1000 kVA Vpi Mai Canjawa-11 / 0.55 kV|Afirka ta Kudu 2024

1000 kVA Vpi Mai Canjawa-11 / 0.55 kV|Afirka ta Kudu 2024

Ƙasa: Afirka ta Kudu 2024
Yawan aiki: 1000kVA
Wutar lantarki: 11/0.55kV
Siffar: tare da mai sarrafa zafin jiki
Aika Aikace-aikacen

 

 

vpi transformer

VPI Dry{0}Nau'in Transformer: Sabon zaɓi don eco{1} abokantaka, inganci, kuma amintaccen watsa wutar lantarki!

 

01 Gabaɗaya

1.1 Fagen Aikin

Wannan 1000kVAvpi transformerAna fitar da shi zuwa Afirka ta Kudu a watan Yuli, 2024. Rukunin vector na wannan transformer shine Dyn11. Hanyar haɗin Dyn11, ingancin wutar lantarki mai girma, tsaka tsaki ba ya motsawa. Babban ƙarfin lantarki shine 11 kV, ƙarfin lantarki na biyu shine 0.55kV, na'urar tana sanye da kayan aikin ba tare da mai sauya kaya ba, kewayon tapping shine ± 2*2.5% a gefen farko, sanyaya shine ONAN/ONAF.

Thebusassun irin na'ura mai canzawayana da halaye na m harshen retardant tsarin, low gudu amo, haske nauyi, kananan sawun, low asara, aminci, kwanciyar hankali, high zafi juriya da kuma karfi obalodi iya aiki. Tare da kyakkyawan aikinsa ya sami karɓuwa ta kasuwar cikin gida, ana fitar da samfuran zuwa Tarayyar Turai, Arewacin Amurka, Gabas ta Tsakiya da sauran yankuna masu haɓaka tattalin arzikin duniya.

 

1.2 Ƙayyadaddun Fasaha

1000 kVA vpi ƙayyadaddun canji da takaddar bayanai

Isarwa zuwa
Afirka ta Kudu
Shekara
2024
Samfura
1000kVA-11/0.55kV
Nau'in
Buɗewar busasshiyar taswira
Daidaitawa
Saukewa: IEC60076
Ƙarfin Ƙarfi
1000kVA
Yawanci
50HZ
Mataki
3
Nau'in Sanyi
AN/AF
Babban Voltage
11kV
Na biyu Voltage
0.55kV
Abubuwan Iska
Aluminum
Impedance
6%
Matsa Canji
Farashin NLTC
Taɓa Range
± 2 * 2.5% @ gefe na farko
Babu Asara Load
1.8KW
Akan Rasa Load
9.1KW
Na'urorin haɗi
Daidaitaccen Kanfigareshan
Matsayin rufi
H
Asalin hasken wutar lantarki yana jure wa wutar lantarki{0}} gefen farko (BIL)
75kV
Mitar wuta tana jure wa wutar lantarki{0}}bangaren farko
35kV
Asalin hasken wutar lantarki mai jure wutar lantarki{0}}gefen na biyu (BIL)
/
Mitar wuta tana jure wa wutar lantarki{0}}gefen na biyu
3kV ku
Hawan zafin iska @ ƙimar sabis
100K

 

1.3 Zane

1000 kVA vpi zane zane da girman.

vpi transformer diagram

 

02 Masana'antu

2.1 Kori

The baƙin ƙarfe core rungumi dabi'ar high permeability Magnetic hatsi fuskantarwa sanyi birgima silicon karfe takardar (CRGO), cikakken oblique ba -rami dauri, gina{1}a cikin Pul farantin tsarin, daidai geometric zane, ƙayyade abu halaye na Magnetic takardar da za a yi amfani da da yawa cikakkun bayanai, ciki har da vibration iko, karkatar matsayi da sauran inji bukatun da sauran injina bukatun da sauran zane matakan, sabõda haka, da cewa shi ne bude da kuma bushe low-loader bayyanar, da cewa shi ne bude da kuma bushe low load. a'a -asara. Karancin amo.

vpi transformer CRGO core

 

2.2 Guda

vpi transformer electrical coils

Babban ƙarfin wutar lantarki yana ɗaukar tsarin jujjuyawar ci gaba, ɓarkewar zafin nada yana da kyau, ta yadda ƙarfin jujjuyawar na'urar ta zama mai ƙarfi, kuma ana sarrafa babban ƙarfin wutar lantarki da dogaro. Ƙarƙashin wutar lantarki -ƙara mai ƙarfi ne, kuma rarrabuwar zafin jiki a cikin iskar yana daidaitawa, wanda ke haɓaka kwanciyar hankali na nada kuma yana inganta gajeriyar juriyar kewayawa. Na'urar tana amfani da fenti na musamman na matsa lamba H{4}, kuma ana warkewa a babban zafin jiki, kuma saman na iya zama mai ƙura, danshi-hujja da tabo-hujja.

 

2.3 Taron Karshe

Matsayin iska: ana shigar da iska na farko da na biyu a kan tushen ƙarfe bisa ga buƙatun ƙira.

Haɗin iska: Haɗa tashar tasha bisa ga zanen lantarki don tabbatar da haɗin gwiwa ya tabbata.

Kayayyakin kayan aiki: Sanya kayan kwalliya (kamar takarda mai rufewa da man fetur) bisa ga buƙatun ƙira don tabbatar da amincin tsarin tsarin. Gwajin insulation: Ana yin gwajin juriya don tabbatar da cewa tsarin ƙirar ya dace da ƙayyadaddun fasaha.

Magoya ko masu sanyaya: Shigar da magoya bayan na'ura ko masu sanyaya don tabbatar da cewa tsarin sanyaya na iya watsar da zafi sosai.

Gyaran Shell: Sanya harsashi ko gadin na'urar a wurin don tabbatar da cewa an rufe harsashi da babban jikin na'urar.

Haɗin kebul: Haɗa manyan igiyoyi masu ƙarfi da ƙarancin wutar lantarki na gidan wuta don tabbatar da cewa haɗin lantarki yana da ƙarfi kuma ya dace da ƙa'idodin aminci.

Grounding: Yi maganin ƙasa don tabbatar da cewa tsarin ƙasa na taswirar yana da kyau.

vpi transformer final assembly

 

 

03 Gwaji

A'a.

Gwajin Abun

Naúrar

Dabi'un Karɓa

Ƙimar Ma'auni

Kammalawa

1

Auna juriya na iska

/

Matsakaicin juriya rashin daidaituwa

Juriya na layi: Kasa da ko daidai da 2%

HV (layi)

LV (layi)

Wuce

0.20%

0.98%

2

Auna ma'aunin ƙarfin lantarki da duba ƙaurawar lokaci

/

Haƙuri na ƙimar ƙarfin lantarki akan babban tapping: ± 1/10

Alamar haɗi: Dyn11

-0.03% ~ 0.09%

Domin 11

Wuce

3

Auna Gajerun -Tsarin Tasirin kewayawa da Rasa Load

/

kW

kW

t: 120 digiri

Z%: ƙimar da aka auna

Pk: ƙimar ƙima

Pt: ƙima mai ƙima

6.24%

6.28

7.909

Wuce

4

Auna A'a{0}}Asara da A halin yanzu a 90% da 110% na ƙimar ƙarfin lantarki

/

kW

I0 :  bayar da ma'auni darajar

P0: ba da ƙima mai ƙima

90% Ur

110% Ur

Wuce

0.378%

0.462%

1.3734

1.6786

5

Gwajin Karfin Wutar Lantarki

/

HV: 35kV 60s

LV: 3kV 60s

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

6

Jarrabawar Juriya da Wutar Lantarki

/

Wutar lantarki mai aiki (kV): 2 Ur

Ƙarfin wutar lantarki (kV): 1.1

Duration(s): 40

Mitar (HZ): 150

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

7

Gwajin fitar da Bangaranci

pC

Matsakaicin matakin sakin juzu'i zai zama 10 pC

<10

Wuce

 

vpi transformer testing
vpi transformer fat

 

 

04 Shiryawa da jigilar kaya

1000kva vpi transformer packing

vpi transformer shipping

 

05 Yanar Gizo da Takaitawa

Na gode don sha'awar ku akan taswirar vpi! An san samfuranmu don ƙwararrun ayyukansu, ingantaccen abin dogaro, da ƙirar ƙira waɗanda aka keɓance da buƙatu daban-daban. Ko na masana'antu, kasuwanci, ko na musamman aikace-aikace, VPI bushe{1} nau'in tasfoma yana sadar da ingantattun hanyoyin samar da wutar lantarki, aminci da dorewa{2}. Muna sa ran zama amintaccen abokin tarayya wajen tuki hanyoyin samar da wutar lantarki da kuma makoma mai dorewa. Don ƙarin bayani ko ayyuka na musamman, da fatan za a ji daɗin tuntuɓar mu a kowane lokaci!