta hanyar keɓewar H0, wanda shine tsarin ANSI salon ramuka biyu mai lamba 25 kV, 208 A, tare da nisa mai zurfi sama da ko daidai da 405 mm da BIL na 125 kV. Wannan keɓantaccen tashar H0 yana ba da damar sassauƙan tsarin tsarin ƙasa - tsaka tsaki na iya zama ƙasa mai ƙarfi, ƙasa mai ƙarfi, ko barin ƙasa lokacin da aka haɗa iskar HV a cikin wye. A cikin aikin delta, H0 bushing yana aiki azaman madaidaicin wurin gwaji don bincikar rufi.
Bugu da ƙari, an samar da fanti guda biyu na bakin ƙarfe na ƙasa (ɗaya a kowane ɗaki) don ingantaccen tanki da tsarin ƙasa.

image015

 

2.5 Taron Karshe

image017

Haɗawa yana bin ƙaƙƙarfan tsari mai inganci: jigon jigon jigon, jujjuyawar coil, haɗin gubar, da murfi ana yin su a ƙarƙashin yanayin sarrafawa. Cikakken sashi mai aiki yana jurewa bushewar bushewa da tsarin cika mai don cire danshi daga ingantaccen rufin, yana tabbatar da busasshen tsarin dielectric mai bushe da kwanciyar hankali kafin rufewar tanki na ƙarshe.

Tankin na nau'in gini ne da aka rufe tare da murfin da aka rufe, wanda aka yi da ƙarfe mai laushi. An rufe shingen tare da Munsell 7GY3.29 / 1.5 gama, saduwa da IEEE C57.12.28 bukatun don juriya na lalata a cikin yankunan bakin teku. An tanadar da ulun ɗagawa da faifan jacking don amintaccen kulawa.

 

 

03 Gwaji

Ana yin duk gwaje-gwaje daidai da IEEE C{0}} da IEEE C57.12.90.
Gwaje-gwaje na yau da kullun (an yi akan kowace naúrar):
• Juyawa juzu'i da ƙaurawar lokaci (tabbacin YNyn0 da YNd11)
• Babu hasara mai nauyi da halin yanzu mai ban sha'awa
• Load asarar da impedance ƙarfin lantarki
• Ƙarfin wutar lantarki da aka yi amfani da shi (HV: 40 kV; LV: 10 kV)
• Ƙunƙarar ƙarfin lantarki
• Gwajin zubin tanki (50 kPa na awanni 12)
• Ƙarfin dielectric mai (Mafi girma ko daidai da 45 kV)
• juriya na insulation DC da ma'anar polarization
Nau'in gwaje-gwaje - buƙatu na musamman don wannan aikin shine cewa an tsara ma'aunin juriya na DC a matsayin gwajin nau'in tilas, ba kawai dubawa na yau da kullun ba. Wannan gwajin yana shigar da na'urar halin yanzu na DC mai sarrafawa cikin kowane iska kuma yana auna digon wutar lantarki don ƙididdige ƙimar juriya. Yana da mahimmancin bincike don gano tsintsiya madauri, rashin kyawun haɗin kai, ko madaidaicin mahaɗin famfo. Ta hanyar yin shi azaman gwajin nau'in nau'in, muna ba da ingantaccen matakin tabbaci kan ci gaba da jujjuyawar iska da amincin haɗin kai - musamman mahimmanci idan aka ba da jeri na ƙungiyar vector daban-daban.

Daga rahoton gwajin da aka kammala (Serial No{0}}), ma'auni masu ƙima:
• Babu asarar nauyi: 1.1445 kW
• Rashin nauyi (digiri 85): 12.037 kW
• Tasiri: 5.74%
• Inganci: 99.23% - duk sun wuce adadin garantin.

image019
image021

 

 

04 Damuwar Abokin Ciniki

An magance mahimman abubuwa da yawa don biyan takamaiman buƙatun abokin ciniki na Kanada:

• Ƙungiya mai dual vector (YNyn0/YNd11): Aiki na ciki: Haɗin ciki an tsara su ta yadda za a iya sake saita iska ta LV daga tauraro zuwa delta. A cikin tauraro, lokaci zuwa matsakaicin ƙarfin lantarki shine 240 V kuma layin zuwa layin 416 V; a cikin delta, layin zuwa layi ya kasance 416 V, yayin da maɓallin tsakiya akan lokaci ɗaya yana samar da 120 0 120 V (watau 0.12 kV) don kayan taimako. Canji mai sauƙi ne, ta amfani da faranti da aka bayar.
Bukatun gwaji na nau'in: Abokin ciniki ya nemi juriya na iska na DC azaman gwajin nau'in - wannan yana ba su takaddun shaida na daidaiton masana'anta da ingancin haɗin kai a duk tsarin iska.
• Yanayin bakin teku na wurare masu zafi: An ƙera na'urorin lantarki tare da ingantaccen kariya na lalata (tsarin fenti mai kauri, kayan aikin bakin karfe) da manyan matakan BIL don jure wa yawan walƙiya, zafi mai zafi, da iska mai gishiri, kamar yadda ƙayyadaddun Jamaican (JPSCo 6950 S 04).
image023

 

 

05 Shiryawa da jigilar kaya

5.1 Shiryawa

Kowane tafsiri yana kunshe ne daban-daban a cikin wani akwati mai nauyi mai nauyi na katako, wanda aka kera don sarrafa cokali mai yatsa da jigilar teku. Abubuwan da suka dace (bushings na ain, bawul ɗin taimako na matsa lamba, ma'aunin matakin) ana kuma kwantar da su tare da kayan ɗaukar girgiza. Akwatin yana da alamar "UP" da "FRAGILE". Ana kiyaye matakin mai 100 150 mm ƙasa da saman tanki don ba da damar haɓaka zafi yayin tafiya.

image025

 

5.2 Shipping

image027

Ana yin jigilar kaya azaman cikakkiyar naúrar (cikakken harru, cike mai). Kafin aikawa, ana buƙatar rubutaccen izini daga mai siye, kuma dole ne a ƙaddamar da rahotannin gwajin da aka tabbatar kuma a amince da su.

Ana jigilar masu taswirar CIF Kingston, Jamaica (ko kamar yadda aka yarda da tashar jiragen ruwa). Abubuwan ɗagawa da ma'auni suna da alama a sarari. Fakitin katako ya bi ka'idodin phytosanitary ISPM 15 don jigilar kayayyaki na duniya. An yi la'akari da girgizar wucewa da girgiza a cikin ƙirar tallafin ciki.

 

 

05 Yanar Gizo da taƙaitawa

SCOTECH kushin ɗorawa an amince da su don ayyukan birane, kasuwanci, masana'antu, da ayyukan makamashi mai sabuntawa. Muna maraba da tambayoyinku da umarni na al'ada - ƙungiyar ƙwararrunmu a shirye take don taimaka muku daga zaɓi zuwa goyon bayan tallace-tallace. Tuntube mu a yau - bari SCOTECH ya ba da ikon nasarar ku.

image029

 

Hot Tags: 1000 kva mai canzawa 3 lokaci-24 / 0.416 * 0.24 * 0.12 kv|jamaica 2026, China 1000 kva taransfoma 3 lokaci-24/0.416*0.24*0.12 kv|jamaica 2026 masana'antun, masu kaya, masana'anta