12 kVA Dry Distribution Transformer-11 / 0.22 kV|Hadaddiyar Daular Larabawa 2025

12 kVA Dry Distribution Transformer-11 / 0.22 kV|Hadaddiyar Daular Larabawa 2025

Ƙasar Bayarwa: Hadaddiyar Daular Larabawa 2025
Yawan aiki: 12kVA
Wutar lantarki: 11000/220V
Siffar: tare da Yadi: IP20
Aika Aikace-aikacen

 

 

12 kVA dry distribution transformer

Amintaccen ƙarfi a cikin ƙaramin tsari - amintaccen injin rarraba busasshen ku

 

 

01 Gabaɗaya

1.1 Bayanin Aikin

Wannan 12 kVA Cast Resin Dry{1} Nau'in Transformer (CRT) ƙaƙƙarfan bayani ne kuma abin dogaro don ƙarancin ƙarfi{2}ƙara uku{3}} rarraba wutar lantarki. An ƙirƙira shi bisa ƙa'idodin IEC, yana fasalta nau'in hatsi{5}}madaidaicin silin karfe core da windings na jan karfe, tare da sanyaya iska (AN), babban ƙarfin lantarki na 11 kV da ƙarfin lantarki na biyu na 0.22 kV.

An sanye shi da ƙungiyar Dy11 vector da No-Load Tap Changer (NLTC) tare da ±2×2.5% daidaitawa, wannan tafsirin yana da ƙarancin kaya mara nauyi da asarar 0.09 kW da 0.39 kW. Rufin aji na B yana tabbatar da aiki mai aminci da aminci a ƙarƙashin yanayin al'ada.

A Cast Resin Transformer (CRT), wanda kuma ake kira Epoxy Cast Resin Dry -Nau'in Transformer, busasshiyar tafsiri ne{1}}. An rufe iskar da aka yi da resin epoxy. Ba ya amfani da mai ko wasu ruwaye don rufewa. Ana amfani da iska don sanyaya da kuma rufe tsakiya da iska.

Resin epoxy yana ba da kariya mai ƙarfi kuma yana dakatar da mai canzawa daga ɗaukar danshi. Wannan yana ba shi damar yin aiki da kyau a cikin m, ƙura, ko yanayi mara kyau. Ana zuba guduro a ƙarƙashin injin. Wannan yana tabbatar da cewa an rufe murhun gaba ɗaya kuma an kiyaye su. Wannan busasshiyar taswira tana da ƙarfin 12 kVA da ƙimar ƙarfin lantarki 11 kV/0.22 kV. Yana ba da ingantaccen bayani don matsakaicin matsakaici -zuwa{9}}arancin rarraba wutar lantarki.

 

 

 

1.2 Ƙayyadaddun Fasaha

12 kVA Resin jefa busassun nau'in taswira ƙayyadaddun bayanai da takaddar bayanai

Isarwa zuwa
Hadaddiyar Daular Larabawa
Shekara
2025
Nau'in
Guduro simintin busassun nau'in taswira
Core Material
Silicon karfe takardar hatsi daidaitacce
Daidaitawa
IEC
Ƙarfin Ƙarfi
12 kVA
Yawanci
50HZ
Mataki
Uku
Ƙungiyar Vector
Dy11
Nau'in Sanyi
AN
Babban Voltage
11KV
Na biyu Voltage
0.22 kV
Abubuwan Iska
Copper
Impedance
4%
Abubuwan Iska
Farashin NLTC
Impedance
2.5%
Matsa Canji
Farashin NLTC
Taɓa Range
± 2 * 2.5% @ ƙarfin lantarki na farko
Babu Asara Load
0.09 kW
Akan Rasa Load
0.39 kW
Matsayin rufi
B
Na'urorin haɗi
Mai sarrafa zafin jiki, Yadi

 

 

1.3 Zane

12kVA Resin jefa busassun nau'in taswira zane da farantin suna

12 kVA dry distribution transformer drawing 12kVA Resin cast dry type transformer nameplate

 

 

02 Masana'antu

2.1 Kori

Silicon karfe yana da kusan 3% silicon. Yana da kyakkyawan aikin maganadisu da ƙarancin hasara. Wannan yana taimakawa rage yawan igiyoyin ruwa kuma yana aiki da kyau a mafi girman mitoci. Lantattun zanen gadon siliki na siliki mai ƙima yana rage asarar eddy a halin yanzu da haɓakar maganadisu, haɓaka ƙarfin kuzari.

 

2.2 Guda

12kVA Resin cast dry type transformer winding

Wannan na'urar rarraba busasshiyar 12 kVA tana amfani da manyan masu gudanar da aikin jan karfe don babban ƙarfi da gajeriyar juriyar kewayawa. Ƙarƙashin wutar lantarki - yana amfani da ƙirar foil don tabbatar da rarraba iri ɗaya na yanzu. Na'urar taswira tana amfani da rufin Class B (digiri 130) da fasahar simintin resin epoxy don kyakkyawan danshi da juriyar ƙura, yayin da kuma ke ba da ingantaccen gajeriyar kariyar kewayawa.{7}}.

 

2.3 IP20 Bayani

Wannan busasshen na'ura na cikin gida{0} nau'in tafsiri yana da ƙayyadaddun shinge mai ƙima na IP20, yana hana hulɗa kai tsaye tsakanin yatsu da ƙaƙƙarfan abubuwa na waje da abubuwan rayuwa, yana tabbatar da amincin ma'aikaci. Har ila yau, shingen yana hana ƙura, aske ƙarfe, da sauran tarkace shiga cikin taransfoma, yana rage haɗarin rushewar rufi da zafi mai tsanani. Bugu da ƙari, shingen yana rage hayaniyar aiki kuma yana inganta yanayin gida.

12kVA dry type transformer IP20 enclosure

 

2.4 Taron Karshe

dry distribution transformer assembly

Abubuwan da aka ƙirƙira da abubuwan da aka ƙirƙira suna haɗuwa, yayin da ake yin haɗin wutar lantarki, rufewa, da gyare-gyaren tsari.
Karkashin injin, resin epoxy yana zubowa tsakanin iskoki da ainihin, yana samar da ingantaccen tsari mai warkewa.
Bayan haɗawa da warkewa, ana yin jerin gwaje-gwajen lantarki da na injina don tabbatar da cewa na'urar ta atomatik ta cika ƙa'idodin ƙira da aminci.

 

 

03 Gwaji

Matsayin Gwaji da Gwajin Na yau da kullun

IEC 60076-1-2011 Masu Canza wutar lantarki - Kashi na 1: Gabaɗaya
IEC 60076-3-2013 Masu Canza wutar lantarki - Kashi 3: Matakan rufi, gwaje-gwajen dielectric da izinin waje a cikin iska
TS EN 60076-11-2018 RLV Masu Canza wutar lantarki - Kashi 11: Busassun na'urar wuta

1. Auna juriya na iska

2. Ma'auni na ƙarfin lantarki da kuma duba ƙaurawar lokaci

3. Ma'auni na gajere - hanawa da kuma asarar kaya

4. Ma'auni na babu asarar nauyi da halin yanzu

5. Gwajin wutar lantarki da aka yi amfani da shi

6. Gwajin jurewar wutar lantarki da aka haifar

7. Gwajin fitar da bangare

 

dry distribution transformer testing
12kVA Resin cast dry type transformer testing

 

Sakamakon Gwaji

A'a.

Gwajin Abun

Naúrar

Dabi'un Karɓa

Ƙimar Ma'auni

Kammalawa

1

Auna juriya na iska

/

Matsakaicin juriya rashin daidaituwa

Juriya na layi: Kasa da ko daidai da 2%

HV (layi)

LV (layi)

Wuce

0.68%

0.53%

2

Auna ma'aunin ƙarfin lantarki da duba ƙaurawar lokaci

/

Haƙuri na ƙimar ƙarfin lantarki akan babban tapping: ± 1/10

Alamar haɗi: Dy11

0.01% ~ 0.12%

Dy11

Wuce

3

Auna Gajerun -Tsarin Tasirin kewayawa da Rasa Load

/

kW

kW

t: 100 digiri

Z%: ƙimar da aka auna

Pk: ƙimar ƙima

Pt: ƙima mai ƙima

3.64%

0.259

0.317

Wuce

4

Auna A'a{0}}Asara da A halin yanzu a 90% da 110% na ƙimar ƙarfin lantarki

/

kW

I0 :: bayar da ma'auni darajar

P0: ba da ƙima mai ƙima

90% Ur

2.88

0.083

Wuce

100% Ur

3.21

0.093

110% Ur

3.53

0.102

5

Gwajin Karfin Wutar Lantarki

/

HV: 28kV 60s

LV 3kV 60s

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

6

Jarrabawar Juriya da Wutar Lantarki

/

Wutar lantarki mai aiki (KV):

2 Ur

Ƙarfafa ƙarfin lantarki (KV): 0.44

Duration(s):40

Mitar (HZ): 150

Babu rushewar ƙarfin gwajin da ke faruwa

Wuce

7

Gwajin fitar da Bangaranci

pC

Matsakaicin matakin sakin juzu'i zai zama 10 pC

<10

Wuce

 

 

04 Shiryawa da jigilar kaya

 
12kVA Resin cast dry type transformer packing 12kVA Resin cast dry type transformer shipping

05 Yanar Gizo da Takaitawa

A cikin gine-ginen masana'antu da kasuwanci, ingantaccen wutar lantarki yana da matukar muhimmanci. Scotech 12 kVA Cast Resin Dry-Nau'in Canja-canje (CRT) yana ba da amintaccen matsakaicin matsakaici{3}} zuwa ƙananan- ƙarfin lantarki.

Yana da iskar jan karfe da silikon karfe core. An rufe iskar da aka cika da resin epoxy da iska{1}} sanyaya, don haka ba a buƙatar mai. Gudun yana kare kariya daga danshi da ƙura, yana ba da damar yin amfani da dogon lokaci a cikin yanayi mara kyau.

Yana da ƙungiyar Dy11 vector da No{1}Load Tap Changer (NLTC) don daidaita wutar lantarki mai sassauƙa. Ƙananan babu - ɗora nauyi da asarar nauyi yana sa shi inganci. Rukunin IP20 yana kiyaye mutane lafiya kuma yana hana ƙura shiga, yayin da kuma yana rage hayaniya a cikin gida.

12kVA Resin cast dry type transformer with enclosure

 