630 kVA Wutar Lantarki Mai Ciki Mai Sauƙi-11 / 0.55 kV|Afirka ta Kudu 2025

630 kVA Wutar Lantarki Mai Ciki Mai Sauƙi-11 / 0.55 kV|Afirka ta Kudu 2025

Ƙasa: Afirka ta Kudu 2025
Yawan aiki: 630kVA
Wutar lantarki: 11/0.55kV
Siffar: tare da magoya baya da matakin rufewar H
Aika Aikace-aikacen

 

 

630 kVA vacuum pressure impregnated transformer

Rarraba Wutar Lantarki, Koren Makomar - Buɗe Busassun Masu Canjin Juyawa don Dorewa!

 

 

01 Gabaɗaya

1.1 Bayanin Aikin

The 630 kVA bude winding busassun irin transformer da aka isar zuwa Afirka ta Kudu a cikin 2025. The rated ikon bude winding busassun irin transformer ne 630 kVA tare da AN / AF sanyaya, na farko irin ƙarfin lantarki ne 11 kV da ± 2 * 2.5% tapping kewayon (NLTC), da sakandare ƙarfin lantarki ne 0.55kV, sun kafa wani vector kungiyar Dyn1.

Buɗewar Buɗewar Nau'in Canjin mu an ƙera shi don ingantaccen aiki, haɗa fasahar ci gaba tare da ingantaccen gini don biyan buƙatun ikon masana'antu da kasuwanci. Tare da mai sarrafa zafin jiki mai hankali, yana tabbatar da ingantaccen sarrafa zafin jiki, yayin da aka gina{1} a cikin magoya baya masu sanyaya suna haɓaka ɓarkewar zafi don daidaiton inganci koda ƙarƙashin nauyi mai nauyi.

An ƙera shi tare da rufin Class H, wannan tafsiran yana jure yanayin yanayin zafi mai tsayi, yana tallafawa haɓakar zafin jiki 100K don ingantaccen aiki na dogon lokaci{2}. Mai jituwa tare da samar da wutar lantarki na 110V, yana ba da canjin ƙarfin lantarki mai ƙarfi tare da ƙarancin ƙarancin kuzari.

Mafi dacewa don sarrafa kansa na masana'antu, tsarin makamashi mai sabuntawa, da muhimman ababen more rayuwa, busassun nau'in na'ura na mu yana ba da kulawa{1}}aiki kyauta, ingantaccen aminci (ba haɗarin gobara), da aikin eco{2} (babu mai ko hayaƙi mai guba). Haɓaka zuwa mafi wayo, ƙarin ƙarfin ƙarfin ƙarfi a yau!

 

 

 

1.2 Ƙayyadaddun Fasaha

630 kVA VPI busassun nau'in canji da takaddun bayanai

Isarwa zuwa
Afirka ta Kudu
Shekara
2025
Nau'in
Buɗe busasshiyar taswira
Babban abu
Silicon karfe takardar hatsi daidaitacce
Daidaitawa
Saukewa: IEC60076
Ƙarfin Ƙarfi
630 kVA
Yawanci
50HZ
Ƙungiyar Vector
Domin 11
Mataki
3
Nau'in Sanyi
ONAN/ONAF
Babban Voltage
11 kv
Na biyu Voltage
0.55 kV
Abubuwan Iska
Aluminum
Impedance
6%
Matsa Canji
Farashin NLTC
Taɓa Range
± 2*2.5%@gefen farko ta hanyar latsa hanyoyin haɗi
Babu Asara Load
1.1KW
Akan Rasa Load
8.3KW
Matsayin rufi
H

 

 

1.3 Zane

630 kVA VPI busassun nau'in mai canzawa zane zane da girman.

vacuum pressure impregnated transformer diagram vacuum pressure impregnated transformer nameplate

 

 

02 Masana'antu

2.1 Kori

Buɗewar busasshiyar busasshiyar mai buɗewa{0}}nau'in tafsiri yana da babban silikon karfe lamined core wanda ke yin daidaitaccen magani don rage asarar da'ira. Mabuɗin yana ɗaukar tsari mai tsauri don rage yawan asarar da aka yi a halin yanzu, haɗe tare da fasaha ta musamman don tabbatar da shiru, amo{3}}aiki kyauta.

 high-permeability silicon steel laminated core

 

2.2 Guda

vacuum pressure impregnated transformer aluminum winding

Transformer yana da madaidaicin wayoyi na aluminium rauni tare da Multi{1}}Layer SHS (Super Heat{2}}Synthetic Synthetic), mai iya jure yanayin zafi har zuwa digiri 220. Ƙirƙirar ƙira mai buɗewa ta- tana tabbatar da mafi kyawun ɓarkewar zafi yayin da ake kiyaye yanayin zafi na Class H (hawan zafin jiki 100K). Tsarin iska ya haɗu da ingantaccen kwanciyar hankali na inji tare da ingantaccen ƙarfin dielectric, yana ba da juriya mai ƙarfi ga girgiza zafin jiki, girgizawa da fitarwa na yanki.

 

2.3 Taron Karshe

1) Precision mounting of SHS-insulated coils onto CRGO cores; 2) Stepped-lamination upper yoke installation with 15-20kN/m clamping force; 3) install cooling fans and PT100 smart temperature controller (150℃ alarm/180℃ trip); 4) install terminal connections passing 5000V insulation tests (>1000MΩ).

final assembly of vip dry transformer

 

 

03 Gwaji

A'a.

Gwajin Abun

Naúrar

Dabi'un Karɓa

Ƙimar Ma'auni

Kammalawa

1

Auna juriya na iska

/

Matsakaicin juriya rashin daidaituwa

Juriya na layi: Kasa da ko daidai da 2%

HV (layi)

LV (layi)

Wuce

0.29%

0.84%

2

Auna ma'aunin ƙarfin lantarki da duba ƙaurawar lokaci

/

Haƙuri na ƙimar ƙarfin lantarki akan babban tapping: ± 1/10

Alamar haɗi: Dyn11

-0.02% ~ 0.13%

Domin 11

Wuce

3

Auna Gajerun -Tsarin Tasirin kewayawa da Rasa Load

/

kW

kW

t: 145 digiri

Z%: ƙimar da aka auna

Pk: ƙimar ƙima

Pt: ƙima mai ƙima

6.22%

4.745

6.485

Wuce

4

Auna A'a{0}}Asara da A halin yanzu a 90% da 110% na ƙimar ƙarfin lantarki

/

kW

I0 :: bayar da ma'auni darajar

P0: ba da ƙima mai ƙima

90% Ur

0.36

0.978

Wuce

100% Ur

0.40

1.087

110% Ur

0.44

1.195

5

Gwajin Karfin Wutar Lantarki

/

HV: 35kV 60s

LV: 3kV 60s

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

6

Jarrabawar Juriya da Wutar Lantarki

/

Wutar lantarki mai aiki (kV):

2 Ur

Ƙarfin wutar lantarki (kV): 1.1

Duration(s):40

Mitar (HZ): 150

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

7

Gwajin fitar da Bangaranci

pC

Matsakaicin matakin sakin juzu'i zai zama 10 pC

<10

Wuce

 

630 kVA vacuum pressure impregnated transformer test
630 kVA vacuum pressure impregnated transformer fat

 

 

04 Shiryawa da jigilar kaya

4.1 Shiryawa

Busassun nau'in tafofi yana cike cikin akwatunan katako masu ƙarfi tare da matattarar ciki don amintaccen sufuri. Duk abubuwan da suka haɗa, gami da mai sarrafa zafin jiki da magoya baya, an riga an shigar dasu{2}} azaman cikakken naúrar. A waje yana da alama a fili tare da umarnin kulawa, yana ba da ingantaccen danshi da kariyar girgiza don jigilar taswira mai nisa-.

dry type transformer packing

 

4.2 Shipping

dry type transformer shipping

Za a aika da tashar tashoshi mai busasshiyar busasshiyar busasshiyar CIF Durban Port a cikin firgici{0}}akwatin katako. Farashin ya shafi inshorar ruwa da izinin fitar da kwastam, yayin da mai karɓar zai gudanar da ka'idojin shigo da kaya. Jirgin yana kula da tsananin zafi/ sarrafa zafin jiki bisa yarda da ƙa'idodin hana lalata na duniya{3}} don jigilar teku.

 

 

05 Yanar Gizo da Takaitawa

A matsayin babban mafita{0}mafi dacewa don watsa wutar lantarki da rarrabawa, Buɗewar Buɗewar Nau'in Canjin mu yana ba da dogaro mai dorewa ga masana'antu, makamashi, da sassan kayan more rayuwa ta hanyar buɗe ido{1} ƙira, ingantaccen sarrafa zafi, da injuna mai ƙarfi. Haɗa kiyayewa{3}aiki kyauta, eco{4} gini na abokantaka, da sarrafa zafin jiki mai hankali, ya yi fice wajen neman aikace-aikace yayin da yake tallafawa maƙasudin makamashi mai dorewa. Haɗin kai tare da mu don amintattun hanyoyin samar da wutar lantarki-inda fasaha ta haɗu da aminci da inganci, ƙarfafa isar da kuzari mafi wayo.

630 kVA vpi transformer

 