1000 kVA Kushin Dutsen Masu Canjawa Na Siyarwa-4.16 / 0.48 kV|Amurka 2025
Yawan aiki: 1000 kVA
Ƙarfin wutar lantarki: 4.16D-0.48Y/0.277 kV
Feature: tare da bawul na Schrader

Uku -kushin ɗorawa{1}maƙallan wutan lantarki: Jagoranci sabon zamanin ikon fasaha, yana haskaka kowane kusurwa.
01 Gabaɗaya
1.1 Bayani & Bukatun Abokin ciniki
A cikin 2025, mun kawo 1000 kVA guda uku -kushin lokaci{3}}wanda aka ɗora tasfoma (4.16 kV Delta / 0.48Y/0.277 kV, Dyn1, ONAN, ± 2×2.4% NLTC) zuwa kasuwar Amurka.
Saitin fasaha daidai ne, amma ƙalubalen da ke bayan buƙatun abokin ciniki ba su da sauƙi.
Mabuɗin Ciwon Abokin Ciniki
1. Tsaro a Wurare masu cunkoson jama'a ko a tsare
Pad{0}}wayoyin da aka ɗora sau da yawa suna zama a cikin matsatsun wurare{1}}kusa da titin tafiya, kantuna, wuraren ajiye motoci, ko ƙananan yadudduka masu amfani. Abokan ciniki suna buƙatar naúrar da ke zaune lafiya ko da wanene ya bi ko wanda ya yi gyara. Babu fallasa babban ƙarfin lantarki{4}, babu lamba ta bazata, babu abin mamaki.
2. Dogon - Dorewar Tsawon Yanayi da Muhalli
Ruwan sama, zafi, hazo na gishiri, yanayin zafi kwatsam{0}} shekara bayan shekara, wurin yana fuskantar damuwa akai-akai. Abokan ciniki suna son na'urar taswira wacce ba za ta lalata, yayyafawa, ko ƙasƙanta ba, kuma tana kiyaye abubuwan cikin gida shekaru da yawa.
3. Aiki mai tsayayye Karkashin Yanayin Load da aka haɗa
Matsalolin birni da na kasuwanci ba safai suke yin tsinkaya ba. Kololuwar wurin zama da daddare, kololuwar kasuwanci a cikin rana, hauhawar masana'antu na lokaci-lokaci{1} duk suna buƙatar na'urar lantarki mai daidaitawa, yana guje wa zazzaɓi, kuma yana ba da madaidaiciyar wutar lantarki ba tare da katsewa ba.
4. Rawanin Rayuwar Rayuwa Tare da Karancin Kulawa
Asarar makamashi tana taruwa, kuma kulawa ta yau da kullun ba ta da arha. Abokan ciniki suna neman na'ura mai canzawa wanda "yana gudana cikin nutsuwa a bango," tare da ƙarancin asara, sa ido mai sauƙi, da ƙarancin ƙarancin lokaci -yayin da ya rage cikakke tare da ƙa'idodin IEEE / ANSI don haɗakar mai sauƙi.
1.2 Maganinmu
Maɗaukaki -Ciyarwa + Matattu-Kirar Rufewar Gaba
Don wannan aikin, aminci ba kawai abin buƙata ba ne{0}} shine farkon farawa.
Mun zabi amadauki{0} tsarin ciyarwada amatattu{0}}gaba, cikakken rufaffiyar tsari, ɗaya daga cikin mafi aminci ga hanyoyin sadarwar birane da na kasuwanci na zamani.
Babu fallasa tashoshi. Babu haɗarin tuntuɓar bazata. Babu lahani ga ruwan sama, ƙura, ko hannaye masu ban sha'awa. Tsarin HV yana kasancewa a rufe a cikin wani daki mai tsauri, yana baiwa masu aiki kwarin gwiwa ko da cikin cunkoson jama'a ko sarari{3}}iyakantaccen muhalli. Kuma tare da madauki -sauƙin ciyarwa, ana iya kiyaye sashe ɗaya na hanyar sadarwar ba tare da rufe gabaɗayan tsarin ba{6}}ƙarancin kashewa, ayyuka masu santsi, da tsaftataccen shigarwa gabaɗaya.
Wannan shine kayan aikin ƙira akai-akai zaɓi lokacin da aminci da amincin jama'a dole ne su fara zuwa.
Aluminum Winding + LV Foil + High-Aikin Asarar Haɓaka
Mun kuma inganta ga abin da ya shafi dogon lokaci{0}: farashin aiki.
Transformer yana amfanialuminum windingsa gefen HV kumacikakken - ginia gefen LV{0}}mai nauyi, inganci, kuma mai ƙarfi a ƙarƙashin yanayin duniya na gaske{{1}.
Kuma ingancin yana magana da kansa.
Tare da1.3 kW babu - asarar kayakuma6.94 kW asarar nauyi, naúrar tana ba da ingantaccen aiki mai ƙarfi tare da rage sharar makamashi. Ƙananan lissafin kuɗi, ƙarancin zafi, da tsawon rayuwar rufi. Wannan nau'in inganci ne wanda ke biyan kuɗi cikin nutsuwa kowace shekara.
Cikakken Kunshin Kulawa & Kariya
Aiki lafiya kuma yana nufin sanin abin da ke faruwa a cikin tanki.
Wannan rukunin yana zuwa sanye take da cikakken kunshin sa ido da kariya, gami da:
Ma'aunin mai
Kira ma'aunin zafi da sanyio
Matsa lamba{0}}ma'auni
Bawul ɗin taimako na matsi
Na'urar rage matsa lamba
Gas samfurin tashar jiragen ruwa
Tare, waɗannan abubuwan haɗin gwiwar suna aiki azaman tsarin faɗakarwa na farko{0}}mai sauƙi, abin dogaro, kuma mai sauƙi ga masu fasahar filin fassara. Suna taimakawa gano haɓakar zafin jiki, iskar gas, matsa lamba na al'ada, ko asarar mai a kallo, inganta lokacin amsawa lokacin da grid ke damuwa.
An tsara & Gwaji ta IEEE C57.12.34-2022
Kowane maɓalli na maɓalli-daga ƙarfin injina zuwa haɓakar zafin jiki da aikin wutan lantarki{1}} yana biIEEE C57.12.34-2022, ƙayyadaddun ƙayyadaddun ƙayyadaddun ƙayyadaddun kushin Arewacin Amurka{0}} ɗorawa masu rarraba wutar lantarki.
Wannan yana tabbatar da haɗin gwiwa tare da tsammanin amfani a duk faɗin yankin.
Ƙirar da ta yi daidai da grid na Amurka, wanda aka gina don dogara, dogon sabis na tsawon lokaci.
1.3 Ƙimar Fasaha
1000 KVA kushin da aka ɗora nau'in ƙayyadaddun bayanai da takaddun bayanai
|
Isarwa zuwa
Amurka
|
|
Shekara
2025
|
|
Nau'in
Tashin wutar lantarki
|
|
Daidaitawa
IEEE StdC57.12.34-2022
|
|
Ƙarfin Ƙarfi
1000 KVA
|
|
Yawanci
60HZ
|
|
Mataki
3
|
|
Ciyarwa
Madauki
|
|
Gaba
Matattu
|
|
Nau'in Sanyi
ONAN
|
|
Babban Voltage
4.16d kV
|
|
Na biyu Voltage
0.48Y/0.277 kV
|
|
Abubuwan Iska
Aluminum
|
|
Matsala ta kusurwa
Dyn1
|
|
Impedance
5.75%
|
|
Matsa Canji
Farashin NLTC
|
|
Taɓa Range
±2*2.4%
|
|
Babu Asara Load
1.3kW
|
|
Akan Rasa Load
6.94 kW
|
|
Na'urorin haɗi
Daidaitaccen Kanfigareshan
|
1.4 Zane
1000 kVA kushin da aka ɗora zane da girman hoto.
![]() |
![]() |
02 Masana'antu
2.1 Kori
Tsarin ginshiƙi guda uku - yana ba da tallafi mai zaman kansa ga kowane lokaci, yana ba da damar rarraba kaya iri ɗaya a kowane shafi yayin aiki. Wannan yana rage tsangwama na maganadisu da asarar makamashi, yana tabbatar da ingantaccen ƙarfin lantarki. Zane na ainihin ya ƙunshi rufaffiyar da'irar maganadisu wanda ke rage girman jikewar maganadisu da hasara, yana haɓaka ingancin watsa makamashi gabaɗaya a cikin gidan wuta. Yin amfani da zanen gadon ƙarfe na silicon tare da haɓakar haɓakawa azaman ainihin kayan ba kawai haɓaka ƙarfin lantarki ba amma kuma yana rage asarar eddy na yanzu da dumama, yana tabbatar da ingantaccen aiki na kayan aiki.

2.2 Guda

Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙashin Ƙarƙwara
Tsarin: Rufin ƙarfe yana ƙara ƙarfin halin yanzu kuma yana rage hasara.
Insulation: Yana haɓaka kwanciyar hankali a ƙananan amfani da wutar lantarki.
Rage zafi: Taimaka ingantaccen rarraba zafi.
EMI: Yana rage tsangwama na lantarki.
Babban - Wutar Wutar Lantarki
Gina: Yana amfani da wayar aluminium don ingantaccen watsa wutar lantarki mai inganci -.
Insulation: Yana Kariya daga gajerun kewayawa.
Sauƙaƙe Load: Ya dace da kaya iri-iri.
Resistance Vibration: Yana tabbatar da aminci a ƙarƙashin damuwa.
2.3 Tanko
Daidaitaccen mashin ɗin ƙarfe ta amfani da yankan Laser ko fasahar yankan plasma. An lanƙwasa farantin karfe kuma an kafa shi, kuma ana tabbatar da daidaiton lanƙwasa ta kayan aiki ta atomatik. Ɗauki babban madaidaicin tsarin walda, kamar walƙiya ta atomatik ko walƙiya argon baka na hannu, don tabbatar da ƙarfi da ƙarfi na walda. Gaba dayan tankin an tarwatsa yashi don cire tarkacen oxide sannan a fesa shi da firamare da saman gashi don haɓaka juriyar lalata. A cikin muhallai na musamman, ana iya amfani da zafi mai zafi{4}} ko wasu ci-gaba na maganin lalata-.

2.3 Taron Karshe

Shigar da Babban Sashe: Haɗa na'urar wuta, haɗa manyan layukan wutar lantarki da ƙananan, sannan duba ƙasa.
Haɗin Waya: Haɗa manyan tashoshi masu ƙarfi da ƙananan ƙarfin lantarki kuma tabbatar da zane na wayoyi.
Na'urorin haɗi da sanyaya: Shigar da tsarin sanyaya da kayan haɗi masu mahimmanci.
Farawa da Debugging: Gudanar da cikakken bincike, kunna wuta don gwaji, da rikodin gyare-gyare.
2.4 Abubuwan






03 Gwaji
|
A'a. |
Gwajin Abun |
Naúrar |
Dabi'un Karɓa |
Ƙimar Ma'auni |
Kammalawa |
|
1 |
Ma'aunin Juriya |
% |
Matsakaicin juriya rashin daidaituwa |
2.93 |
Wuce |
|
2 |
Gwajin Rabo |
% |
Bambancin rabon ƙarfin lantarki akan babban tapping: ƙasa da ko daidai da 0.5% |
-0.13 |
Wuce |
|
3 |
Mataki{0}}gwajin dangantaka |
/ |
Dyn1 |
Dyn1 |
Wuce |
|
4 |
A'a -asara da tashin hankali na halin yanzu |
% |
I0 : bayar da ma'auni darajar |
0.43 |
Wuce |
|
kW |
P0: Bayar da ƙima (digiri 85) |
1.289 |
|||
|
/ |
Haƙuri don asarar nauyi shine ± 10% |
/ |
|||
|
5 |
Load asarar , impedance ƙarfin lantarki, jimlar asara da kuma yadda ya dace |
/ |
t:85 ku haƙuri ga impedance shine ± 7.5% Haƙuri don asarar nauyi shine ± 6% |
/ |
Wuce |
|
% |
Z%: ƙimar da aka auna |
5.42 |
|||
|
kW |
Pk: ƙimar ƙima |
7.223 |
|||
|
kW |
Pt: ƙima mai ƙima |
8.451 |
|||
|
% |
Ingancin ba kasa da 99.43% |
99.43 |
|||
|
6 |
Gwajin Karfin Wutar Lantarki |
/ |
HV: 19kV 60s LV: 10kV 60s |
Babu rushewar ƙarfin gwajin da ke faruwa |
Wuce |
|
7 |
Jarrabawar Juriya da Wutar Lantarki |
/ |
Wutar lantarki mai aiki (KV): 0.96 |
Babu rushewar ƙarfin gwajin da ke faruwa |
Wuce |
|
Duration(s): 48 |
|||||
|
Mitar (HZ): 150 |
|||||
|
8 |
Ma'aunin Resistance Insulation |
GΩ |
HV{0}LV zuwa Kasa: |
20.8 |
/ |
|
LV -HV zuwa Ground: |
31.0 |
||||
|
HV&LV zuwa Ground: |
19.4 |
||||
|
9 |
Gwajin Leaka |
/ |
matsa lamba: 20kPA |
Babu yabo kuma babu Lalacewa |
Wuce |
|
Tsawon lokaci: 12h |
|||||
|
10 |
Gwajin Mai |
kV |
Ƙarfin Dielectric |
54.9 |
Wuce |
|
mg/kg |
Abubuwan Danshi |
9.7 |
|||
|
% |
Factor Dissipation |
0.00227 |
|||
|
mg/kg |
Furan Analysis |
/ |
|||
|
/ |
Gas Chromatography Analysis |
/ |


04 Shiryawa da jigilar kaya


05 Yanar Gizo da Takaitawa
A taƙaice, ɗorawa ɗin mu guda uku{0}}{1}maƙallan wutan lantarki yana ba da ingantaccen aiki da ingantattun hanyoyin rarraba wutar lantarki don aikace-aikace daban-daban. Tare da ƙaƙƙarfan ƙira, shigarwa mai sauƙi, da sifofin aminci na ci gaba, zaɓi ne mai kyau don tsarin lantarki na zamani wanda ke buƙatar inganci da dorewa. Mun himmatu wajen samar da samfuran inganci masu inganci waɗanda ke biyan buƙatun abokan cinikinmu, da tabbatar da kyakkyawan aiki da gamsuwa. Zaɓi na'urorin mu don buƙatun makamashi kuma ku sami bambanci a cikin inganci da sabis.

Hot Tags: pad Dutsen transformers for sale,manufacturer,maroki,farashi,cost
You Might Also Like
75 kVA Kushin Dutsen Mai Canjawa-22.86 / 0.208 kV|Am...
1500 kVA Kushin Haɗa Mai Canjawa-34.5 / 0.48 kV|Amur...
112.5 kVA Matattu Masu Canjin gaba-22.86 / 0.208 kV|...
2500 kVA Kushin Dutsen Mai Canjawa-12.47 / 0.48 kV|A...
1000 kVA Matattu Mai Canjin gaba-24 / 0.48 kV|Amurka...
2000 kVA Kushin Haɗa Mai Canjawa-24 / 0.48 kV|Amurka...
Aika Aikace-aikacen